Altronix T2MK3F4D Trove2-Mercury Kits with PTC Outputs Instruction Manual
Altronix T2MK3F4D Trove2-Mercury Kits with PTC Outputs

Altronix Trove2/Mercury Kits with PTC Outputs

4 Door Kits

T2MK3F4D
Fully assembled kit includes:

  • Trove2 enclosure with
    TM2 Altronix/Mercury backplane
  • (1) eFlow6NB – Power Supply/Charger
  • (1) ACM4CB – PTC Access Power Controller
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module

T2MK3F4DQ
Fully assembled kit includes:

  • Trove2 enclosure with
  • TM2 Altronix/Mercury backplane
  • (1) eFlow6NB – Power Supply/Charger
  • (1) LINQ2 – Network Communications Module
  • (1) ACM4CB – PTC Access Power Controller
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module
8 Door Kits

T2MK3F8D
Fully assembled kit includes:

  • Trove2 enclosure with
    TM2 Altronix/Mercury backplane
  • (1) eFlow6NB – Power Supply/Charger
  • (1) ACM8CB – PTC Access Power Controller
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module

T2MK3F8DQ
Fully assembled kit includes:

  • Trove2 enclosure with
    TM2 Altronix/Mercury backplane
  • (1) eFlow6NB – Power Supply/Charger
  • (1) LINQ2 – Network Communications Module
  • (1) ACM8CB- PTC Access Power Controller
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module

T2MK7F8D
Fully assembled kit includes:

  • Trove2 enclosure with
    TM2 Altronix/Mercury backplane
  • (1) eFlow104NB – Power Supply/Charger
  • (1) ACM8CB- PTC Access Power Controller
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module

T2MK7F8DQ
Fully assembled kit includes:

  • Trove2 enclosure with
    TM2 Altronix/Mercury backplane
  • (1) eFlow104NB – Power Supply/Charger
  • (1) LINQ2 – Network Communications Module
  • (1) ACM8CB- PTC Access Power Controller
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module
16 Door Kits

T2MK75F16D
Fully assembled kit includes:

  • Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane
  • (1) eFlow104NB and (1) eFlow102NB – Power Supply/Chargers
  • (2) ACM8CB – PTC Access Power Controllers
  • (1) PD16WCB – PTC Power Distribution Module

T2MK75F16DQ
Fully assembled kit includes:

  • Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane
  • (1) eFlow104NB and (1) eFlow102NB – Power Supply/Chargers
  • (1) LINQ2 – Network Communications Module
  • (2) ACM8CB – PTC Access Power Controllers
  • (1) PD16WCB – PTC Power Distribution Module

T2MK77F16D
Fully assembled kit includes:

  • Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane
  • (2) eFlow104NB – Power Supply/Chargers
  • (2) ACM8CB – PTC Access Power Controllers
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module

T2MK77F16DQ
Fully assembled kit includes:

  • Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane
  • (2) eFlow104NB – Power Supply/Chargers
  • (1) LINQ2 – Network Communications Module
  • (2) ACM8CB – PTC Access Power Controllers
  • (1) VR6 – Voltage Regulator
  • (1) PDS8CB – Dual Input PTC
    Power Distribution Module

Overview

Altronix Trove Mercury kits are pre-assembled and consist of Trove2M2 enclosure with factory installed Altronix power supply/charger(s) and sub-assemblies.
These kits also accommodate various combinations of Mercury boards for up to sixteen (16) doors in a single enclosure.

