APG RPE Resistive Chain Continuous Level Probes

APG-RPE-Resistive-Chain-Continuous-Level-Probes-PRODUCT

FAQs

  • Q: What should I do if the RPX probe label does not match my order?
    • A: If the part number on the label does not match your order, contact APG for assistance and verification.
  • Q: How do I ensure compliance with hazardous location installation requirements?
    • A: Follow the installation drawings (9001930 and 9001932) provided in the manual for RPX probes to meet safety approvals and ratings. Faulty installation can invalidate safety certifications.

Introduction

  • Thank you for purchasing an RP Resistive Chain Continuous Level Probe from APG. We appreciate your business! Please take a few minutes to familiarize yourself with your RPE or RPX and this manual.
  • The RP resistive probes contain reed switches in a 1/2” Ø stainless steel stem and a permanent magnet in a float. As the float rises or falls with the level of the liquid, the magnet inside the float acts on the corresponding reed switches inside the stem changing the output of the probe. The RPX carries explosion-proof, intrinsically safe, and non-incendive hazardous location approvals.

Reading your label

  • Every APG instrument comes with a label that includes the instrument’s model number, part number, and serial number. Please ensure that the part number on your label matches your order.

RPX Electrical ratings

  • APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (1)Class I Division 1, Groups C, and D T3
  • Ta 40°C
  • Rated: 5 – 24 VDC, 100 mA, or 12 – 24 VDC, 4-20 mA
  • Ex d, IIB T3
  • Class I Zone1, AEx, lIB 13
  • Ta 40°C
  • Rated: 5 – 24 VDC, 100 mA, or 12 – 24 VDC, 4-20 mA
  • Class I Division 2, Groups C, and D T3
  • Ta 85°C
  • Rated: 5 – 24 VDC, 100 mA, or 12 – 24 VDC, 4-20 mA
  • Class I Division 2, Groups C, and D T3
  • Ta 85°C
  • Field wiring is non-incendive when installed per drawing 9001932
  • Rated: 5 – 15 VDC, 100 mA, or 12 – 24 VDC, 4-20 mA
  • Class I Division 1, Groups C, and D T3C
  • Max Ta 85°C
  • Intrinsically Safe when installed per drawing 9001930 with the following entity parameters: max = 30 V, max = 130 mA, C, = 3 nF, L, = 0 ph
  • Rated: loop-powered 24 VDC, 4-20 mA converter module

IMPORTANT: Your RPX MUST be installed according to drawing 9001930 (IS Hazardous Installation Drawing For RPX) or 9001932 (Hazardous Mounting Drawing RPX) to meet the listed approvals. The faulty installation will invalidate all safety approvals and ratings.
DANGER: OPEN CIRCUIT BEFORE REMOVING COVER or KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE;
IMPORTANT: SEAL SHALL BE INSTALLED WITHIN 50 mm OF THE ENCLOSURE;
IMPORTANT –– UNSCELLEMENT DOIT ETRE INSTALLE A MOINS DE 50 mm DU BOITIER.
DANGER: EXPLOSION HAZARD-DO NOT DISCONNECT WHILE THE CIRCUIT IS LIVE UNLESS THE AREA IS KNOWN TO BE NON-HAZARDOUS;

Warranty

Warranty and Warranty Restrictions

This product is covered by APG’s warranty to be free from defects in material and workmanship under normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit www.apgsensors.com/resources/warranty-certifications/warranty-returns/. Contact Technical Support to receive a Return Material Authorization before shipping your product back.

Specifications and Options

Dimensions

APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (2)

  • Legend
    • L = Total Stem Length
    • M = Measured Length
    • S1 = Top Deadband (1.75” / 44.5 mm)
    • S2 = Bottom Deadband (1.75” / 44.5 mm)
    • L = M + S1 + S2 M = L – S1 – S2
  • Maximum Stem Length:
    • RPX: 96” / 2440 mmAPG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (3)
  • Legend
    • L = Total Stem Length
    • M = Measured Length
    • S1 = Top Deadband (1.75” / 44.5 mm)
    • S2 = Bottom Deadband (1.75” / 44.5 mm)
    • L = M + S1 + S2 M = L – S1 – S2
  • Maximum Stem Length:
    • RPE: 153” / 3890 mm

