1. Introduction
The Potter VSR-S is a vane-type waterflow switch designed for use in wet sprinkler systems. It is compatible with 1" (25mm), 1-1/4" (32mm), 1-1/2" (38mm), and 2" (50mm) pipe sizes. This device can also function as a sectional waterflow detector in larger systems. It features two single-pole, double-throw (SPDT) snap-action switches and an adjustable, instantly recycling pneumatic retard. The switches activate when a water flow of 10 gallons per minute (38 LPM) or more is detected downstream of the device. The flow condition must persist for a duration sufficient to overcome the selected retard period.
This manual provides essential information for the safe and effective installation, operation, and maintenance of your Potter VSR-S waterflow switch.
2. Safety Information
Read all instructions carefully before installation and operation. Failure to follow these instructions may result in property damage, serious injury, or death.
- Installation must be performed by qualified personnel in accordance with all national and local codes and standards.
- Ensure power is disconnected before performing any wiring or maintenance to prevent electrical shock.
- Do not exceed the specified electrical ratings of the switch.
- Protect the device from physical damage during installation and operation.
- Verify proper operation after installation and periodically thereafter.
3. Setup and Installation
The VSR-S switch is designed for horizontal or vertical pipe installation. Ensure the arrow on the switch housing points in the direction of water flow.
3.1 Mounting Location
- Install the switch in an accessible location for maintenance and inspection.
- Avoid locations where water turbulence is excessive, such as immediately after a pump or elbow.
- Ensure sufficient clearance around the device for wiring and cover removal.
3.2 Mechanical Installation
- Drain the pipe system completely before beginning installation.
- Drill a hole in the pipe at the desired location, ensuring it is clean and free of burrs. Refer to the template provided with the product for precise hole size.
- Insert the vane into the pipe, ensuring the arrow on the saddle points in the direction of water flow.
- Secure the switch saddle to the pipe using the provided U-bolt and nuts. Tighten nuts evenly to ensure a watertight seal.
- Verify that the vane moves freely within the pipe and does not obstruct water flow.

Figure 1: Potter VSR-S Vane-Type Waterflow Switch. This image shows the red housing of the switch connected to a brass pipe fitting, with the white vane extending downwards, ready for insertion into a pipe. The overall design indicates a robust and functional component for water flow detection.
3.3 Electrical Wiring
- Ensure all power to the circuit is OFF before wiring.
- Open the switch cover.
- Connect wiring to the appropriate terminals as per the system's electrical diagram. The VSR-S features two SPDT contacts.
- Use proper conduit and wiring methods as required by local codes.
- Close the switch cover securely after wiring is complete.
3.4 Retard Adjustment
The VSR-S includes an adjustable pneumatic retard to prevent false alarms due to pressure surges. The retard time can be adjusted from 0 to 90 seconds.
- To adjust, locate the retard adjustment screw inside the switch housing.
- Turn the screw clockwise to increase the retard time and counter-clockwise to decrease it.
- Test the switch after adjustment to ensure the desired delay is achieved.
4. Operating Instructions
Once installed and wired, the VSR-S operates automatically. When water flow exceeding 10 GPM (38 LPM) is detected and sustained for the set retard period, the internal switches will activate.
- The switch contacts will change state, typically signaling an alarm panel or control system.
- The switch will reset automatically when the water flow drops below the activation threshold and the retard period expires.
5. Maintenance
Regular maintenance ensures the reliable operation of your VSR-S waterflow switch.
5.1 Routine Inspection
- Inspect the switch annually for any signs of physical damage, corrosion, or loose connections.
- Ensure the housing cover is securely fastened.
5.2 Functional Testing
- Test the waterflow switch periodically as required by local codes and NFPA standards (e.g., quarterly or semi-annually).
- Initiate a water flow condition (e.g., by opening an inspector's test valve) to activate the sprinkler system.
- Verify that the VSR-S activates within the specified retard time and sends a signal to the alarm panel.
- Confirm that the alarm panel receives and processes the signal correctly.
- After testing, ensure the system is returned to its normal operating state.
6. Troubleshooting
This section addresses common issues you might encounter with the VSR-S waterflow switch.
| Problem | Possible Cause | Solution |
|---|---|---|
| Switch does not activate with water flow. |
|
|
| False alarms or intermittent activation. |
|
|
| No signal to alarm panel. |
|
|
7. Specifications
| Feature | Detail |
|---|---|
| Model | VSR-S |
| Brand | Potter Electric Signal |
| Operation Mode | Automatic |
| Contact Type | Normally Open, Normally Closed (SPDT) |
| Connector Type | Screw Terminal |
| Actuator Type | Vane |
| Contact Material | Copper |
| Number of Positions | 4 |
| Control Method | Touch (likely referring to manual test/reset, or general system control) |
| Unit Count | 1.0 Count |
| Item Weight | 2 pounds |
| Package Dimensions | 11 x 6 x 3 inches |
| UPC | 785192014324 |
8. Warranty and Support
For warranty information and technical support, please contact Potter Electric Signal directly or refer to their official website. Keep your purchase receipt for warranty claims.
- Manufacturer: POTTER ELECTRIC SIGNAL COMPANY
- Website: www.pottersignal.com