Configuration Chart

Altronix Model Number Networkable 120VAC 60Hz Input Current (A) Power Supply Board Input Fuse Rating Power Supply Board Battery Fuse Rating Nominal DC Output Voltage  

Maximum Supply Current for Main and Aux. Outputs on Power Supply board and ACM4CB/

ACM8CB Access Power Controller’s

outputs

Fail-Safe/Fail-Secure Auto-Resettable Outputs Current Per ACM4CB/ACM8CB Output (A) ACM4CB/ACM8CB Board Input Fuse Rating ACM4CB/ACM8CB Board Output PTC Rating PDS8CB Board Input Fuse Rating PDS8CB Board Output PTC Rating PD8ULCB/PD16WCB Board Output PTC Rating
Power Supply 1 Power Supply 2
[DC] [Aux] [DC] [Aux]
Output Range (VDC) Output Range (VDC) Output Range (VDC) Output Range (VDC)
T2MK3F4D 3.5 5A/ 250V 10A/ 32V 20.19- 26.4 20.19- 26.4 24VDC @ 5.8A 4 2.0 10A/

250V

2A 10A/ 250V 2A
T2MK3F4DQ P 3.5 5A/ 250V 10A/ 32V 20.19- 26.4 20.19- 26.4 24VDC @ 5.8A 4 2.0 10A/

250V

2A 10A/ 250V 2A
T2MK3F8D 3.5 5A/ 250V 10A/ 32V 20.19- 26.4 20.19- 26.4 24VDC @ 5.8A 8 2.0 10A/

250V

2A 10A/250V 2A
T2MK3F8DQ P 3.5 5A/ 250V 10A/ 32V 20.19- 26.4 20.19- 26.4 24VDC @ 5.8A 8 2.0 10A/

250V

2A 10A/ 250V 2A
T2MK7F8D 4.5 6.3A/, 250V 15A/ 32V 20.17- 26.4 20.28- 26.4 24VDC @ 9.2A 8 2.0 10A/

250V

2A 10A/ 250V 2A
T2MK7F8DQ P 4.5 6.3A/ 250V 15A/ 32V 20.17- 26.4 20.28- 26.4 24VDC @ 9.2A 8 2.0 10A/

250V

2A 10A/ 250V 2A
T2MK75F16D 8 6.3A/ 250V  

15A/ 32V

 

20.17- 26.4

 

20.28- 26.4

 

9.7- 13.2

 

10.03-

13.2

 

12VDC @ 9.3A
24VDC @ 9.2A

16 2.0  

10A/ 250V

2A 2A
5A/ 250V
T2MK75F16DQ P 8 6.3A/ 250V  

15A/ 32V

 

20.17- 26.4

 

20.28- 26.4

 

9.7- 13.2

 

10.03- 13.2

 

12VDC @ 9.3A 24VDC @ 9.2A

16 2.0 10A/ 250V 2A 2A
5A/ 250V
T2MK77F16D 9 6.3A/ 250V 15A/ 32V 20.17- 26.4 20.28- 26.4 20.17- 26.4 20.28- 26.4 24VDC @ 9.2A 16 2.0 10A/ 250V 2A 10A/ 250V 2A
T2MK77F16DQ P 9 6.3A/ 250V 15A/ 32V 20.17- 26.4 20.28/ 26.4 20.17- 26.4 20.28- 26.4 24VDC @ 9.2A 16 2.0 10A/ 250V 2A 10A/ 250V 2A

Installation Instructions

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.

  1. Remove backplane(s) from enclosure. Do not discard hardware.
  2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
  3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
    Installation Instructions
  4. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB, eFlow102NB, eFlow104NB and Sub-Assembly Installation Guide for the following models: ACM4CB, ACM8CB, LINQ2, PDS8CB, VR6 for further installation instructions.
  5. Fasten snap on spacers onto metal pems configuration of backplane depending on the Mercury access controller
    (Fig. 2-5).
  6. Position Mercury access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2-5).
  7. Mount backplane to enclosure with hardware.
T2MK3F4D, T2MK3F4DQ, T2MK3F8D, T2MK3F8DQ: Configuration of Mercury Boards
  1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 2).
  2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2a)
  3. Mount backplane to enclosure with hardware.
    Configuration

Access Controller Position Chart for the Following Models:

