Johnson Controls P70AA-118C

Johnson Controls P70AA-118C Condenser Fan Cycling Control

Model: P70AA-118C | Brand: Johnson Controls

1. Introduction and Overview

The Johnson Controls P70AA-118C is a robust pressure control designed for commercial refrigeration and air conditioning applications. Its primary functions include high pressure cut-out control, head-pressure control, and condenser fan cycling. This control is compatible with most common non-corrosive refrigerants and can also be utilized in other non-corrosive fluid applications. It features a single-pole, single-throw (SPST) switch configuration and is designed for a pressure range of 100 to 400 psi.

Johnson Controls P70AA-118C control unit, packaging, and mounting bracket.

Figure 1: Johnson Controls P70AA-118C control unit, packaging, and mounting bracket.

The P70AA-118C control unit and its dedicated mounting bracket.

Figure 2: The P70AA-118C control unit and its dedicated mounting bracket.

2. Key Features

  • All-steel case and cover: Provides long-lasting, rugged protection for internal components, ensuring durability in demanding environments.
  • Sight-set calibrated pressure adjustment: Features a visible pressure scale that is fully adjustable through the range without requiring removal of the cover (on NEMA 1 enclosure models), simplifying setup.
  • Manual reset lockout option: Offers a trip-free lockout mechanism that prevents overriding or resetting until the pressure returns to the specified safe level, enhancing system safety.
  • Variety of available pressure connection styles: Allows for greater flexibility during mounting and adaptation of pressure connections to various field application requirements.
Close-up of the control's front panel, showing the pressure adjustment scale and differential settings.

Figure 3: Close-up of the control's front panel, showing the pressure adjustment scale and differential settings.

3. Specifications

SpecificationValue
Model NumberP70AA-118C
BrandJohnson Controls
Pressure Range100 to 400 psi
Capillary Length36 inches
Flare Nut Size1/4 inch
Switch TypeSingle-Pole, Single-Throw (SPST)
MaterialSteel
Item Weight1.49 Pounds
Product Dimensions10.25 x 2.75 x 4.37 inches
Display TypeAnalogue
ManufacturerJohnson Controls
Date First AvailableOctober 11, 2012
Detailed product label from the packaging, showing specifications including pressure range, differential, and capillary length.

Figure 4: Detailed product label from the packaging, showing specifications including pressure range, differential, and capillary length.

4. Installation

Installation of the P70AA-118C control should be performed by a qualified HVAC technician or electrician in accordance with all local and national electrical codes. Ensure the power supply to the system is disconnected before beginning any installation work.

4.1 Mounting

Mount the control unit in a location that is easily accessible for adjustments and maintenance, yet protected from physical damage and excessive vibration. Use the provided mounting bracket and appropriate fasteners to secure the unit firmly.

Underside view of the P70AA-118C control unit, showing mounting points and electrical conduit entry.

Figure 5: Underside view of the P70AA-118C control unit, showing mounting points and electrical conduit entry.

4.2 Capillary Tube Connection

Carefully route the 36-inch capillary tube to the desired pressure sensing point. Avoid sharp bends or kinks that could damage the tube. Connect the 1/4 inch flare nut to the system's pressure port, ensuring a tight, leak-free seal. Do not overtighten.

Angled view of the P70AA-118C control, highlighting the capillary tube connection.

Figure 6: Angled view of the P70AA-118C control, highlighting the capillary tube connection.

Detail of the capillary tube and 1/4 inch flare nut connection.

Figure 7: Detail of the capillary tube and 1/4 inch flare nut connection.

4.3 Electrical Wiring

Refer to the wiring diagram provided with the control unit or the system's specific schematics. Connect the electrical wiring to the appropriate terminals within the control's enclosure. Ensure all connections are secure and properly insulated. The P70AA-118C is a single-pole, single-throw (SPST) control.

5. Operating Instructions

Once installed and wired, the P70AA-118C control can be adjusted to the desired operating parameters. The control features a sight-set calibrated pressure adjustment for easy setting.

