1. Introduction
This manual provides essential information for the proper installation, operation, and maintenance of the Notifier FMM-1 Monitor Module. The FMM-1 is designed to monitor a circuit of normally open contact devices in a fire alarm system. It is an integral component for ensuring the safety and reliability of your fire detection system.
2. Safety Information
Always adhere to local codes, standards, and regulations when installing and maintaining fire alarm equipment. Installation and servicing should only be performed by qualified personnel. Disconnect all power before servicing. Failure to follow these instructions may result in property damage, serious injury, or death.
- Ensure power is disconnected before installation or maintenance.
- Follow all wiring diagrams and instructions provided by Notifier.
- Do not operate the module outside its specified environmental limits.
- Keep the module clean and free from dust and debris.
3. Product Description and Features
The Notifier FMM-1 is a compact monitor module designed for use with Notifier intelligent fire alarm control panels. It provides a single initiating device circuit (IDC) for monitoring normally open contact devices such as manual pull stations, waterflow switches, or supervisory switches. The module communicates with the control panel using the FlashScan protocol, allowing for fast and reliable communication.

Figure 3.1: Front view of the Notifier FMM-1 Monitor Module, showing its compact design and terminal connections.

Figure 3.2: Multiple Notifier FMM-1 Monitor Modules packaged in a box, indicating new, original packaging.
4. Installation and Setup
The FMM-1 module is typically installed in a standard 4-inch square electrical box. It is designed for surface or flush mounting. Refer to the specific wiring diagrams provided with your Notifier fire alarm control panel for detailed connection instructions.
4.1 Wiring
Connect the module to the Signaling Line Circuit (SLC) of the fire alarm control panel and to the initiating device circuit (IDC) according to the system's design and Notifier's documentation. Ensure proper polarity and termination for all connections.
4.2 Addressing
Each FMM-1 module must be assigned a unique address on the SLC loop using the rotary switches on the module. Consult your control panel's manual for valid address ranges and programming procedures.
Video 4.1: An overview of the Notifier FMM-1 Monitor Module, showcasing its physical appearance and key features. This video provides a visual guide to the module's design.
5. Operating Instructions
Once properly installed and addressed, the FMM-1 module operates automatically as part of the fire alarm system. It continuously monitors the connected initiating device circuit for changes in state (e.g., a pull station being activated, a waterflow switch closing). Upon detecting an alarm or supervisory condition, the module transmits this information to the fire alarm control panel, which then initiates the appropriate system response.
6. Maintenance
Regular maintenance is crucial for the reliable operation of the FMM-1 module and the overall fire alarm system. Refer to NFPA 72 (National Fire Alarm and Signaling Code) and local authority having jurisdiction (AHJ) requirements for specific testing and maintenance schedules.
- Annual Inspection: Visually inspect the module and its connections for any signs of damage, corrosion, or loose wiring.
- Functional Testing: Periodically test the initiating devices connected to the FMM-1 to ensure they properly trigger an alarm or supervisory signal at the control panel.
- Cleaning: If necessary, gently clean the module's exterior with a soft, dry cloth. Do not use abrasive cleaners or solvents.
7. Troubleshooting
If the FMM-1 module or its associated circuit is indicating a fault condition on the fire alarm control panel, consider the following:
| Problem | Possible Cause | Solution |
|---|---|---|
| Module Fault/Trouble | Incorrect wiring, short circuit, open circuit on IDC, incorrect addressing, module failure. | Verify wiring connections and polarity. Check for shorts or opens on the IDC. Confirm correct address setting. If issues persist, replace the module. |
| No Response from Device | Device not properly connected, device failure, wiring issue on IDC. | Check connections at the initiating device and the FMM-1. Test the initiating device independently. Inspect IDC wiring for breaks or damage. |
For complex issues, contact a certified fire alarm technician or Notifier technical support.
8. Specifications
- Brand: Notifier
- Model: FMM 1
- Part Number: FMM-1
- UPC: 643485653585
- Manufacturer: NOTIFIER
- Item Weight: 5.6 ounces
- Package Dimensions: 6.5 x 5.75 x 1.9 inches
- Color: Ivery
- Date First Available: August 28, 2015
9. Warranty and Support
For warranty information and technical support, please refer to the official Notifier website or contact your authorized Notifier distributor. Keep your purchase receipt for warranty claims.
Notifier Official Website: www.notifier.com