Specifications

RPX

  • Performance
    • Resolution ±0.25 in. (6.4 mm)
    • Accuracy ±0.12 in. (3 mm)
  • Environmental
    • Temperature See Chart Below
    • Maximum pressure 72.5 PSI (5 bar)
    • Enclosure Protection NEMA 4 & 7, IP65
  • Electrical
    • Output 4-20 mA; Resistive
    • Typical Current (Resistive Output) I = VDC supply / (45 Ω * Length in inches)
    • Internet Connectivity via RST-5003; 4-20 mA output only
  • Materials of Construction
    • Stem 316L Stainless Steel
    • Floats 316L Stainless Steel, or Buna
    • Housing Die Cast Aluminum
  • Mechanical
    • Conduit connection 3/4” NPTM
    • Maximum stem length 96 inches / 8 feet / 2440 mm
    • Float Specific Gravity 0.39, 0.57, or 0.65

RPX Outputs with Temperature and Power Requirements for Hazardous Locations

APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (4)

  • Performance
    • Resolution ±0.25 in. (6.4 mm)
    • Accuracy ±0.12 in. (3 mm)
  • Environmental
    • Temperature -40 – 85°C / -40 – 185°F
    • Maximum Pressure 72.5 PSI (5 bar)
    • Enclosure Protection
    • Large Aluminum NEMA 4 & 7, IP65
    • Small Nylon IP65
    • Small Aluminum NEMA 4X, IP68
  • Electrical
    • Output 4-20 mA; Resistive
    • Voltage and Current Ratings
    • Resistive 5 – 24 VDC, 100 mA (max)
    • 4-20 mA 12 – 24 VDC, 4-20 mA
    • Typical Current (Resistive Output) I = VDC supply / (45 Ω * Length in inches)
    • Hookup wire 22 AWG
    • Internet Connectivity via RST-5003; 4-20 mA output only
  • Materials of Construction
    • Materials
      • Stem 316L Stainless Steel
      • Floats 316L Stainless Steel, or Buna
    • Housing
      • Large Cast Aluminum
      • Small Nylon
      • Small Aluminum
  • Mechanical
    • Conduit connection
      • Large Aluminum 3/4” NPT
      • Small Nylon 1/2” NPT
      • Small Aluminum 3/4” NPT
      • Maximum stem length 153 inches / 12.75 feet / 3890 mm
      • Float Specific Gravity 0.39, 0.57, or 0.65

Model Number Configurator

Model Number: APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (5)

A. Output

  • A Hazardous, 4-20 mA output
  • R Hazardous, resistive output
  • I Intrinsic safety, 4-20 mA output

B. Mounting Type, Option, and Size

  • F Flat Face ANSI 150# Flange (size=1.5, 2, 2.5, 3, 4)
  • R Raised Face ANSI 150# Flange (size=1.5, 2, 2.5, 3, 4)
  • S Triclamp (size=2, 2.5, 3, 4)
  • P Externally-mounted NPT Plug 150# (size=1.5†, 2, 2.5, 3, 4)
  • N None

C. Mounting Connection

  • W Welded (fixed)
  • S Slide with Compression Fitting
    • †Note: Size 1.5 NPT Externally-mounted (P1.5) requires float F.

D. Stem Material

  • S6 316L Stainless Steel
  • E. Float Type
  • E 316L SS 2.01 in. (53 mm) Round; 0.57 SG
  • F 316L SS 2.17h x 1.48w in. (55h x 38w mm); 0.65 SG
  • G Buna 1.77h x 1.89w in. (45h x 48w mm); 0.39 SG

F. Stem Length in Inches

  • __ Min. 11 in. – Max 96 in.