5.1 Setting Pressure Range

The control allows for adjustment of both the cut-out (high pressure limit) and the differential (the difference between cut-in and cut-out pressures). Use a flat-head screwdriver to adjust the set points visible through the window on the front panel. The scale indicates the pressure in PSI.

5.2 Manual Reset Lockout

If the control is equipped with a manual reset lockout, it will trip and lock the system off if the pressure exceeds a critical threshold. To reset, the pressure must return to a safe level, and then the manual reset button must be pressed. This feature prevents automatic restarts under unsafe conditions.

6. Maintenance

Regular maintenance ensures the longevity and reliable operation of your Johnson Controls P70AA-118C unit. Perform the following checks periodically:

  • Visual Inspection: Check the control unit, capillary tube, and electrical connections for any signs of wear, corrosion, or damage.
  • Cleanliness: Keep the control unit clean and free from dust, dirt, and debris, which can affect performance.
  • Connection Integrity: Ensure all electrical and pressure connections remain tight and secure.
  • Functionality Check: Periodically verify that the control is cycling the fan or cutting out at the set pressure points as expected.

7. Troubleshooting

If you encounter issues with your P70AA-118C control, consider the following common troubleshooting steps. For complex issues, always consult a qualified technician.

  • Control Not Cycling Fan:
    • Verify power supply to the control.
    • Check pressure settings; ensure they are within the system's operating range and the control's capabilities.
    • Inspect capillary tube for kinks or leaks.
    • Check electrical connections for looseness or corrosion.
  • Inaccurate Pressure Readings:
    • Ensure the capillary tube is properly connected and not damaged.
    • Verify the system's actual pressure with a calibrated gauge.
  • Control Trips Frequently:
    • Check for system overpressure conditions.
    • Review the set pressure and differential settings.
    • If equipped, ensure the manual reset lockout is not being triggered by transient pressure spikes.

8. Warranty and Support

For detailed warranty information, please refer to the official documentation provided by Johnson Controls at the time of purchase or visit the Johnson Controls official website. Support for the P70AA-118C control can be obtained through authorized distributors or by contacting Johnson Controls customer service directly.

Product packaging label displaying the model number P70AA-118C and barcode.

Figure 8: Product packaging label displaying the model number P70AA-118C and barcode (UCC/EAN Code 128: 1078502829326).

Manufacturing origin label on the control unit, indicating 'ASSEMBLED IN MEXICO'.

Figure 9: Manufacturing origin label on the control unit, indicating 'ASSEMBLED IN MEXICO'.

Related Documents - P70AA-118C

Preview Johnson Controls P70, P72, P170 Series High Pressure Controls
Detailed overview of Johnson Controls PENN P70, P72, and P170 Series Electromechanical Pressure Controls for high-pressure applications. Includes features, applications, selection charts, and cross-references for refrigeration and HVAC systems.
Preview Johnson Controls Series 100 Single Package Units: Engineering Guide
Comprehensive engineering guide for Johnson Controls Series 100 Single Package Units, covering capacities from 70 to 105 tons. Details features, benefits, application data, nomenclature, and technical specifications for these energy-efficient HVAC units.
Preview Johnson Controls Series 100 Single Package Units Engineering Guide
Comprehensive engineering guide for Johnson Controls Series 100 Single Package Units (70-130 tons). Details features, application data, physical specifications, and cooling performance data for efficient HVAC solutions.
Preview Johnson Controls Controller Tool Help for HVAC Systems
This comprehensive help document provides detailed guidance for the Johnson Controls Controller Tool, covering configuration, simulation, commissioning, and troubleshooting of VAV Single Duct and other HVAC applications. It assists professionals in managing building automation systems effectively.
Preview User's Information Manual: Outdoor Split-System Air Conditioning and Heat Pump
Comprehensive user manual for Johnson Controls Ducted Systems outdoor split-system air conditioning and heat pump units, covering operation, safety guidelines, system functions, maintenance, troubleshooting, and limited warranty information.
Preview AHE Series Single Piece Air Handler ECM Motor Flex Coil Models Parts List
Detailed parts list and diagram for Johnson Controls AHE Series Single Piece Air Handler with Standard ECM Motor and Flex Coil Models (Style A). Includes component descriptions and part numbers for various models.