1. Introduction
This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Schneider Electric Osisense XS130B3PAL2 Inductive Proximity Sensor. Please read this manual thoroughly before using the product.

Figure 1: Schneider Electric Osisense XS130B3PAL2 Inductive Proximity Sensor. A detailed view of the cylindrical brass housing, M30 threading, and pre-wired cable connection.
2. General Information
The Schneider Electric Osisense XS130B3PAL2 is a cylindrical inductive proximity sensor designed for general-purpose industrial applications. It features a robust nickel-plated brass housing and a PPS sensing face, ensuring durability and reliable performance in challenging environments.
Key Features:
- Model: XS130B3PAL2
- Sensor Type: Inductive Proximity Sensor
- Housing: Cylindrical, M30, L45mm, Nickel-plated Brass
- Sensing Face: PPS
- Sensing Range (Sn): 15 mm
- Supply Voltage: 12-24 V DC
- Output Type: 3-wire, NO (Normally Open), PNP
- Connection: Pre-wired cable (2 meters length)
- Protection Ratings: IP65, IP68, IP69K
- Operating Temperature: -25°C to +70°C
- Indication: Annular LED for status visualization
- Certifications: E2, CSA, UL
3. Safety Instructions
Always adhere to the following safety guidelines to prevent injury and damage to the equipment:
- Disconnect power before installation, wiring, or maintenance.
- Ensure proper grounding to prevent electrical shock.
- Do not exceed the specified supply voltage (12-24 V DC).
- Avoid exposing the sensor to corrosive substances or extreme mechanical stress beyond its ratings.
- Installation and wiring should be performed by qualified personnel only.
- Verify all connections are secure before applying power.
- This device features double insulation for enhanced protection against electric shocks.
4. Installation
The XS130B3PAL2 sensor is designed for flush mounting and can be installed directly onto a metallic surface or support.
Mounting Steps:
- Identify the desired mounting location. Ensure sufficient clearance for the sensor body and cable.
- Drill a hole of appropriate diameter (Ø 30 mm) for the M30 x 1.5 thread.
- Insert the sensor into the drilled hole.
- Secure the sensor using the two provided nuts on the external thread. Tighten firmly but do not overtighten to avoid damaging the housing.
- Ensure the sensing face is flush with the mounting surface for optimal performance.
Note: For non-flush mounting applications, consult the product datasheet for specific mounting distances and considerations to prevent mutual interference between sensors or with metallic objects.
5. Wiring
The XS130B3PAL2 is a 3-wire, PNP, Normally Open (NO) sensor with a 2-meter pre-wired cable. Follow the wiring diagram below:
- Brown Wire: Connect to +12-24 V DC (Power Supply Positive)
- Blue Wire: Connect to 0 V DC (Power Supply Negative / Ground)
- Black Wire: Connect to Load (Output Signal)
Ensure all connections are correct and secure before applying power. Incorrect wiring can damage the sensor or connected equipment.
6. Operation
Once properly installed and wired, the sensor is ready for operation. When a metallic object enters the sensing range (15 mm), the sensor's output will switch states.
Sensing Indication:
The sensor features an annular LED indicator. This LED illuminates when a target object is detected within the sensing range, providing visual confirmation of operation and aiding in configuration and troubleshooting.
Sensing Principle:
Inductive proximity sensors generate an electromagnetic field. When a metallic object enters this field, it causes a change in the field, which the sensor detects, triggering its output. The nickel-plated brass housing provides magnetic shielding, enhancing precision and immunity to external magnetic disturbances.
7. Maintenance
The Schneider Electric Osisense XS130B3PAL2 sensor is designed for minimal maintenance. Regular inspection can help ensure long-term reliable operation.
- Cleaning: Periodically clean the sensing face to remove dust, dirt, or debris that may accumulate and affect performance. Use a soft, damp cloth. Do not use abrasive cleaners or solvents.
- Cable Inspection: Check the cable for any signs of damage, such as cuts, abrasions, or kinks. Replace the sensor if the cable is damaged.
- Mounting Security: Ensure the sensor remains securely mounted. Vibrations or impacts can loosen mounting nuts over time.
- Environmental Conditions: Verify that the operating environment remains within the specified temperature range (-25°C to +70°C) and that the IP protection ratings are not compromised.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Sensor not detecting object |
|
|
| LED not illuminating |
|
|
| Intermittent detection |
|
|
9. Specifications
| Manufacturer | Schneider Electric |
| Model Number | XS130B3PAL2 |
| Sensor Type | Inductive Proximity Sensor |
| Housing Dimensions (L x W x H) | 13.1 x 9.5 x 4.2 cm |
| Weight | 20 grams |
| Housing Material | Nickel-plated Brass |
| Sensing Face Material | PPS |
| Mounting Type | Flush, M30 x 1.5 thread, Pole mount |
| Nominal Sensing Distance (Sn) | 15 mm |
| Supply Voltage | 12-24 V DC |
| Output Type | 3-wire, NO (Normally Open), PNP |
| Connection | Pre-wired cable (2 meters) |
| Protection Rating | IP65, IP68, IP69K |
| Operating Temperature Range | -25°C to +70°C |
| Certifications | E2, CSA, UL |
| Recommended Uses | Industrial automation and machine control |
| Compatible Devices | Security systems |
10. Warranty and Support
Information regarding specific warranty terms and conditions for the Schneider Electric Osisense XS130B3PAL2 Inductive Proximity Sensor is not provided in this document. For detailed warranty information and technical support, please refer to the official Schneider Electric website or contact their customer service directly.
Components included: Product and instructions (French not guaranteed). Spare parts availability: Information unavailable on spare parts.
Ask a question about this manual
Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.