Intermatic T104P

Intermatic T104P 24-Hour Mechanical Time Switch User Manual

Brand: Intermatic | Model: T104P

1. Introduction

The Intermatic T104P is a heavy-duty 24-hour mechanical time switch designed for automatic control of electrical loads. This device provides reliable scheduling for various applications, offering up to 12 ON/OFF operations daily. Its robust plastic enclosure is suitable for both indoor and outdoor installations, providing protection against environmental elements.

Key features include direct 24-hour control, a minimum ON/OFF time of one hour, and a manual override function for temporary control adjustments.

2. Safety Information

WARNING: Risk of Electric Shock. Disconnect power at the circuit breaker or fuse before installing or servicing this time switch. Failure to do so may result in serious injury or death.

3. Package Contents

Verify that all items are present in the package:

4. Setup and Installation

4.1 Mounting the Time Switch

The T104P features a NEMA 3R rated plastic enclosure, suitable for both indoor and outdoor mounting. Choose a location that is easily accessible for programming and maintenance, and protected from direct impact.

  1. Open the enclosure door.
  2. Use appropriate screws or mounting hardware (not included) to secure the enclosure to a flat, stable surface through the designated mounting holes.
  3. Ensure the enclosure is level to allow for proper operation of the mechanical timer.

4.2 Wiring Instructions

Refer to the internal wiring diagram and the following steps for proper electrical connection. Always ensure power is disconnected before proceeding.

Internal view of Intermatic T104P mechanical time switch showing the yellow dial, manual lever, and wiring terminals.

Figure 1: Internal view of Intermatic T104P mechanical time switch showing the yellow dial, manual lever, and wiring terminals. This image displays the internal components of the Intermatic T104P time switch, including the 24-hour dial for setting time, the manual ON/OFF lever, and the clearly labeled LINE and LOAD wiring terminals. A caution label regarding power disconnection and wire types is visible.

  1. Disconnect Power: Turn off power at the main circuit breaker or fuse panel before beginning any wiring.
  2. Access Terminals: The insulator covering the wiring terminals must be lifted and swung out of the way to access the connections. DO NOT REMOVE THIS INSULATOR.
  3. Connect Line Wires: Connect the incoming power supply wires (LINE) to the terminals labeled 'LINE'. This time switch is DPST (Double Pole Single Throw), meaning it controls two separate hot lines.
  4. Connect Load Wires: Connect the wires leading to the electrical load (e.g., pump, lighting) to the terminals labeled 'LOAD'.
  5. Grounding: Ensure the time switch is properly grounded according to local electrical codes.
  6. Secure Wires: Ensure all wire connections are tight and secure.
  7. Replace Insulator: Swing the insulator back into its original position, covering the wiring terminals.
  8. Close Enclosure: Close and secure the enclosure door.
  9. Restore Power: Turn power back on at the main circuit breaker or fuse panel.
Side view of Intermatic T104P mechanical time switch with the gray plastic enclosure open, revealing the internal mechanism.

Figure 2: Side view of Intermatic T104P mechanical time switch with the gray plastic enclosure open, revealing the internal mechanism. This image shows the Intermatic T104P time switch with its gray plastic enclosure open, providing a view of the internal mechanical timer and the wiring compartment. The NEMA 3R rated enclosure is designed for both indoor and outdoor use.

5. Operating Instructions

5.1 Setting the Current Time

To set the current time, rotate the yellow dial clockwise until the current time of day aligns with the small arrow located at the top of the dial. Ensure to differentiate between AM and PM hours as indicated on the dial.

5.2 Setting ON/OFF Times

The T104P uses trippers to set the ON and OFF times. The unit comes with one ON tripper (green) and one OFF tripper (red).

  1. Install ON Tripper: Locate the green ON tripper. Push it onto the outer edge of the yellow dial at the desired time you want the connected load to turn ON.
  2. Install OFF Tripper: Locate the red OFF tripper. Push it onto the outer edge of the yellow dial at the desired time you want the connected load to turn OFF.
  3. Additional Cycles: The time switch supports up to 12 ON/OFF operations per day. Additional trippers can be purchased separately if more cycles are required. Each ON/OFF cycle requires one green ON tripper and one red OFF tripper.
  4. Minimum Interval: The minimum ON/OFF time interval is one hour. Ensure there is at least one hour between an ON and OFF tripper.