Mercury Access Controller

Pem Mounting

EP1502, MR52, MR16IN, MR16OUT

A
EP2500, MUX8

B

EP1501, MR51e

C
MR50

D

T2MK7F8D, T2MK7F8Q: Configuration of Mercury Boards
  1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig.3).
  2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig.3a).
  3. Mount backplane to enclosure with hardware.
    Configuration

Access Controller Position Chart for the Following Models:

Mercury Access Controller

Pem Mounting
EP1502, MR52, MR16IN, MR16OUT

A

EP2500, MUX8

B
EP1501, MR51e

C

MR50

D

T2MK75F16D, T2MK75F16DQ: Configuration of Mercury Boards
  1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig.4).
  2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig.4a).
  3. Mount backplane to enclosure with hardware.
    Configuration

Access Controller Position Chart for the Following Models:

Mercury Access Controller

Pem Mounting

EP1502, MR52, MR16IN, MR16OUT

A
EP2500, MUX8

B

EP1501, MR51e

C
MR50

D

T2MK77F16D, T2MK77F16DQ: Configuration of Mercury Boards
  1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig.5).
  2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig.5a).
  3. Mount backplane to enclosure with hardware.
    Configuration

Access Controller Position Chart for the Following Models:

Mercury Access Controller

Pem Mounting

EP1502, MR52, MR16IN, MR16OUT

A
EP2500, MUX8

B

EP1501, MR51 e

C
MR50

D

TMV2 (T2MK75F16D, T2MK75F16DQ, T2MK77F16D, and T2MK77F16DQ):

TMV2 accommodates a variety of Mercury boards with or without Altronix sub-assemblies for access systems.

Configuration of Mercury and/or Altronix Boards

Mercury Access Controllers:

  1. Fasten spacers onto metal pems configuration (A) (B) of backplane depending on the access controller (Fig.6).
  2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig.6a).
  3. Mount backplane to enclosure with hardware.

Altronix Sub-Assemblies and/or Adapters:

  1. Fasten spacers to pems which match the hole pattern (C) for Altronix Sub-Assemblies (Fig. 6, 6a).
  2. Mount boards to spacers utilizing pan head screws provided with the product (Fig. 6).
    Configuration

Access Controller Position Chart for the Following Models:

Mercury

Access Controller

Pem Mounting
EP1502, MR52, MR16IN, MR16OUT

A

EP2500, MUX8

B

Altronix

Sub-Assembly or Adapter

Pem Mounting
ACM4(CB), MOM5, PD4UL(CB), PD8UL(CB), PDS8(CB), VR6, GB1 (Genetec Synergis Cloud Link adapter plate)

C

Dimensions

Enclosure Dimensions (H x W x D approximate):
27.25” x 21.5” x 6.5” (692.2mm x 552.5mm x 165.1mm)
Dimensions

All registered trademarks are property of their respective owners.
Rev. TMKD060117
Installing Company: _________________________
Service Rep. Name: _________________________
Address: _________________________
Phone #: _________________________

Support

Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
web site: www.altronix.com
e-mail: info@altronix.com
Lifetime Warranty
IITrove2/Mercury PTC Kits

Logo

Documents / Resources

Altronix T2MK3F4D Trove2-Mercury Kits with PTC Outputs [pdf] Instruction Manual
T2MK3F4D Trove2-Mercury Kits with PTC Outputs, T2MK3F4D, Trove2-Mercury Kits with PTC Outputs, PTC Outputs, Trove2-Mercury Kits
Altronix T2MK3F4D Trove2-Mercury Kits with PTC Outputs [pdf] Installation Guide
T2MK3F4D, T2MK3F8D, T2MK75F16D, T2MK75F16DQ, T2MK3F4D Trove2-Mercury Kits with PTC Outputs, T2MK3F4D, Trove2-Mercury Kits with PTC Outputs, T2MK3F4DQ, T2MK3F8DQ, T2MK77F16D, T2MK7F8D, T2MK75F16DQ, Trove2-Mercury Kits, Mercury Kits

References

Leave a comment

Your email address will not be published. Required fields are marked *