1. Introduction
This manual provides essential information for the safe and effective installation, operation, and maintenance of your ICM Controls ICM491 Single Phase Monitor. The ICM491 is designed to protect single-phase equipment from damaging high and low voltage conditions and rapid system recycling.
Please read this manual thoroughly before installation and retain it for future reference.
2. Product Overview
The ICM491 is a single-phase line voltage monitor that offers advanced protection for various electrical systems. It continuously monitors the incoming voltage and disconnects the load if the voltage falls outside the adjustable high or low voltage limits. It also incorporates an Anti-Short Cycle (ASC) timer to prevent rapid cycling of equipment, which can cause premature wear and failure.

Figure 1: ICM Controls ICM491 Single Phase Monitor. This image shows the compact design of the ICM491 unit with its terminal connections and adjustment dials.
3. Features
- Adjustable Voltage Range: Operates within 95-270 VAC.
- High/Low Voltage Protection: Safeguards equipment from damaging voltage fluctuations.
- Anti-Short Cycle (ASC) Timer: Prevents rapid cycling, extending equipment lifespan.
- Compact Design: Easy to integrate into existing systems.
- LED Indicators: Provides visual status of operation and fault conditions.
4. Safety Information
WARNING: Electrical shock hazard. Disconnect all power before installing or servicing this device. Installation should only be performed by a qualified electrician in accordance with all national and local electrical codes.
- Ensure the power supply matches the device's voltage rating.
- Do not operate the device if it appears damaged.
- Keep away from moisture and extreme temperatures.
5. Installation
The ICM491 is designed for straightforward installation. Follow these steps carefully:
- Power Disconnection: Turn off all power to the equipment and circuit where the ICM491 will be installed. Verify power is off using a voltmeter.
- Mounting: Mount the ICM491 in a suitable electrical enclosure, ensuring adequate ventilation and protection from environmental elements.
- Wiring:
- Connect the incoming 95-270 VAC power lines to the designated input terminals on the ICM491. Polarity typically does not matter for AC input.
- Connect the load (e.g., compressor contactor coil) to the output terminals of the ICM491. Refer to the wiring diagram provided with the unit for specific terminal assignments.
- Setting Voltage Trip Points:
- Use the adjustment dials on the unit to set the desired high and low voltage trip points. These settings determine the voltage thresholds at which the unit will disconnect power.
- It is recommended to set the trip points based on the nominal line voltage and the acceptable operating range for your equipment. A common practice is to set the trip for 15% below and 12% above the measured voltage, as mentioned in user feedback.
- Setting ASC Delay: Adjust the Anti-Short Cycle (ASC) timer to the desired delay period. This delay prevents the equipment from restarting too quickly after a power interruption or voltage event.
- Power Restoration: Once all connections are secure and settings are configured, restore power to the circuit.

Figure 2: Example of ICM491 terminal connections. This image illustrates the typical wiring terminals on the ICM491, showing where input power and load connections are made. Consult the specific diagram included with your unit.
6. Operation
Once installed and powered, the ICM491 continuously monitors the line voltage. The unit's LED indicators provide status feedback:
- Normal Operation: When voltage is within the set limits, the unit allows power to the load.
- Voltage Fault: If the voltage goes above the high limit or below the low limit, the ICM491 will open its output contacts, disconnecting power to the protected equipment.
- ASC Delay: After a voltage fault or power interruption, the ASC timer initiates a delay before allowing the equipment to restart, protecting the compressor or motor from short cycling.
7. Maintenance
The ICM491 is designed for maintenance-free operation. However, periodic checks are recommended:
- Visual Inspection: Periodically inspect the unit and its wiring for any signs of damage, loose connections, or overheating.
- Functionality Check: If possible, periodically test the unit's trip functionality by simulating a voltage fluctuation (only if safe and feasible, or by a qualified technician).
- Cleaning: Ensure the unit is free from dust and debris to maintain proper ventilation.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Equipment does not turn on. |
|
|
| Unit trips frequently. |
|
|
If troubleshooting steps do not resolve the issue, contact a qualified technician or ICM Controls customer support.
9. Specifications
| Parameter | Value |
|---|---|
| Input Voltage Range | 95-270 VAC |
| Frequency | 50/60 Hz |
| High Voltage Trip | Adjustable (typically 12% above set point) |
| Low Voltage Trip | Adjustable (typically 15% below set point) |
| Anti-Short Cycle (ASC) Delay | Adjustable (e.g., 2-3 minutes) |
| Product Dimensions | 8 x 6.2 x 2.1 inches |
| Weight | 5.6 ounces |
| Material | Metal, Plastic |
10. Warranty and Support
For warranty information, please refer to the documentation included with your purchase or visit the official ICM Controls website. If you require technical assistance or have questions regarding the ICM491, please contact ICM Controls customer support directly.
ICM Controls Contact Information:
- Website: www.icmcontrols.com (Note: This is a placeholder URL, please refer to official product documentation for actual contact details.)
- Phone: Refer to the manufacturer's website for current contact numbers.