AIRZONE Aidoo Zigbee Controller

Quick Setup & Use
- Assemble and connect the device by performing the screw attachment or double-sided adhesive attachment.
- Disconnect the indoor unit.
- Connect the Aidoo to the Wi‑Fi W950 terminal of the indoor unit using the supplied cable.
- Power the indoor unit, then check the LEDs in the Self‑diagnosis section.
- Start the pairing process by pressing (5) (Start/Stop association process). The LED remains solid red until the device is included in the network.
AIDOO ZIGBEE HISENSE 1X1
(WI-FI PORT) BY AIRZONE
- Device to manage and integrate units remotely. Wireless Zigbee connection. The Aidoo Zigbee by Airzone, with the 3.0 standard, operates in any Zigbee network with other Zigbee-certified devices and controllers from any other manufacturer.
- As a constantly powered node, it will act as a repeater regardless of the vendor in order to increase the reliability of the network.
Functionalities:
- Control of the parameters of the unit.
- VPort for integration via Modbus.
- For further information about our products, go to airzonecontrol.com
Dimension

Technical Specifications
| Connection to Indoor Unit | |
|---|---|
| V max. | 18 Vdc |
| I max. | 137.5 mA |
| V in | 12-16 Vdc |
| Consumption | 216 mW |
| Type of cable | AZPV8WIRE30 |
| Wire section | 6 x 0.2 mm² |
| Wire length | 2.5 m (8.2 ft) |
| Zigbee Communication | |
| Protocol | Zigbee |
| Model | MGM210P |
| Communication frequency | 2.4 GHz |
| Maximum power | Antenna power | + 10 dBm | 1.86 dBi |
| Sensitivity | – 103.9 dBm |
| RS-485 Port | |
| Shielded twisted pair | 2 x 0.22 + 2 x 0.5 mm² (AWG 23 – 2 wired + AWG 20 – 2 wired) Min: 0.2 mm² / Max: 1.5 mm² |
| Communication protocol | MODBUS RS-485 Par – 19200 bps |
| Operating Temperatures | |
| Storage | – 20 … 70 °C (- 4 … 158 °F) |
| Operation | 0 … 45 °C (32 … 113 °F) |
| Operating humidity range | 5 … 90 % (non-condensing) |
| Mechanical Aspects | |
| Protection class | IP 41 |
| Weight | 130 g (0.29 lb) |
| Size (WxHxD) | 92x80x29 mm (3.62×3.15×1.14″) |
| Max. operating height | 2000 m (6561.68 ft) |
DEVICE ELEMENTS
| Nº | Description |
| 1 | Unit connection wires |
| 2 | Puerto RS-485 / RS-485 port / Porta RS-485 |
| 3 | Indoor unit port |
| 4 | Device reboot |
| 5 | Start/Stop association process |
| 6 | Factory reset |

SELF-DIAGNOSIS

ASSEMBLY AND CONNECTION
- Perform the assembly following the next steps:
- a. Screw attachment.
- b. Double-sided adhesive attachment.

- Disconnect the indoor unit.
- Connect the Aidoo to the Wi-Fi W950 terminal of the indoor unit using the supplied cable.

- Power the indoor unit. Check the LEDs (see Self-diagnosis section).
- Start the pairing process by pressing 5. The LED
remains solid red until the device is included in the network.
Change units
Change units ºC/ºF.
Important: It is recommended to maintain an alternative control of the unit for situations in which connection to the network is lost. The unit controller is optional.
Important: The equipment shall be supplied by a limited power source meeting class PS2 of the standard IEC 62368-1.
- This device complies with FCC / ISED regulatory notices.

- This device complies with the requirements of Directive 2014/53/EU. The full declaration at www.airzonecontrol.com.
Troubleshooting
- Need to confirm Zigbee connectivity: Check the self-diagnosis Zigbee icon—steady blue indicates connected to the Zigbee network, while blinking red indicates TX/RX communication with the Zigbee.
- Pairing/association issues: During linking/identification mode, the linking icon shows fast blinking red. If the linking icon is steady red, the device is linking/identified.
- Ensure the association process is started (press (5)) until inclusion completes (LED no longer remains solid red).
- No data exchange with the indoor unit: Check “A” (data transmission to the IU) and “B” (data reception from the IU) indicators—A blinking red and B blinking green indicate activity.
- Device activity/power: Microprocessor activity blinks green under the processor icon; the power icon should be steady red for power supply status.
Documents / Resources
![]() | Aidoo Zigbee Controller |
References
- airzonecontrol.comairzonecontrol.com
- doc.airzone.es/Certificates/Product/REG_AZ6_FCC_ELV_A4_MUL.pdfdoc.airzone.es
- airzonecontrol.comwww.airzonecontrol.com
- airzonecontrol.com/www.airzonecontrol.com
- User Manualmanual.tools