APOLLO Snow Melt Sensor

SAFETY PRECAUTIONS
- Before installing or operating the sensor, read this manual carefully to ensure safe and correct use.
- Installation and wiring must be performed only by qualified personnel, in accordance with applicable local electrical codes and regulations.
- Always disconnect power before wiring, servicing, or removing the sensor to prevent electric shock or equipment damage.
- Do not disassemble or modify the sensor, as it contains no user-serviceable parts. Unauthorized modifications may result in malfunction or void the warranty.
- Install the sensor only in suitable outdoor locations, avoiding exposure to corrosive chemicals, excessive vibration, or conditions beyond the specified operating limits.
- Ensure the system is powered down and secured before performing any maintenance or inspection.
- Dispose of electrical components and packaging materials in accordance with local environmental and recycling regulations.
INTRODUCTION
The APOLLO Snow Melt Sensor is designed for reliable detection of snow or rain presence in outdoor environments. It operates using a frequency-domain reflection principle combined with high-frequency electronic measurement and an embedded microprocessor. This allows fast response, high sensitivity, and stable operation in harsh winter conditions. The sensor includes an integrated surface heating function to eliminate moisture accumulation and prevent false readings.
FEATURES
- Capacitive detection technology for rain and snow presence
- Aluminum housing
- Normally Open (NO) relay contact available for HVAC control logic
- Surface heating function
- High sealing level, IP67
- Strong resistance to electromagnetic interference
- Multiple output signal options
- Designed for long service life in outdoor installations
APPLICATIONS
This sensor is suitable for qualitative detection of rain or snow (presence / absence).
Typical applications include:
- Hydronic snow-melt systems
- Driveway and walkway heating systems
- Roof and gutter ice prevention
- Building automation systems (BMS)
- Industrial and environmental monitoring
TECHNICAL SPECIFICATIONS
- Measurement Rain / Snow presence
- Operating temperature -30 °C to +70 °c
- Operating humidity 0-99 % RH
- Storage temperature -40 °C to +80 °c
- Power supply 12-24 V DC
- Stability time < 1 second
- Response time < 1 second
- Protection rating IP67
- Housing material Aluminum
- Auxiliary function Heating function
OUTPUT SIGNAL OPTIONS
The sensor supports multiple output configurations:
- Relay output (Normally Open dry contact)
- AC 220 V / 1 A
- DC 24 V / 2 A
- Voltage output: 0-2 V / 0-5 V / 0-10 V
- Current output: 4-20 mA
- RS485 (Modbus-RTU, default address 01)
- N PN output
- Combined outputs (Relay+ Current+ RS485)
- SDl-12 protocol
Impedance requirement for the current signals:
| Service voltage | 9V | 12V | 20V | 24V |
| Maximum Impedance | <250 Ω | <400 Ω | <500 Ω | <900 Ω |
DIMENSIONS

INSTALLATION
- Install the sensor outdoors in an open area exposed to snowfall.
- The sensor is supplied with a wall-mounting support, designed for secure installation on vertical surfaces.
- The mounting support includes a 12-inch pipe (arm length) to position the sensor away from the wall and ensure proper exposure to snowfall.
- The supplied support provides a fixed 15° inclination, ensuring the correct mounting angle to prevent snow accumulation on the sensing surface.
- Avoid installation near sources of chemical corrosion.
- Maintain adequate distance from high-voltage cables and strong heat sources.

ELECTRICAL CONNECTIONS
The sensor may be connected to:
- Snow-melt controllers
- PLC or BMS digital inputs
- Data acquisition modules
The wiring description is shown below: 
DATA CONVERSION METHOD
| OUTPUT SIGNAL | NO RAIN (SNOW) | THERE IS RAIN (SNOW) |
| Relay switch quantity (normally open) | break | actuation |
| 0~2V DC | 0.6V | 1.6V |
| 0 ~SV DC | 1.5V | 4V |
| 0~l0V DC | 3V | 8V |
| 4~20mA | 6mA | 16mA |
| RS485 | 0X000A | 0X000B |
RS485 signal (default address 01): Standard Modbus-RTU protocol,
- Baud rate: 9600;
- Check bit: no;
- Data bit: 8;
- Stop bit: 1
MODIFICATION ADDRESS
For example, change the sensor with address 1 to address to 2, the host slave.
| The Original Address |
Function Code |
High register Address | The register Address is low | The starting address is high | The starting address is low |
CRC16 low |
CRC16 high |
| 0X0l | 0X06 | oxoo | 0X30 | oxoo | 0X02 | 0X08 | 0X04 |
If the sensor is received correctly, the data is returned in the original route.
Note: If you forget the original address of the sensor, you can use the broadcast address 0 XFE instead. When using 0 XFE, the host can only connect to one slave, and the returned address is still the original address, which can be used as the method of address query.
QUERY DATA
Query the data of the sensor (address 01) (rain or snow), the host slave.
| Address |
Function Code |
Star register address is high | Star register address is low | The register length is high | The register length is low |
CRC16 low |
CRC16 high |
| 0X0l | 0X03 | 0X0l | 0X84 | 0X0A |
If the sensor receives correctly, return the following data to the slave host.
| Address | Function Code | DL | Register 0 data is high | Register 0 datais low | CRC16 low | CRC16 high |
| 0XOl | 0X03 | 0X02 | 0X00 0X0A | 0X38 | 0X43 | |
| No rain (snow): 0X000A Rain (snow): 0X000B | ||||||
SET UP ACTIVE REPORTING
When it needs to be set to active reporting mode, the host slave.

If the data returned to the host is the same as the sent data, the setting is successful.
- When the air temperature is below the starting heating temperature (34°F/1℃), start the heating.
- When the air temperature is above the stop heating temperature (77°F/25℃), the heating is stopped.
- When the temperature is between 34°F/1℃ and 77°F/25℃, start heating when there is rain, and not heating when there is no rain.

SET OR QUERY THE START AND END TEMPERATURE OF AUTOMATIC HEATING
SET THE HEATING START TEMPERATURE
Hosting oneself from the machine 
The data returned from the machine to the host is the same as the sent data, and the same description is set successfully.
SET THE HEATING STOP TEMPERATURE
Hosting oneself from the machine. 
- If the data returned to the host is the same as the sent data, the setting is successful.
MAINTENANCE
- The APOLLO Snow Melt Sensor is designed for reliable, maintenance-free operation under normal environmental conditions. Periodic inspection is recommended to ensure optimal performance. Inspect the sensing surface regularly and remove any accumulated dirt, debris, or residue that may affect detection accuracy. Verify that all electrical connections are secure and that the cable insulation is intact.
- Do not use abrasive materials, solvents, or high-pressure water when cleaning the sensor. If cleaning is required, use a soft cloth and clean water only. Any maintenance or inspection must be performed with the power supply disconnected. The sensor contains no user-serviceable internal components; disassembly or modification is not permitted.
COMMISSIONING PARAMETERS
All control parameters are adjustable at the controller level:
- Outdoor temperature threshold
- Slab temperature setpoint
- Temperature differential
- Maximum operating time
SAFETY & COMPLIANCE
- The sensor must be installed by qualified personnel. All wiring shall comply with local electrical codes. Relay outputs must not exceed rated load limits.
SUPPORT
For technical assistance, contact:
- MBTek USA
- www.mbtek.com
- support@mbtek.com
APOLLO Heat Pump
info@mbtek.com
888-301-0737