Altronix logoBC750
Access Power and Control Enclosure for
Maximal Fit Series
Installation Guide

BC750 Access Power and Control Enclosure for Maximal Fit Series

Rev. 071020
Installing Company: ______________ Service Rep. Name: _________
Address: _______________ Phone #: __________
Overview:
Altronix BC750 accommodates various combinations of Altronix power supplies and accessories for access systems.

Specifications:

Features:

  • 16 Gauge enclosure with ample knockouts for convenient access.
  • Includes: tamper switch, cam lock, and mounting hardware.

Battery Backup:
Accommodates up to four (4) 12VDC/12AH batteries.
Enclosure Dimensions (H x W x D):
20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm).

Installation Instructions:

  1. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws; level and secure. Mark the position of the lower holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 16).
  2. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in the desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect the tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate the alarm signal open the door of the enclosure.
    Altronix BC750 Access Power and Control Enclosure for Maximal Fit Series - Fig 1
  3. Fasten spacers (provided) to poems that match the hole pattern for Altronix Power Supply/Chargers, Transformers, or Sub-Assembly boards (positions (A), (B), (C), (D) and (E) (Fig. 2, pg. 2).
  4. Mount boards to spacers utilizing 5/16” pan head screws (provided) (Fig. 2a, pg. 2).
  5. For detailed information about installing and connecting Altronix sub-assemblies refer to the individual Installation Guides listed in the

Compatible Power Supplies and Sub-Assemblies Chart, pg. 3.
Altronix BC750 Access Power and Control Enclosure for Maximal Fit Series - Fig 2

Compatible Power Supplies and Sub-Assemblies Chart:

Altronix Power Supplies

Altronix Model Number

Pem Mounting Input Rating Output Rating

Refer To:

eFlow4NB*

A

120VAC, 60Hz, 3.5A 12VDC or 24VDC @ 4A  eFlow Installation Guide Rev. EFNB-021319
eFlow6NB* 120VAC, 60Hz, 3.5A 12VDC or 24VDC @ 6A
eFlow102NB* 120VAC, 60Hz, 3.5A 12VDC @ 10A
eFlow104NB* 120VAC, 60Hz, 4.5A 24VDC @ 10A
Tango1B PoE up to 90W 12VDC up to 6A (72W) and/or 24VDC up to 3A (72W) Tango1B Installation Guide Rev. TANGO-071119
PoE201** 115VAC, 60 Hz, 2.5A or 230VAC, 50/60 Hz, 1.3A 56VDC @ 2.2A (120W) PoE201 Installation Guide Rev. 01162017
PoE60** 115VAC, 60 Hz, 2.5A or
230VAC, 50/60 Hz, 1.3A
56VDC @ 1.3A (75W)
Charger for LiFePO4 batteries
PoE60 Installation Guide Rev. 12242018
VR6

B

24VDC @ 1.75A or 3.5A 5VDC or 12VDC @ 6A VR6 Installation Guide Rev. 050517
AL175ULB 24VAC, 40VA
Class 2 transformer
12VDC or 24VDC @ 1.75A AL175ULB Installation Guide Rev. 081601
AL176ULB 28VAC, 56VA
Class 2 transformer
12VDC or 24VDC @ 1.75A AL176ULB Installation Guide Rev. 081701

Altronix Transformers

Altronix Model Number

Pem Mounting Input Rating Output Rating

Refer To:

T12100

C

115VAC, 50/60Hz, 1A 12VAC @ 8.3A T12100 Installation Guide Rev. 051512
T16100 115VAC, 50/60Hz, 0.5A 16VAC @ 6.25A T16100 Installation Guide Rev. 051612
T2428100 115VAC, 50/60Hz, 1A 24 @ 4A or 28VAC @ 3.5A T2428100 Installation Guide Rev. 051612

Altronix Sub-Assemblies

Altronix Model Number

Pem Mounting Description

Refer To:

LINQ8ACM(CB)

A

Networked 8-Fused (or PTC) Output Access Power Controller LINQ8ACM(CB) Installation Guide Rev. 100219
ACMS8(CB) 8 Fused (or PTC) Dual Input Access Power Controller ACMS8(CB) Installation Guide Rev. 073019
ACM8(CB) 8 Fused (or PTC) Output Access Power Controller ACM8(CB) Installation Guide Rev. 031819
LINQ8PD(CB)

B

Networked 8-Fused (or PTC) Output Power Distribution Module LINQ8PD(CB) Installation Guide Rev. 012918
ACM4(CB) 4 Fused (or PTC) Output Access Power Controller ACM4(CB) Installation Guide Rev. 052819
MOM5 5 PTC Output Power Distribution Module w/Fire Alarm Interface MOM5 Installation Guide Rev. 020119
PD4UL(CB) 4 Fused (or PTC) Output Power Distribution Module PD4UL Installation Guide Rev. 020119
PD4ULCB Installation Guide Rev. 020119
PD8UL(CB) 8 Fused (or PTC) Output Power Distribution Module PD8UL Installation Guide Rev. 020119
PD8ULCB Installation Guide Rev. 020119
PDS8(CB) 8 Fused (or PTC) Dual Input Power Distribution Module PDS8/PDS8CB Installation Guide Rev. 070116
PD16W(CB) D 16 Fused (or PTC) Output Power Distribution Module PD16W/PD16WCB Installation Guide Rev. 020119
LINQ2* F Network Communication Module LINQ2 Installation Guide Rev. 060514

Altronix Ethernet over Fiber PoE+ Switches

Altronix Model Number

Pem Mounting Description

Refer To:

NetWaySP3B**

E

Single 1G Fiber SFP, 3 port 10/100/1000
(2 ports PoE/PoE+ 60W Hi-PoE & 1 port PoE/PoE+)
NetWaySP3 Installation Guide Rev. 020917
NetWay4EB** Single 1G Fiber SFP, 4 port 10/100 PoE/PoE+, configurable for 2x 60W Hi-PoE NetWay4EWP Installation Guide Rev. 090616
NetWaySP4B** Dual 1G Fiber SFP, 4x 10/100/1000 PoE/PoE+, configurable for 2x 60W Hi-PoE NetWaySP4 Installation Guide Rev. 032917
NetWaySP8B** Dual 1G Fiber SFP, 2 ports 10/100/1000 PoE/PoE+, configurable for 2x 60W Hi-PoE & 6 ports 10/100 PoE/PoE+ NetWaySP8 Installation Guide Rev. 032117

* LINQ2 can be installed when utilizing eFlow power supply/charger boards.
** Altronix NetWay Spectrum Switches are compatible with PoE201 and PoE60 power supplies.

BC750 Enclosure Dimensions:

20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm)
Altronix BC750 Access Power and Control Enclosure for Maximal Fit Series - Fig 3
Altronix is not responsible for any typographical errors.

140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
website: www.altronix.com
e-mail: info@altronix.com
IIBC750
L08U
Altronix BC750 Access Power and Control Enclosure for Maximal Fit Series - logo2

Documents / Resources

Altronix BC750 Access Power and Control Enclosure for Maximal Fit Series [pdf] Installation Guide
BC750 Access Power and Control Enclosure for Maximal Fit Series, BC750, Access Power and Control Enclosure for Maximal Fit Series, Access Power and Control Enclosure, Control Enclosure, Enclosure, Access Power, Power
Altronix BC750 Access Power and Control Enclosure for Maximal Fit Series [pdf] Installation Guide
BC750 Access Power and Control Enclosure for Maximal Fit Series, BC750, Access Power and Control Enclosure for Maximal Fit Series, for Maximal Fit Series, Fit Series

References

Leave a comment