This instruction manual provides essential information for the safe and effective installation, operation, and maintenance of the MARS 61481 780 Definite Purpose Contactor. Please read this manual thoroughly before attempting any installation or operation to ensure proper function and safety.
2. انتهى المنتجview
The MARS 61481 780 is a 3-pole, 75 Amp definite purpose contactor designed for switching electrical loads in various applications. It features a 120VAC coil for control circuit operation and box lug terminals for secure wiring connections.

Image of the MARS 61481 780 Definite Purpose Contactor, showing its three main power terminals with box lug connections and the two smaller coil terminals at the bottom. The product label is visible on top.
3. المواصفات
| ماركة | المريخ |
| رقم الموديل | 61481 |
| التقييم الحالي | 75 Amps |
| عدد البولنديين | 3 |
| لفائف المجلدtage | 120 فولت تيار متردد |
| نوع التركيب | التركيب السطحي |
| الأبعاد (الطول × العرض × الارتفاع) | 6 × 5.04 × 3.96 بوصة |
| وزن العنصر | 4 رطل |
| رمز المنتج الموحد | 685744614814 |
4. معلومات السلامة
تحذير: خطر حدوث صدمة كهربائية. افصل الطاقة قبل إجراء الصيانة.
- يجب أن يتم إجراء التثبيت والصيانة بواسطة أفراد مؤهلين فقط.
- تأكد من اتباع جميع القوانين الكهربائية المحلية والوطنية.
- تأكد من أن حجم العرضtage matches the contactor's coil voltage (120VAC).
- لا تقم بتشغيل الموصل إذا كان يبدو تالفًا.
- ارتدِ معدات الحماية الشخصية المناسبة عند العمل مع الأنظمة الكهربائية.
5. التثبيت والإعداد
- انقطاع التيار الكهربائي: Ensure all power to the circuit is disconnected at the main breaker or fuse panel before beginning installation. Verify with a voltagه اختبار.
- التركيب: Securely mount the contactor to a stable surface using appropriate fasteners. The surface mount design allows for direct attachment.
- Wiring Power Terminals: Connect the main power lines to the three large box lug terminals. Ensure proper phase sequence if applicable. Tighten all connections to the manufacturer's specified torque to prevent loose connections and overheating.
- Wiring Coil Terminals: Connect the 120VAC control circuit wires to the smaller coil terminals. These terminals energize the coil, which in turn closes the main contacts.
- تَحَقّق: تأكد من صحة جميع توصيلات الأسلاك وإحكامها. تأكد من عدم وجود أسلاك مكشوفة.
- استعادة الطاقة: بمجرد اكتمال التثبيت والتحقق منه، قم باستعادة الطاقة إلى الدائرة.
Note: Consult a licensed electrician if you are unsure about any part of the installation process.
6. التشغيل
The MARS 61481 780 Definite Purpose Contactor operates by using an electromagnetic coil to open and close a set of electrical contacts. When 120VAC is applied to the coil terminals, the coil energizes, creating a magnetic field that pulls the armature, closing the main power contacts. This allows current to flow through the connected load. When power is removed from the coil, the magnetic field collapses, and springs return the contacts to their open position, interrupting the power to the load.
- تنشيط الملف: Apply 120VAC to the coil terminals to close the main contacts.
- إزالة الطاقة من الملف: Remove 120VAC from the coil terminals to open the main contacts.
7. الصيانة
الصيانة الدورية تضمن عمرًا أطول وتشغيلًا موثوقًا لموصلك. افصل الكهرباء دائمًا قبل إجراء أي صيانة.
- التفتيش البصري: Periodically inspect the contactor for signs of wear, damage, or discoloration (indicating overheating). Check for loose connections.
- تنظيف: Keep the contactor free from dust, dirt, and debris. Use a dry, non-conductive brush or compressed air for cleaning. Do not use liquids.
- ضيق الطرفية: Re-check the tightness of all terminal connections annually to prevent arcing and overheating.
8. استكشاف الأخطاء وإصلاحها
إذا لم يعمل الموصل كما هو متوقع، ففكر في المشكلات الشائعة التالية:
- لا يتم تشغيل الملامس:
- Check if 120VAC is present at the coil terminals when the control circuit is active.
- Verify the coil is not open or shorted (requires multimeter testing by qualified personnel).
- Ensure mechanical parts are not obstructed.
- ارتفاع درجة حرارة الموصل:
- Check for loose power connections at the terminals.
- Ensure the load current does not exceed the 75 Amp تصنيف.
- Verify proper ventilation around the contactor.
- Contacts Are Pitted or Welded:
- This indicates excessive arcing or overload. The contactor may need replacement.
- Investigate the cause of overload or frequent switching.
For complex issues, contact a qualified electrician or MARS technical support.