Model Number: APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (6)

A. Output

  • A 4-20 mA output†
  • R Resistive output

B. Mounting Type, Option, and Size

  • F Flat Face ANSI 150# Flange (size=1.5, 2, 2.5, 3, 4)
  • R Raised Face ANSI 150# Flange (size=1.5, 2, 2.5, 3, 4)
  • S Triclamp (size=2, 2.5, 3, 4)
  • P Externally-mounted NPT Plug 150# (size=1.5††, 2, 2.5, 3, 4)
  • I Internally-mounted NPT Plug 150#††† (size=0.25, 0.375, 0.5, 0.75, 1, 1.25, 1.5)
  • N None

C. Mounting Connection

  • W Welded (fixed)
  • S Slide with Compression Fitting

D. Stem Material

  • S6 316L Stainless Steel
  • †Note: Output A 4-20 mA requires Housing A Large Aluminum.
  • ††Note: Size 1.5 NPT Externally-mounted (P1.5) requires float F.
  • †††Note: Mounting Type I Internally-mounted NPT Plug requires Housing W Hookup Wire and Output R Resistive.

E. Float Type

  • E 316L SS 2.01 in. (53 mm) Round; 0.57 SG
  • F 316L SS 2.17h x 1.48w in. (55h x 38w mm); 0.65 SG
  • G Buna 1.77h x 1.89w in. (45h x 48w mm); 0.39 SG

F. Stem Length in Inches

  • __ Min. 11 in. – Max 153 in.

G. Housing, Cable Entry Size

  • A Large Aluminum, 3/4” NPT
  • B Small Nylon, 1/2” NPT
  • C Small Aluminum, 3/4” NPT
  • W Hookup wire (no housing)

H. Hookup Wire Length

  • 12 12 in.
  • 24 24 in.
  • __ Specify length in inches

Wire Color and Terminal Tables

  • Wire Colors For RPE-R with Hookup Wires
    Wire Resistive Output
    Red +24 VDC
    Black DC Ground
    White Voltage Out
  • Terminals for RPX-A, RPX-I, and RPE-A (4-20 mA Output)APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (7)
  • Terminals for RPE-R with Housing and RPX-R (Resistive Output)APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (8)

Installation and Removal Procedures and Notes

Tools Needed

  • Wrench-sized appropriately for your RPEs or RPX’s mounting
  • Wrench-sized appropriately for conduit connections
  • Thread tape or sealant compound for threaded connections

Physical Installation Notes

  • The RPE or RPX should be installed in an area–indoors or outdoors–that meets the following conditions:
    • IEC-664-1 Conductive Pollution Degree 2
    • IEC 61010-1 Measurement Category II
    • Altitude up to 2000 meters (6560 feet)
    • Relative humidity up to 100%
    • DC power supply
    • Ambient temperature between -40°C and 85°C (-40°F to +185°F)
    • No chemicals corrosive to stainless steel (such as NH3, SO2, Cl2, etc.)
    • Ample space for maintenance and inspection
  • Additionally, locate the probe:
    • Away from strong magnetic fields, such as those produced by motors, transformers, solenoid valves, etc.
    • Away from excessive vibration.
    • In a medium free from metallic substances and other foreign matter.

Installation Notes

  • Do not locate your RP series level sensor near inlets/outlets.
  • If there is surface wave action, then use a time-delay relay or stilling tube. If a stilling tube is used, drill vent holes in the tube and use a spacer to ensure the float has free travel inside the tube (See Figure 2.1).
  • The RPE and RPX can be mounted up to 20° from vertical.APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (9)

Mounting Instructions

  • Flange Mounting
    • Provide the compatible mating flange on the tank and install using a suitable gasket.
  • Plug Mounting
    • Provide the compatible female boss on the tank and install the probe with thread tape.

Electrical Installation

DANGER: Do not remove the housing cover until the atmosphere is determined safe, and the power supply is turned off.

For RPX and RPE probes with Housings

  • install conduit and/or cable with necessary seal(s) per Drawing 9001930 or 9001932 for hazardous locations.
  • Remove the housing cover.
  • Check the Wire Color and Terminal Tables on page 6 before making any connections.
  • Connect the wire for your system to the appropriate terminal.
  • Replace the housing cover.

For RPE probes with hookup wires

  • Pull probe hookup wires through the conduit as appropriate before attaching the conduit to the top of the probe.
  • Check the Wire Color and Terminal Tables on page 6 before making any connections.
  • Connect the wires from the probe to your system appropriately.

