AIKO PV Solar Module Installation Guide

PV Solar Module

Specifications

  • Manufacturer: AIKO
  • Module Types: Dual Glass, Mono Glass
  • Models: AIKO-Axxx-MAH54Dw, AIKO-Axxx-MCE54Dw,
    AIKO-Axxx-MAH60Db, AIKO-Axxx-MAH72Dw, AIKO-Axxx-MAH78Dw,
    AIKO-Axxx-MAH54Db, AIKO-Axxx-MCE54Db, AIKO-Gxxx-MCH72Dw,
    AIKO-Axxx-GRH66Dw, AIKO-Axxx-MAH54Mw, AIKO-Axxx-MAH54Mb,
    AIKO-Axxx-MCE54Mw, AIKO-Axxx-MAH60Mw, AIKO-Axxx-MAH72Mw,
    AIKO-Axxx-MAH54Tm, AIKO-Axxx-MCE54Mb, AIKO-Axxx-MAH60Mb,
    AIKO-Gxxx-MCH72Mw

Product Usage Instructions

01 Overview

Refer to the Installation Manual for detailed information on
laws, acts, general information, storage, transportation
instructions, installation conditions, mechanical and electrical
installation, grounding, and maintenance.

02 Laws and Acts

Ensure compliance with applicable laws and acts such as
electrical regulations, building codes, and electrical connection
requirements based on the installation location and system
specifications.

03 General Information

Ensure proper module identification, wiring methods, general
safety precautions, electrical safety measures, handling safety
guidelines, and fire safety protocols are followed.

04 Storage and Transportation Instructions

Follow guidelines for turnover, handling, and storage of PV
modules to prevent damage during transportation and ensure safe
storage practices.

05 Installation Conditions

Consider location, working environment, and tilt angle selection
when installing PV modules to optimize performance.

06 Mechanical Installation

Adhere to general requirements and guidelines for the mechanical
installation of PV modules to ensure stability and longevity.

07 Electrical Installation

Focus on electrical performance, cables and connections, and
connectors during the electrical installation of PV modules to
maintain efficiency and safety.

08 Grounding

Implement proper grounding techniques as outlined in the manual
to ensure electrical safety and system functionality.

09 Maintenance of PV Modules

Regularly clean the modules, visually inspect for any damage or
issues, check connectors and cables for secure connections, and
contact AIKO Technical Support for assistance if needed.

FAQ

Q: What should I do if I have questions about the installation
or usage of AIKO PV Modules?

A: Contact AIKO customer service personnel for further
explanation and support.

“`

AIKO PV Modules Installation Manual
Website: www.aikosolar.com Email: marketing@aikosolar.com

AIKO PV Modules Installation Manual
AIKO reserves the right to change this Manual without prior notice. Please check the latest version of the Installation Manual in the official website of AIKO
Website: https://www.aikosolar.com/

Module structure

AIKO-Axxx-MAH54Dw AIKO-Axxx-MCE54Dw AIKO-Axxx-MAH60Db AIKO-Axxx-MAH72Dw AIKO-Axxx-MAH78Dw

AIKO-Axxx-MAH54Db AIKO-Axxx-MCE54Db AIKO-Gxxx-MCH72Dw AIKO-Axxx-GRH66Dw

AIKO-Axxx-MAH54Mw

AIKO-Axxx-MAH54Mb

AIKO-Axxx-MCE54Mw AIKO-Axxx-MAH60Mw AIKO-Axxx-MAH72Mw AIKO-Axxx-MAH54Tm

AIKO-Axxx-MCE54Mb AIKO-Axxx-MAH60Mb AIKO-Gxxx-MCH72Mw

Applicable module type Dual Glass
Mono Glass

Table 1: Applicable modules models

Important Safety Information

This Installation Manual provides information regarding the installation and safe use of PV Power Generation Module (hereinafter referred to as “PV modules”produced by Zhejiang Aiko Solar Technology Co., Ltd. (hereinafter referred to as “AIKO”). Installation and day to day maintenance of modules shall be in accordance with all safety precautions specified in this Manual and local laws.
Installing a module system requires specialized skills and knowledge, and modules shall be installed and maintained by qualified personnel. Please read this manual carefully before installing and using this module. The installers shall be familiar with mechanical and electrical requirements of the system. Please keep this Manual for future maintenance or treatment.
If you have any questions, please contact AIKO customer service personnel and ask them to provide further explanation.

CONTENTS

01 Overview

P01

02 Laws and acts

P01

03 General information P02
3.1 Module identification 3.2 Wiring method 3.3 General safety 3.4 Electrical safety 3.5 Handling safety 3.6 Fire safety

04 Storage and trans P07 portation instructions
4.1 Considerations for PV module turnover and handling
4.2 Considerations for PV module turnover and transportation
4.3 Considerations for PV module storage and placement

05 Installation conditions P09
5.1 Location and working environment
5.2 Tilt angle selection

06 Mechanical installation P 1 1
6.1 General requirements 6.2 Mechanical Installation of PV Modules

07 Electrical installation
7.1 Electrical performance 7.2 Cables and Connections 7.3 Connector

P20

08 Grounding

P22

09 Maintenance of PV P24 modules
9.1 Cleaning 9.2 Visual Checks of the PV Modules 9.3 Checks of connectors and cables 9.4 AIKO Technical Support

