AKO D1 Series Temperature Controller

AKO-D1-Series-Temperature-Controller-PRODUCT

Product Information

Specifications

  • Model: AKO-D141xx/D101xx
  • Temperature Indication: Yes
  • Programming Access: Yes
  • Time for Access: 5 seconds for set point, 10 seconds for programming

Product Usage Instructions

Accessing Set Point and Programming

To access the set point:

  • For AKO-D141xx/D101xx: Press and hold SET for 5 seconds.
  • For AKO-D140xx: Press and hold SET for 5 seconds.

To access programming:

  • For AKO-D141xx/D101xx: Press and hold SET for 10 seconds.
  • For AKO-D140xx: Press and hold SET for 10 seconds.

Temperature Indication

Release SET to access the set point or programming based on the specific model.

FAQ

  • Q: How do I enter programming mode?
    • A: To enter programming mode, for AKO-D141xx/D101xx, press and hold SET for 10 seconds. For AKO-D140xx, do the same for 10 seconds.
  • Q: How do I access the set point?
    • A: To access the set point, for AKO-D141xx/D101xx, press and hold SET for 5 seconds. For AKO-D140xx, do the same for 5 seconds.
  • Q: What happens if no key is pressed for 20 seconds?
    • A: The equipment will return to the previous level. If you are on level 3, the changes will not be saved.

Access to set point and programming

AKO-D141xx/D101xxAKO-D1-Series-Temperature-Controller-FIG-1

AKO-D140xxAKO-D1-Series-Temperature-Controller-FIG-2

Programming Menu

Programming Menu parameters

After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved.

AKO-D141xx/D101xx

PROGRAMMINGAKO-D1-Series-Temperature-Controller-FIG-3

AKO-D140xx

PROGRAMMINGAKO-D1-Series-Temperature-Controller-FIG-4

Changeset point

AKO-D1-Series-Temperature-Controller-FIG-5

  • AKO-D1-Series-Temperature-Controller-FIG-6Change Menu
  • AKO-D1-Series-Temperature-Controller-FIG-7Cambiare menu
  • AKO-D1-Series-Temperature-Controller-FIG-8Change Menu
  • A) Temperature Indication
  • B) Level 1 Menu
  • C) Level 2 Parameters
  • D) Level 3 Values
  • E) Current Value
  • F) New Value

Parameters and messages

Table of parameters and messages

  • Def. column shows factory-set default parameters. Those marked with * are variable parameters depending on the application chosen in the wizard. Unless otherwise stated, temperatures are expressed in °C. (Equivalent velues in °F)
AKO-D14023-C
AKO-D14012, AKO-D14023  
AKO-D14120, AKO-D14123, AKO-D10123  
Level1 Menus and description            
rE Leve l 2         Control      
    Level 3        Description                                   Values Min. Def. Max.      
        99.9 AKO-D1-Series-Temperature-Controller-FIG-9    
SP Temperature Adjustment (Set Point)                                               With NTC (ºC/ºF)

(limits depending on probe type)                                                    With PTC

-50.0 (-58ºF) (210ºF)
150 (302ºF) AKO-D1-Series-Temperature-Controller-FIG-9    
C0 Calibrating probe 1 (Offset)                                                                        (ºC/ºF) -20.0 0.0 20.0 AKO-D1-Series-Temperature-Controller-FIG-9    
C1 Probe 1 differential (Histeresis)                                                                    (ºC/ºF) 0.1 2.0 20.0 AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
      99.9 99.9 AKO-D1-Series-Temperature-Controller-FIG-9    
C2 Upper blocking of the set point                                                    With NTC (ºC/ºF)

(cannot be set above this value)                                                     With PTC