IMPORTANT: Your RPX MUST be installed according to drawing 9001930 (IS Hazardous Installation Drawing For RPX) or 9001932 (Hazardous Mounting Drawing RPX) to meet the listed approvals. The faulty installation will invalidate all safety approvals and ratings.

Removal Instructions

  • Removing your RP probe from service must be done with care.
  • Ensure all circuits are de-energized, and any hazardous atmosphere has dispersed.
  • Disconnect wires, at terminals in the RP head or at your system.
  • Remove the RP with an appropriately sized wrench (per your mounting type).
  • Clean the RP’s stem float of any debris (see General Care) and inspect for damage.
  • Store your RP in a dry place, at a temperature between -40° and 40°C (-40° and 104°F).

Maintenance

General Care

Your RP series continuous-level probe is very low maintenance and will need little care as long as it is installed correctly. However, in general, you should:

  • Periodically inspect the stem and float for any trapped debris, sediment, or other foreign material.
  • Avoid applications for which the RP was not designed, such as extreme temperatures, contact with incompatible corrosive chemicals, or other damaging environments.
  • If your RPX or RPE has an NPT mount, inspect the threads whenever you remove it from duty or change its location.
  • For units with housing, never leave the housing cover off. If the cover is damaged or lost, order a replacement immediately.

Offset and Span Calibration (4-20 mA output probes only)

NOTE: This procedure can be performed in a non-hazardous area, either before installation or by temporarily uninstalling your 4-20 mA RP probe.

  1. Remove the housing cover.
  2. Set the DC power supply to 24 VDC, and connect to the RP probe, with an ammeter in the loop.
  3. Move float to the desired position for 4 mA output.
  4. Using a jeweler’s screwdriver or a suitable instrument, adjust the “Offset” potentiometer until you have a 4 mA output.
  5. Move float to the desired position for 20 mA output.
  6. Using a jeweler’s screwdriver or a suitable instrument, adjust the “Span” potentiometer until you have a 20 mA output.
  7. Repeat steps 3 – 6 as necessary to fine-tune calibration.APG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (10)

NOTE: You may also return the RP probe to the factory for repair and/or adjustment.

Repair and Returns

Should your RPX or RPE require service, please contact the factory via phone, email, or online chat. We will issue you a Return Material Authorization (RMA) number with instructions.

Please have your probe’s part number and serial number available. See Warranty & Warranty Restrictions for more information.

Hazardous Location Installation and Certification

  • IS Hazardous Installation Drawing For RPXAPG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (11)
  • Hazardous Mounting Drawing RPXAPG-RPE-Resistive-Chain-Continuous-Level-Probes-FIG-1 (12)

CSA Certificate of Compliance

Certificate of Compliance

  • Certificate: 2167400
  • Master Contract: 237484
  • Project: 70193876
  • Date Issued: 2019-04-09
  • Issued To: Automation Products Group Inc 1025 West 1700 North Logan, Utah, 84321 United States
  • Attention: Joe James

The products listed below are eligible to bear the CSA Mark shown with adjacent indicators ‘C’ and ‘US’ for Canada and US or with adjacent indicator ‘US’ for US only or without either indicator for Canada only.

  • Issued by: Albert Jansen Albert Jansen

PRODUCTS

  • CLASS 2252 06 – PROCESS CONTROL EQUIPMENT
  • CLASS 2252 86 – PROCESS CONTROL EQUIPMENT (Certified to U.S. Standards)
  • Float Level Sensors, permanently connected, indoor and outdoor use, max. operating ambient 85°C:
  • Models FLXx and FLRx, rated 220 V, 0.5 A;
  • Models RPMx, RPXx, and RPEx, rated 5 – 15 Vdc, 100 mA, or 12 to 24 Vdc, 4-20mA;
  • Model RPAx rated 12 to 24 Vdc, 4-20mA;
  • Model CTR-0100 (P/Ns 110101 and 110101-0001), Loop Powered 4-20mA Module, rated 4-20mA output is 12 to 24 Vdc.

Note: The above models are Pollution Degree 2, Measurement Category II.

