Danfoss 034N0082

Instruction Manual for Danfoss 034N0082 Hot Gas Bypass Regulator

Model: 034N0082

1. Introduction

This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Danfoss 034N0082 Hot Gas Bypass Regulator. This device is designed for capacity control in refrigeration and air conditioning systems, ensuring stable evaporator pressure during periods of low load.

Please read this manual thoroughly before installing or operating the regulator to ensure proper function and to prevent damage or injury.

2. Safety Information

Always observe general safety precautions when working with refrigeration systems and components. Only qualified personnel should install, service, or troubleshoot this equipment.

3. Product Overview

The Danfoss 034N0082 is a CPCE series hot gas bypass regulator designed to maintain a constant evaporator pressure by bypassing hot gas from the discharge side of the compressor to the evaporator inlet. This prevents evaporator icing and ensures stable operation during low-load conditions.

Danfoss 034N0082 Hot Gas Bypass Regulator in its original packaging

Figure 3.1: The Danfoss 034N0082 Hot Gas Bypass Regulator shown alongside its cardboard packaging. The packaging features the Danfoss logo and product identification labels, indicating the model number and capacity.

Close-up view of the Danfoss 034N0082 regulator's label

Figure 3.2: A detailed close-up of the regulator's label, clearly displaying "REFRIGERANT HOT-GAS BYPASS REGULATOR", "Type CPCE", and "RANGE 0-6 bar / 0-85 psig". This label provides critical operational parameters and identification.

Side view of the Danfoss 034N0082 Hot Gas Bypass Regulator

Figure 3.3: A side profile view of the Danfoss 034N0082 regulator, highlighting its brass body and copper solder connections. The compact design and connection points are visible, indicating its readiness for integration into a refrigeration line.

4. Installation

Proper installation is crucial for the optimal performance and longevity of the hot gas bypass regulator. Follow these steps carefully:

  1. System Depressurization: Ensure the refrigeration system is completely depressurized and isolated before beginning installation.
  2. Location: Install the regulator in the hot gas line between the compressor discharge and the evaporator inlet. Ensure there is sufficient space for servicing.
  3. Flow Direction: Observe the flow arrow on the regulator body to ensure correct installation direction. Hot gas should flow into the regulator from the compressor side.
  4. Connection: The 034N0082 features 1/2" CPCE solder connections. Use appropriate soldering techniques and materials to create leak-free joints. Protect the valve body from excessive heat during soldering to prevent internal damage.
  5. Mounting: The regulator can be mounted in any position, but ensure it is securely supported to prevent vibration and stress on the piping.
  6. Leak Test: After installation, evacuate the system and perform a thorough leak test using an appropriate leak detection method.
  7. Refrigerant Charge: Recharge the system with the correct type and amount of refrigerant as specified by the system manufacturer.

5. Operation

The Danfoss 034N0082 Hot Gas Bypass Regulator operates automatically to maintain a minimum evaporator pressure. When the evaporator load decreases, the suction pressure tends to drop. The regulator senses this pressure drop and opens to allow hot gas from the compressor discharge to bypass directly into the evaporator inlet.

This injection of hot gas raises the evaporator pressure, preventing it from falling below the set point and thus avoiding evaporator icing and ensuring stable system operation. The regulator modulates its opening to precisely match the system's capacity requirements.

6. Maintenance

The Danfoss 034N0082 regulator is designed for long-term, reliable operation with minimal maintenance. However, regular system checks are recommended:

Note: Internal components of the regulator are not user-serviceable. In case of malfunction, the unit should be replaced by a qualified technician.

7. Troubleshooting

This section provides guidance for common issues that may arise. Always ensure safety precautions are followed before attempting any troubleshooting.

ProblemPossible CauseSolution
Evaporator pressure too low / IcingRegulator not opening or set point too low. Insufficient hot gas supply.Check system charge. Verify regulator is installed correctly. If regulator is faulty, replace it.
Evaporator pressure too high / OverheatingRegulator stuck open or set point too high.Check for debris in the valve. If regulator is faulty, replace it.
Leaks at connectionsImproper soldering or damaged connections.Locate leak using leak detector. Repair or re-solder connections. If valve body is cracked, replace unit.

8. Specifications

AttributeValue
Model Number034N0082
Product TypeHot Gas Bypass Regulator
Connection Type1/2" CPCE Solder
Pressure Range0-6 bar / 0-85 psig
Maximum Working Pressure (MWP)312 psig
Compatible RefrigerantsR12, R22, R134a, R404A, R507, R407C, R410A
ManufacturerDanfoss
Product Dimensions9 x 7 x 5 inches
Product Weight5 Pounds

9. Warranty and Support

For specific warranty terms and conditions, please refer to the documentation provided with your purchase or contact the authorized Danfoss distributor or seller from whom the product was acquired. Warranty coverage typically applies to defects in materials and workmanship under normal use.

For technical support, product inquiries, or to locate an authorized service center, please visit the official Danfoss website or contact their customer service department. You can also find more information on the Danfoss Store on Amazon.

Related Documents - 034N0082

Preview Danfoss CPCE Hot Gas Bypass Regulator & LG Liquid Gas Mixer Installation Guide
Installation guide for the Danfoss CPCE hot gas bypass regulator and LG liquid gas mixer. Covers approved refrigerants, technical specifications, system diagrams, and installation notes for refrigeration systems.
Preview Danfoss ERC 214 Digital Regulator Installation Guide
Comprehensive installation guide for the Danfoss ERC 214 digital regulator, detailing its features, user interface, quick-start configuration, basic functions, technical data, and parameter settings for refrigeration and defrosting applications.
Preview Danfoss ERC 213 Electronic Refrigeration Control Installation Guide
Installation guide for the Danfoss ERC 213 electronic refrigeration controller, detailing its technical highlights, user interface, dimensions, electrical connections, and parameter settings for commercial refrigeration applications.
Preview Designing Transcritical CO2 Refrigeration Systems: A Guide for Light Commercial Applications
A comprehensive guide from Danfoss on designing and optimizing transcritical refrigeration systems using carbon dioxide (CO2) for light commercial applications. It covers system basics, cycle processes, component design, safety considerations, and handling procedures.
Preview Danfoss EKC 367: Instructions and Operation Guide
Comprehensive instructions and operational guide for the Danfoss EKC 367 electronic refrigeration controller, covering installation, connections, parameters, and troubleshooting.
Preview Danfoss AK-PC 781A: Kapacitetsregulator med Värmeåtervinningsfunktion - Användarguide
Denna användarguide beskriver Danfoss AK-PC 781A, en avancerad kapacitetsregulator med värmeåtervinningsfunktion för kylsystem. Upptäck dess funktioner för optimerad prestanda, energieffektivitet och flexibel integration.