Dwyer 605-6

Dwyer Magnehelic Series 605 Differential Pressure Indicating Transmitter

Model: 605-6

1. Introduction

The Dwyer Magnehelic Series 605 Indicating Transmitter is designed for both visual monitoring and electronic control of very low differential pressure. This device is particularly suited for control applications within building HVAC systems, where local pressure indication is beneficial for routine maintenance and system troubleshooting. It combines the easily readable dial gauge of the time-proven Dwyer Magnehelic gauge mechanical design with Series 600 transmitter technology, providing a two-wire, 4-20 mA control signal. The rear terminal strip simplifies connection to any 4-20 mA control loop powered by a 10-35 VDC supply.

Front view of the Dwyer Magnehelic Series 605 Differential Pressure Indicating Transmitter

Figure 1: Front view of the Dwyer Magnehelic Series 605 Indicating Transmitter, showing the circular dial with pressure readings in inches of water, and the Dwyer logo at the bottom.

2. Safety Information

Please read and understand all instructions before installing or operating this product. Failure to do so may result in injury or damage to the equipment.

Close-up of the caution label on the Dwyer Magnehelic Series 605

Figure 2: Close-up view of the caution label, indicating maximum pressure of 25 PSIG (170 kPa), maximum temperature of 120°F (48°C), and minimum temperature of 20°F (-6°C).

3. Product Features

4. Components and Overview

The Dwyer Magnehelic Series 605 consists of the following main components:

Close-up of the dial face of the Dwyer Magnehelic Series 605

Figure 3: Close-up of the Magnehelic dial face, showing the "inches of water" scale, the pointer, and the "MAX. PRESSURE 25 PSIG" marking.

Close-up of the Dwyer logo and adjustment screws on the Magnehelic Series 605

Figure 4: Detail view of the Dwyer logo, along with the "SPAN" and "ZERO" adjustment screws located on the lower part of the dial.

5. Setup and Installation

5.1 Mounting

The Series 605 can be surface mounted. Ensure the mounting location is stable, free from excessive vibration, and within the specified operating temperature range. Use appropriate fasteners for the mounting surface. The back of the unit features mounting holes for secure installation.

5.2 Electrical Connections

The transmitter utilizes a two-wire, 4-20 mA output signal. Connect the power supply and signal wires to the terminal strip located on the rear of the unit. Observe proper polarity.

Rear view of the Dwyer Magnehelic Series 605 showing electrical terminals and pressure ports

Figure 5: Rear view of the transmitter, showing the electrical terminal strip at the top and the high and low pressure ports with green caps.

5.3 Pressure Connections

Connect the high-pressure source to the "HIGH PRESSURE" port and the low-pressure source to the "LOW PRESSURE" port. Ensure all connections are secure and leak-free.

Side view of the Dwyer Magnehelic Series 605 showing pressure ports

Figure 6: Side view of the transmitter, highlighting the two pressure ports with their protective green caps.

6. Operating Instructions

6.1 Initial Zero Adjustment

Before applying any pressure, ensure the pointer on the dial reads zero. If it does not, use a small screwdriver to carefully adjust the "ZERO" screw until the pointer aligns with the zero mark on the scale.

6.2 Reading the Dial

The dial indicates differential pressure in "inches of water" (WC). The red pointer moves across the scale to show the current pressure. Read the value directly from the scale where the pointer rests.

6.3 Span Adjustment (Calibration)

For precise 4-20 mA output calibration, apply a known full-scale pressure to the unit. Adjust the "SPAN" screw until the 4-20 mA output corresponds to the desired full-scale value (e.g., 20 mA at 6.0"WC for a 0-6.0"WC range). Refer to the specific calibration procedure in the full technical manual for detailed steps.

7. Maintenance

The Dwyer Magnehelic Series 605 is designed for minimal maintenance. However, regular checks can ensure optimal performance and longevity.

8. Troubleshooting

ProblemPossible CauseSolution
No pointer movement / No 4-20 mA outputNo power, incorrect wiring, clogged pressure ports, damaged unit.Check power supply (10-35 VDC). Verify wiring connections and polarity. Inspect pressure ports for obstructions. If issues persist, unit may be damaged.
Incorrect pressure reading on dialZero offset, span error, pressure leaks, incorrect pressure application.Perform zero adjustment. Check for leaks in pressure tubing. Verify pressure source accuracy. Perform span calibration if necessary.
Inaccurate 4-20 mA outputIncorrect calibration, power supply issues, load resistance too high/low.Perform span calibration. Ensure power supply is stable and within range. Check load resistance in the control loop (typically 250-750 ohms).

9. Specifications

10. Warranty and Support

For information regarding product warranty, technical support, or service, please contact Dwyer Instruments directly or visit their official website. Ensure you have your product model number (605-6) and serial number (if applicable) ready when contacting support.

Dwyer Instruments, Inc.
Michigan City, IN 46360 U.S.A.

For the most up-to-date contact information and resources, please refer to the official Dwyer Instruments website: www.dwyer-inst.com