Notes for Models FLXx, FLRx, RPMx, RPAx, RPXx, RPEx:

  1. The “x” in the Model designations may be any alpha-numeric character, to denote minor mechanical options, not affecting safety. Refer to Illustration 28 for Model designator and suffix details.
  2. The equipment is intended to be installed as required by the applicable electrical code (CEC, NEC) and as specified by the manufacturer’s Installation Instructions.
  3. The circuit board P/N STF-CTR-01** from the Model RPMx Probe may be supplied as a part where the suitability of the final installation will be inspected by the authority with jurisdiction in the area where installed.
  4. The installation will be inspected by the authority with jurisdiction in the area where installed.
    • FS-400, FS-410, and FS-500 float switches. Single Seal (MWP 1000psi). Ambient temperature -40°C to 260°C.
    • Type 4X (NPT Connection Only). Ratings as follows:
      • 0.416A, 240Vac (50/60 Hz)
      • 0.833A, 120Vac (50/60 Hz)/Vdc
      • 1.00A, ≤100Vac (50/60 Hz)/Vdc
    • Conditions of Acceptability for FS-400, FS-410, and FS-500
      • The equipment must be connected to a purely resistive load
      • The equipment must be grounded through the final installation
      • CLASS 2258 02 – PROCESS CONTROL EQUIPMENT – FOR HAZARDOUS LOCATIONS
      • CLASS 2258 82 – PROCESS CONTROL EQUIPMENT – FOR HAZARDOUS LOCATIONS, U.S. Requirements

Class I, Division 1, Groups C, and D T3

  • Float Level Sensors, model FLXx, rated 220 V, 0.5 A, max. or rated 24Vdc, 0.5A, max., and model RPMx and RPXx, rated 5 – 24 Vdc, 100mA or 12 to 24 Vdc, 4-20mA; operating ambient 40°C.

Ex d, IIB T3 Class I, Zone 1, AEx d, IIB T3

  • Float Level Sensors, model FLXx, rated 24 Vdc, 0.5 A, max., and model RPMx and RPXx, rated 5 – 24 Vdc, 100mA or 12 to 24 Vdc, 4-20mA; operating ambient 40°C.

Notes for Models FLXx, RPMx, RPXx:

  1. The “x” in the Model designations may be any alpha-numeric character, to denote minor mechanical options, not affecting safety.
  2. The equipment is intended to be installed as required by the applicable electrical code (CEC, NEC) and as specified by the manufacturer’s Installation Instructions.
  3. The installation will be inspected by the authority with jurisdiction in the area where installed.

Class I, Division 2, Groups C, and D T3

Float Level Sensor model FLXx, rated 220 V, 0.5 A, model RPMx and RPXx, rated 5 – 15 Vdc, 100mA, or rated 12 to 24 Vdc, 4-20mA, and model RPAx, rated 12 to 24 Vdc, 4-20mA; max; operating ambient 85°C.

Notes for Models FLXx, RPMx, RPAx, RPXx:

  1. The “x” in the Model designations may be any alpha-numeric character, to denote minor mechanical options, not affecting safety.
  2. The equipment is intended to be installed as required by the applicable electrical code (CEC, NEC) and as specified by the manufacturer’s Installation Instructions.
  3. The installation will be inspected by the authority with jurisdiction in the area where installed.
    • Class I Division 1 Groups A, B, C, and D, Class II Division 1 Groups E, F, Class III; T3
    • Class I Division 2 Groups A, B, C, and D, Class II Division 2 Groups F, G; T200°C
    • FS-400, FS-410, and FS-500 (NPT Connection) float switches. Single Seal (MWP 1000psi). Ambient temperature -40°C to 187°C. Type 4X. Seal Not Required. Ratings as follows:
      • 0.416A, 240Vac (50/60 Hz)
      • 0.833A, 120Vac (50/60 Hz)/Vdc
      • 1.00A, ≤100Vac (50/60 Hz)/Vdc

Conditions of Acceptability

  • The equipment must be connected to a purely resistive load
  • The equipment must be grounded through the final installation
  • CLASS 2258 03 – PROCESS CONTROL EQUIPMENT – INTRINSICALLY SAFE AND NON INCENDIVE
  • SYSTEMS – FOR HAZARDOUS LOCATIONS
  • CLASS 2258 83 PROCESS CONTROL EQUIPMENT – INTRINSICALLY SAFE AND NON INCENDIVE SYSTEMS – FOR HAZARDOUS LOCATIONS, CERTIFIED TO U.S. STANDARDS