C3 (210ºF) (210ºF)
150 (302ºF) AKO-D1-Series-Temperature-Controller-FIG-9    
C3 Lower blocking of the set point (cannot be set below this value)                             (ºC/ºF) -50.0 -50.0 C2 AKO-D1-Series-Temperature-Controller-FIG-9    
(-58ºF) (-58ºF)
C4 Type of delay for protection of the compressor: 0=OFF/ON (since the last disconnection) 0 0 1 AKO-D1-Series-Temperature-Controller-FIG-9    
1=OFF-ON/ON-OFF (since the last shut-down /start-up)
C5 Protection delay time (value of the option selected in parameter C4)                      (min.) 0 0 120 AKO-D1-Series-Temperature-Controller-FIG-9    
C6 Status of the COOL relay with probe fault 0=OFF; 1=ON; 0 2 2 AKO-D1-Series-Temperature-Controller-FIG-9    
2=Average based on the last 24 hours before the probe fault
EP Exit to Level 1       AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
dEF Leve l 2         DEFROST Control (if P0=0 Direct, Cold)      
    Level 3        Description                                   Values Min. Def. Max. AKO-D1-Series-Temperature-Controller-FIG-9    
d0 Defrost frequency (Time between two starts)                                                     (h.) 0   96 AKO-D1-Series-Temperature-Controller-FIG-9    
d1 Maximum defrost duration (0=defrost deactivated)                                            (min.) 0 0 255 AKO-D1-Series-Temperature-Controller-FIG-9   AKO-D1-Series-Temperature-Controller-FIG-10
d2 Type of message during defrosting: 0=Current temperature;

1=Temperature at start of defrost; 2=Display dEF message

0 2 2 AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
d3 Maximum duration of the message (time added at the end of the defrost)                     (min.) 0 5 255 AKO-D1-Series-Temperature-Controller-FIG-9    
EP Exit to Level 1       AKO-D1-Series-Temperature-Controller-FIG-9    
AKO-D14023-C
AKO-D14012, AKO-D14023  
AKO-D14120, AKO-D14123, AKO-D10123  
CnF Leve l 2         General status      
    Level 3        Description                                  Values Min. Def. Max.      
P0 Type of operation 0=Direct, Cold;1=Inverted, Heat 0 * 1 AKO-D1-Series-Temperature-Controller-FIG-9    
P1 Delay of all functions on receiving electrical power                                            (min.) 0 0 255 AKO-D1-Series-Temperature-Controller-FIG-9    
P2 Access code (password) functions 0 0 2 AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
0=Inactive; 1=Block access to parameters; 2=Keyboard lock
P5 Address (only systems with built-in communications) 1 1 255     AKO-D1-Series-Temperature-Controller-FIG-10
P7 Temperature display mode                 0= Integer °C                  1=One decimal in ºC 0 1 3 AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
2=Integer °F                  3=One decimal in °F
P9 Selection of probe type 0=NTC; 1=PTC 0 0 1 AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
EP Exit to Level 1            
tid Lev el 2          Access and information control      
    Level 3        Description                                  Values Min. Def. Max.      
L5 Access code (Password) 0 99 AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
PU Program version (Information)     AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
Pr Program revision (Information)     AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
EP Exit to Level 1       AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
EP Exit Programming       AKO-D1-Series-Temperature-Controller-FIG-9 AKO-D1-Series-Temperature-Controller-FIG-10 AKO-D1-Series-Temperature-Controller-FIG-10
MESSAGES
L5 Access code (Password) request D  
dEF This indicates a defrost is underway. (Only if parameter d2=2) D
E1 Probe 1 faulty (open circuit, crossover, NTC: temp. >110°C or <-55 °C

PTC: temp. >150 °C or <58 °C) – (equivalent limits in °F)

D S
InI Setup wizard (See section“Start-up”) D  
  • D: Displays the message on the display
  • S: Shows the message in the AKONet software (Only AKO-D14023-C)

AKO ELECTROMECÀNICA, S.A.

  • We reserve the right to supply materials that may be slightly different from those described in our Data Sheets.
  • Updated information on our website.
  • We reserve the right to supply materials that may vary slightly differ from those described in our technical specifications.
  • Updated information can be obtained on our website.
  • Av. Roquetes, 30-38
  • 08812 Sant Pere de Ribes
  • Barcelona España
  • www.ako.com
  • ako@ako.com
  • Tel. 34938 142700
  • Fax 34938934054

Documents / Resources

AKO D1 Series Temperature Controller [pdf] User Guide
D14120, D14123, D14012, D14023, D14023-C, D10123, D1 Series Temperature Controller, D1 Series, Temperature Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *