Model: 4009-9201

1. Introduction

This manual provides essential information for the proper installation, operation, and maintenance of the SIMPLEX 4009-9201 Notification Appliance Circuit (NAC) Extender. This device is designed to expand the capacity of existing fire alarm systems by providing additional supervised and synchronized NACs.

It is imperative that all personnel involved in the installation, testing, and maintenance of this equipment read and understand the contents of this manual completely before proceeding. Adherence to all local and national electrical codes, as well as fire safety regulations, is mandatory.

Front view of the SIMPLEX 4009-9201 NAC Extender enclosure.

Figure 1: Front view of the SIMPLEX 4009-9201 NAC Extender enclosure. The unit is a rectangular metal box, light gray in color, with ventilation slots at the top and bottom. A black label across the center reads "4009 IDNet NAC EXTENDER" with the Simplex logo.

2. Safety Information

WARNING: Installation and servicing of this equipment must be performed by qualified personnel only. Disconnect all power before servicing.

  • Always disconnect AC power and battery power before installing, servicing, or removing the unit.
  • Ensure proper grounding of the unit as per local electrical codes.
  • Do not expose the unit to moisture or extreme temperatures.
  • Use only manufacturer-approved replacement parts.
  • Verify all wiring connections are secure and correct before applying power.

3. Product Features

The SIMPLEX 4009-9201 NAC Extender is designed to provide reliable and expandable notification appliance circuit capabilities for fire alarm systems. Key features include:

  • Expansion of Notification Appliance Circuits (NACs).
  • Supervised circuits for integrity monitoring.
  • Synchronization capabilities for connected notification appliances.
  • Robust enclosure for industrial and commercial environments.

4. Setup and Installation

Installation of the SIMPLEX 4009-9201 NAC Extender requires careful attention to wiring and system integration. It is recommended that installation be performed by a certified fire alarm technician.

4.1 Unpacking and Inspection

Upon receiving the unit, carefully inspect the packaging for any signs of damage. Open the package and verify that all components are present and undamaged. Report any discrepancies to your supplier immediately.

4.2 Mounting

Mount the NAC Extender securely to a wall or suitable surface in a dry, protected area, away from direct sunlight and heat sources. Ensure adequate ventilation around the unit.

4.3 Wiring Connections

Refer to the internal wiring diagram and system schematics for precise connection details. All wiring must comply with NFPA 70 (National Electrical Code) and NFPA 72 (National Fire Alarm and Signaling Code), as well as all local authority having jurisdiction (AHJ) requirements.

Internal view of the SIMPLEX 4009-9201 NAC Extender with wiring diagram.

Figure 2: Internal view of the SIMPLEX 4009-9201 NAC Extender. The enclosure door is open, revealing the main circuit board, a large transformer, and various wiring connections. A detailed wiring and configuration diagram is affixed to the inside of the door.

Close-up of the internal components of the SIMPLEX 4009-9201 NAC Extender.

Figure 3: Close-up view of the internal components of the SIMPLEX 4009-9201 NAC Extender. This image highlights the main circuit board with various electronic components, capacitors, and relays, alongside the large toroidal transformer and associated wiring.

  • Connect the AC power input to a dedicated, unswitched circuit as specified in the technical specifications.
  • Connect the battery backup terminals to appropriate standby batteries (if applicable) to ensure continuous operation during power outages.
  • Connect the NAC outputs to the notification appliances (horns, strobes, speakers) ensuring proper polarity and supervision.
  • Connect the input from the fire alarm control panel (FACP) to the designated terminals.

4.4 Power-Up and Initial Test

After all wiring is complete and verified, apply AC power to the unit. Observe any status indicators for normal operation. Perform initial system tests as per the FACP manufacturer's instructions and relevant fire codes to ensure all connected NACs and appliances function correctly.

5. Operating Instructions

The SIMPLEX 4009-9201 NAC Extender operates in conjunction with a compatible fire alarm control panel (FACP). Its primary function is to receive signals from the FACP and activate connected notification appliances.

5.1 Normal Operation

Under normal conditions, the NAC Extender will be in a standby state, supervising its connected circuits. Status indicators (if present) should show a normal, non-alarm condition.

5.2 Alarm Activation

Upon receiving an alarm signal from the FACP, the NAC Extender will activate its connected notification appliances according to the programmed sequence (e.g., continuous, temporal 3, synchronized). The unit will continue to power the appliances until the alarm condition is cleared by the FACP.

5.3 Trouble Conditions

The NAC Extender continuously monitors its circuits for trouble conditions such as open circuits, short circuits, or ground faults. If a trouble condition is detected, the unit will typically send a signal back to the FACP, and a local trouble indicator may illuminate.

6. Maintenance

Regular maintenance is crucial for the reliable operation of the SIMPLEX 4009-9201 NAC Extender and the overall fire alarm system.

  • Annual Inspection: Have a qualified technician inspect the unit annually as part of the overall fire alarm system inspection.
  • Battery Check: If equipped with battery backup, check battery terminals for corrosion and test battery voltage and capacity regularly as per NFPA 72 guidelines. Replace batteries as needed.
  • Cleaning: Keep the exterior of the unit clean and free of dust. Do not use abrasive cleaners or solvents.
  • Wiring Integrity: Periodically check all wiring connections for tightness and signs of wear or damage.

7. Troubleshooting

This section provides basic troubleshooting steps for common issues. For complex problems, contact a qualified fire alarm technician.

ProblemPossible CauseSolution
NAC Extender not powering on.No AC power; Blown fuse; Disconnected battery.Check AC power source; Inspect and replace fuse if necessary (ensure power is off); Verify battery connections.
Trouble indicator illuminated.Open circuit on NAC; Short circuit on NAC; Ground fault; Low battery.Inspect NAC wiring for breaks or shorts; Check for ground faults; Test and replace battery if low.
Notification appliances not activating.No alarm signal from FACP; Wiring error on NAC output; Faulty appliance.Verify FACP is in alarm; Check NAC output wiring; Test individual appliances.

8. Specifications

The following specifications apply to the SIMPLEX 4009-9201 NAC Extender:

SpecificationValue
Model Number4009-9201
ManufacturerSIMPLEX
UPC643485653868
Maximum Input Voltage120 Volts (AC)
Minimum Input Voltage100 Volts (AC)
Item Dimensions (L x W x H)17 x 20 x 8 inches
Item Weight22.9 Pounds
Cooling MethodAir
Form FactorATX
Connector TypeATX
Shipping label for the SIMPLEX 4009-9201 NAC Extender.

Figure 4: Shipping label for the SIMPLEX 4009-9201 NAC Extender. The label displays the PID: 4009-9201, Description: NAC EXTENDER 120VAC, IDNET, Part No. 0636867, and Serial Number information.

9. Warranty and Support

The SIMPLEX 4009-9201 NAC Extender is covered by the manufacturer's standard warranty. For specific warranty terms and conditions, please refer to the documentation provided with your purchase or contact SIMPLEX directly.

For technical support, service, or to report issues, please contact your authorized SIMPLEX distributor or the manufacturer's customer service department. Always provide the model number (4009-9201) and serial number of your unit when seeking support.

Related Documents - 4009-9201

Preview Simplex 4009 IDNet NAC Extender Installation and Operation Guide
Comprehensive guide for installing and configuring the Simplex 4009 IDNet Notification Appliance Circuit (NAC) Extender. Covers hardware components, system configuration, wiring, and operational modes for fire alarm systems.
Preview Simplex 4090-9007 IDNet Signal IAM: Addressable Module for Fire Alarm Systems
Detailed technical specifications and features for the Simplex 4090-9007 IDNet Signal Individual Addressable Module (IAM), designed for enhanced selective signaling and audio control in Simplex 4100ES, 4010ES, 4100U, and 4008 Series fire alarm control panels. Includes wiring, operation, and mounting information.
Preview Simplex 4008/4006-9801 Expansion Power Supply (EPS) Installation Guide
Installation instructions for the Simplex 4008/4006-9801 Expansion Power Supply (EPS), detailing mounting, panel interconnections, NAC wiring, auxiliary power, and NAC ratings for fire alarm systems.
Preview Simplex 4010ES: Systèmes de commande d'extinction automatique pour gicleurs
Guide technique Simplex 4010ES détaillant les modules de commande pour les systèmes d'extinction automatique par gicleurs, couvrant les modes déluge et préventif, avec spécifications, homologations et schémas de câblage.
Preview Simplex IDNet Signal IAM Installation Instructions
Detailed installation instructions for the Simplex 4090-9007 IDNet Addressable Signal Individual Adapter Module (Signal IAM), covering address setting, wiring configurations for Class A and Class B Notification Appliance Circuits (NACs), and mounting procedures. This guide provides essential information for integrating the Signal IAM with fire alarm control panels and notification appliances.
Preview Simplex 4010ES Fire Alarm System Installation Guide
This installation guide provides comprehensive instructions for the Simplex 4010ES Fire Alarm System, covering standalone and networked configurations, hardware components, wiring, and system checkout procedures.