Class I, Division 2, Groups C, and D T3

  • Float Level Sensor model RPMx and RPXx, rated 5 – 15 Vdc, 100mA, or rated 12 to 24 Vdc, 4-20mA, and model RPAx, rated 12 to 24 Vdc, 4-20mA; max; operating ambient 85°C. Field wiring is non-incendive when installed per drawings 9001415, 9001932, and 9002023 respectively.

Notes for Models RPMx, RPAx, RPXx:

  1. The “x” in the Model designations may be any alpha-numeric character, to denote minor mechanical options, not affecting safety.
  2. The equipment is intended to be installed as required by the applicable electrical code (CEC, NEC) and as specified by the manufacturers Installation Instructions.
  3. The installation will be inspected by the authority with jurisdiction in the area where installed.
    • CLASS 2258 04 – PROCESS CONTROL EQUIPMENT – INTRINSICALLY SAFE, ENTITY – FOR HAZARDOUS LOCATIONS
    • CLASS 2258 84 – PROCESS CONTROL EQUIPMENT – INTRINSICALLY SAFE, ENTITY – FOR HAZARDOUS LOCATIONS, U.S. Requirements

Class I, Division 1, Groups C, and D

Float Level Sensors, model RPMx, RPAx, RPXx, and model CTRx loop powered 24Vdc, 4-20mA converter module, max. operating ambient 85°C; Temperature Code rating T3C; Intrinsically Safe when connected as per drawing 9001414, 9001423 and 9001930 with the following Entity Parameters: Vmax = 30V, Imax = 130mA, Ci = 3nF, Li = 0uH.

Notes for Models RPMx, RPAx and RPXx:

  1. The “x” in the Model designations may be any alpha-numeric character, to denote minor mechanical options, not affecting safety.
  2. The equipment is intended to be installed as required by the applicable electrical code (CEC, NEC) and as specified by the manufacturers Installation Instructions.
  3. The installation will be inspected by the authority with jurisdiction in the area where installed.

APPLICABLE REQUIREMENTS

Standard Title
CSA C22.2 No. 0-10 General Requirements – Canadian Electrical Code, Part II
CSA C22.2 No. 25-17 Enclosures for use in Class II, Division 1, Groups E, F, and G hazardous locations
CSA C22.2 No. 30-M1987 Explosion-Proof Enclosures for Use in Class I Hazardous Locations
CAN/CSA C22.2 No. 61010-1-12 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements
CSA C22.2 No. 157-M1992 Intrinsically Safe and Non-Incendive Equipment for Use in Hazardous Locations
CSA C22.2 No. 213-17 Non-Incendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations
CSA C22.2 No. 60079-0:15 Explosive atmospheres – Part 0: Equipment – General requirements
CSA C22.2 No. 60079-1:11 Explosive atmospheres – Part 1: Equipment protection by flameproof enclosures “d”
ANSI/UL 61010-1 (3rd Edition) Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use – Part 1: General Requirements
UL 913, Eighth Edition Intrinsically Safe Apparatus and Associated Apparatus for use in Class I, II, III, Division 1, Hazardous (Classified) Locations
UL1203, Fifth Edition Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations
UL/ISA 60079-0, Sixth Edition Explosive atmospheres – Part 0: Equipment – General requirements
UL/ISA 60079-1, Seventh Edition Explosive Atmospheres – Part 1: Equipment Protection by Flameproof Enclosures “d”
FM 3611, December 2018 Nonincendive Electrical Equipment for Use in Class I and II, Divisions 1 and 2 Hazardous (Classified) Locations

CONTACT INFORMATION

Documents / Resources

APG RPE Resistive Chain Continuous Level Probes [pdf] User Manual
RPE, RPX, RPE Resistive Chain Continuous Level Probes, RPE, Resistive Chain Continuous Level Probes, Chain Continuous Level Probes, Continuous Level Probes, Level Probes, Probes