5.3 Manual Override

The time switch includes a manual override lever for temporary control of the connected load without affecting the programmed schedule.

6. Maintenance

The Intermatic T104P is designed for minimal maintenance. However, periodic checks can ensure optimal performance and longevity.

7. Troubleshooting

ProblemPossible CauseSolution
Load does not turn ON/OFF at programmed times.
  • Incorrect current time setting.
  • Trippers incorrectly placed or missing.
  • Manual override engaged.
  • No power to the time switch.
  • Verify and adjust the current time.
  • Check tripper placement and ensure they are securely attached.
  • Ensure manual override lever is in the automatic position.
  • Check circuit breaker/fuse and wiring connections.
Time switch dial is not rotating.
  • No power to the time switch.
  • Internal mechanical issue.
  • Check circuit breaker/fuse and wiring connections.
  • If power is present and dial still does not rotate, the unit may require replacement.
Enclosure door does not close properly.
  • Obstruction or damage to hinges/latch.
  • Inspect for debris or damage. Clear any obstructions.

8. Specifications

Front view of the Intermatic T104P mechanical time switch with its gray plastic enclosure closed, showing the Intermatic logo.

Figure 3: Front view of the Intermatic T104P mechanical time switch with its gray plastic enclosure closed, showing the Intermatic logo. This image presents the Intermatic T104P time switch with its durable gray plastic enclosure closed, suitable for protecting the internal components from environmental elements. The Intermatic brand logo is embossed on the front.

FeatureDetail
ModelT104P
Type24-Hour Mechanical Time Switch
Voltage208-277 VAC
Frequency60 Hz
Number of Poles2 (DPST)
Amperage40 Amps
Horsepower (HP) Rating2 HP @ 120V, 5 HP @ 240V
Enclosure TypePlastic, NEMA 3R (Indoor/Outdoor)
Minimum ON/OFF Time1 Hour
Maximum ON/OFF Cycles12 per day
Dimensions (H x W x D)9.43" x 5.5" x 3.81"
Item Weight2 Pounds
MaterialSolid
ColorGray

9. Warranty and Support

For warranty information, please refer to the manufacturer's official documentation included with your product or visit the Intermatic brand store or their official website.

If you require technical assistance or have questions regarding the operation or installation of your Intermatic T104P time switch, please contact Intermatic customer support directly.

Related Documents - T104P

Preview Intermatic T103 24-Hour Dial Time Switch: Installation and Operation Manual
Detailed guide for the Intermatic T103 24-Hour Dial Time Switch, covering specifications, safety warnings, wiring instructions, programming, and operation. Suitable for indoor use with 120/208/240 VAC power.
Preview Intermatic T170, T1400 & T1800 Series Electromechanical Time Switches
Comprehensive details on Intermatic T170, T1400, and T1800 Series 24-Hour Electromechanical Time Switches, covering features, specifications, ratings, model variations, and wiring diagrams for commercial, industrial, and residential applications.
Preview Intermatic T105 24-Hour Dial Time Switch: Installation, Wiring, and Operation Guide
Comprehensive guide for the Intermatic T105 24-hour mechanical dial time switch. Covers model specifications, safety warnings, wiring instructions for various configurations (SPNO, SPNC, SPDT), programming procedures, and manual operation. Includes a detailed table of electrical ratings and wire gauge recommendations.
Preview Intermatic T104 24-Hour Dial Time Switch - Specifications and Instructions
Comprehensive guide for the Intermatic T104 24-hour dial time switch, detailing its specifications, electrical ratings, safety warnings, wiring instructions, programming procedures, and operating guidelines. Includes technical data and troubleshooting tips.
Preview Intermatic GM40AV Series Electromechanical Commercial Time Switch: Installation and Operation Manual
Comprehensive installation, operation, and programming guide for the Intermatic GM40AV Series electromechanical commercial time switches. Includes electrical ratings, wiring diagrams, and warranty information.
Preview Intermatic GMXFM1 Electronic Time Switch Instruction Manual
Instruction manual for the Intermatic GMXFM1 electronic time switch, covering safety precautions, symbols, initial setup, programming, time settings, daylight saving adjustments, operating modes, and warranty information.