1. Introduction
This manual provides essential information for the safe and proper use of the Siemens QN2200R 200-Amp 2 Pole 240-Volt Circuit Breaker. This circuit breaker is designed for use in Siemens EQ, Siemens Ultimate, ITE, and Gould load centers or meter combinations. It is a double pole breaker, rated for 240V, and can be used in single or 3-phase load centers. Please read all instructions carefully before installation and operation.
2. Safety Information
WARNING: Electrical shock hazard. This product must be installed and serviced by a qualified electrician in accordance with all national and local electrical codes. Failure to follow these instructions can result in serious injury or death.
- Always turn off power at the main service panel before working on electrical circuits.
- Use only Siemens circuit breakers in Siemens panels to maintain warranty validity and ensure proper system function.
- Do not use "used" circuit breakers. Siemens strongly recommends against their use.
- Ensure proper wire gauge and torque settings for all connections.
- Protect the circuit breaker from moisture and extreme temperatures.
3. Product Overview
The Siemens QN2200R is a 200-Amp, 2-pole, 240-Volt plug-in type circuit breaker. It is designed to protect electrical circuits from overcurrents and short circuits, tripping to interrupt the flow of electricity when a fault is detected. Key features include:
- Current Rating: 200 Amps
- Number of Poles: 2
- Voltage Rating: 240 Volts
- Mounting Type: Plug-In
- Frame Size: 4-Inch
- Certifications: UL Listed

Figure 1: Front view of the Siemens QN2200R circuit breaker, showing the 200A rating and ON/OFF switch.
4. Specifications
| Specification | Value |
|---|---|
| Brand | SIEMENS |
| Model Number | QN2200R |
| Current Rating | 200 Amps |
| Number Of Poles | 2 |
| Voltage | 240 Volts |
| Circuit Breaker Type | Standard |
| Mounting Type | Plug-In Mount |
| Product Dimensions | 7.7 x 2.5 x 4.1 inches |
| Item Weight | 1.5 pounds |
| UPC | 783643204232 |
5. Installation
Installation of this circuit breaker must be performed by a qualified electrician. Refer to the specific instructions provided with your Siemens load center or meter combination for detailed installation procedures. Ensure the main power supply is disconnected before beginning any work.
- Power Disconnection: Turn off the main power to the electrical panel at the utility disconnect or main breaker. Verify power is off using a voltage tester.
- Panel Access: Carefully remove the cover of the electrical panel.
- Breaker Placement: Identify the appropriate slot in the bus bar for the 2-pole breaker.
- Connection: Connect the load wires to the terminals on the circuit breaker. Ensure proper torque is applied to the terminal screws as specified by local codes and manufacturer guidelines.
- Mounting: Align the circuit breaker with the bus bar and firmly push it into place until it is securely seated.
- Panel Reassembly: Replace the electrical panel cover.
- Power Restoration: Restore power to the main service panel.

Figure 2: Side view of the Siemens QN2200R circuit breaker, showing its profile and connection points.

Figure 3: Rear view of the Siemens QN2200R circuit breaker, highlighting the plug-in connectors for the bus bar.
6. Operation
The circuit breaker features a toggle switch for manual operation and an internal mechanism for automatic tripping.
- ON Position: Push the toggle switch fully to the "ON" position to allow electricity to flow through the circuit.
- OFF Position: Push the toggle switch fully to the "OFF" position to manually interrupt the flow of electricity to the circuit.
- TRIPPED Position: If an overcurrent or short circuit occurs, the breaker will automatically trip. The toggle switch will move to an intermediate position, typically between "ON" and "OFF". To reset a tripped breaker, first push the switch firmly to the "OFF" position, then push it to the "ON" position. If the breaker immediately trips again, there is still a fault in the circuit that needs to be addressed by a qualified electrician.
7. Maintenance
Circuit breakers generally require minimal maintenance. However, periodic inspection by a qualified electrician is recommended to ensure continued safe operation.
- Visual Inspection: Periodically inspect the circuit breaker for any signs of physical damage, discoloration, or loose connections.
- Testing: Some electrical codes recommend periodic testing of circuit breakers. Consult a qualified electrician for appropriate testing procedures.
- Cleaning: Ensure the area around the circuit breaker is free from dust and debris. Do not use liquids to clean electrical components.
8. Troubleshooting
If the circuit breaker trips frequently or fails to reset, it indicates an electrical issue that requires attention.
- Frequent Tripping: This often indicates an overloaded circuit or a short circuit. Disconnect some appliances or devices from the circuit and try resetting the breaker. If it continues to trip, there may be a fault in the wiring or an appliance.
- Failure to Reset: If the breaker does not stay in the "ON" position after being reset (pushed to OFF then ON), it suggests a persistent fault. Do not force the breaker into the "ON" position.
- No Power: If a circuit has no power and the breaker is in the "ON" position, check for loose connections or other issues within the electrical panel or circuit.
For any persistent electrical issues, contact a qualified electrician immediately.
9. Warranty and Support
Siemens circuit breakers are manufactured to high-quality standards. For specific warranty information, please refer to the documentation provided with your purchase or visit the official Siemens website. For technical support or inquiries, please contact Siemens customer service.
Using non-Siemens breakers in a Siemens panel may void the panel's warranty.
10. Additional Product Views

Figure 4: Angled view of the Siemens QN2200R circuit breaker, showing its overall form factor.