01 Overview
Thank you very much for choosing the products of Zhejiang Aiko Solar Technology Co., Ltd. (hereinafter referred to as “AIKO” ). This Installation Manual contains important information regarding electrical and mechanical installation which you shall know before installing modules. It also contains some other safety information that you must be familiar with. This installation manual does not entail any explicit or implicit quality warranty and does not stipulate on compensation schemes for losses, module damages or other costs caused by or related to module installation, operation, utilization and maintenance process. When there is a dispute between the parties about the root -cause of module damage, the IEC 61215:2021 static mechanical load test item and the approved maximum static test load should be applied to determine the module quality. AIKO is liable for the losses or expenses incurred only when the module failed above tests. If any infringement of patent rights or third-party rights arises due to the use of the components, AlKO shall not bear any related responsibility. AIKO reserves the rights for modifying product manual or installation manual without advanced notice.It is recommended to visit our website regularly at https://aikosolar.com/ for the latest version of this installation manual. Customer’s failure to install modules according to the requirements listed in this Installation Manual will invalidate the limited product warranty offered to customer. Recommendations in this Manual are provided to improve installation safety, and are based on tests and practical experience. Please provide this Manual to end customers (or consumers) and inform them of all safety, operation and maintenance requirements and recommendations.
02 Laws and acts
Mechanical and electrical installations of PV modules shall be executed by referring to the applicable laws and acts, including the electrical act, building act and electrical connection requirements. These requirements vary from one location to another, such as building rooftop installations and onboard applications. They may also vary with mounting system voltage and current property (DC or AC). Please contact your local authority for further details.

Overview / Laws and acts / General information 01/02
03 General information
3.1 Module ldentification

AlKO PV modules provide Three visual labels.

(1)Nameplate

Product type, information regarding the rated power, rated current, rated voltage, open circuit voltage, short circuit current under standard test conditions (STC), maximum system voltage and certification mark, etc.

(2)Serial number Each individual PV module is identified with a unique serial number which is printed on the barcode and cannot be torn or smeared after lamination. The same serial number can also be found at the side of frame of pV module as well as at the back of PV module.

(3)Packaging List Packaging list including the information of the PV module type, Module barcode information, number of
modules, package weight, package dimension as well as cells color classification. To ensure consistency of the overall color of system when the customer use the modules, the box of PV modules is packaged according to the same color of cells and marking the with S1, S2, S3, on the packing list. Following as a sample:

General information 03/04

3.2 Wiring method

The junction box of AlKO PV modules is located in the middle position. Please refer to the table below for how to connect AlKO PV modules in series.

Position of junction box

Module mounting type
Mounting on the long side, single
row

Connection diagram
Horizontally adjacent modules are directly connected at the shortest distance or, if the wire is too long, by placing the wire into the secondary beam.

Mounting on the long side,
double rows
Mounting on the short side, single
row

1. Horizontally adjacent modules are directly connected at the shortest distance or, if the wire is too long, by placing the wire into the secondary beam;
2. Connections between adjacent rows of modules shall be designed and installed by considering the opposite polarity on the same side as shown below. Adjacent modules are side connected by routing the wire through a duct instead of using an uncovered wire.
In vertical installation, connections between vertically adjacent modules are de- signed and installed with opposite polarities between adjacent modules as shown and the extension line can be placed into the secondary beam.

Mounting on the short side,
multiple rows

1. Vertically adjacent modules as shown below are connected at the shortest di- stance;
2. Connections between adjacent columns of modules shall be designed and installed by considering the opposite polarity on the same side as shown below. Adjacent modules may be side connected by placing the wire into the secondary beam.

Table 2: Connection diagram as per mounting type

3.3 General safety
AlKO PV modules are designed to operate in application according to lEC standards lEC-61215 and lEC-61730. The module can be used in systems with DC voltage greater than 50V or power greater than 240W that may be accessible to the public. Dual glass PV modules are designed with safety Class ll and fire class rating A; Mono glass PV modules are designed with safety Class ll and fire class rating C.
Before to handle and install AIKO PV modules, read carefully and understand this Installation Manual. If you need any explanation, contact AIKO (aikosolar.com). Regardless of whether the module is electrically connected or not, always use appropriate protections such as insulated tools, safety helmets, insulating gloves, safety belts and safety insulating shoes when handling the Pv module whether it is or not connected to the system. Please use the appropriate electrical safety tools when you need to install ground,connect, clean or handle the module.
PV modules generate DC electrical energy when exposed to sunlight or other light source. Direct contact with modules should be avoided, causing electric shock.
Observed local laws and regulations for module installation and obtain a building license or other qualifications where necessary.
PV modules shall be installed by qualified personnel who have specialized skills and knowledge and are familiar with the mechanical and electrical reguirements of the system. Potentially harmful risks during installation, including electrical shock, shall be identified in advance.Installers should be equipped with appropriate safety and personal protective equipment and use them correctly.
Rooftop systems can only be installed on the roofs which have passed the evaluation of construction experts with formal, full structural analysis results. The roof also shall be proven to be able to withstand the weight of the related photovoltaic system.
Observed the safety regulations for all mounting components. For example, wires and cables,connectors, Charge controller, inverters and batteries. Only use equipment, connectors, wires,and brackets that match the solar power system. lf the PV system is equipped with a battery,the advice of the battery manufacturer should be followed.
Artificially concentrated sunlight shall not be directed onto the PV module.
3.4 Electrical safety
Please strictly follow the electrical safety precautions below to avoid any form of electrical safety accident.
PV modules can generate DC voltage>30V under standard temperature condition (STC), take care to avoid direct contact. When installing POV modules, wear protective helmets, insulating gloves, and rubber shoes. Do not install PV modules without security precautions.
Do not drill holes in the frame, this action may cause PV module insulation failure
Do not make electrical connection by means other than connectors.
Broken PV modules have the risk of electric shock and fire that must be replaced immediately.
PV Module must be installed when it is electrically safe.
Avoid unnecessary touching PV modules as the surface and frame of the PV modules may be hot and there is a risk of burns or electric shock. The voltage connected in series of the PV modules must not exceed the maximum withstand voltage value.
Do not connect or disconnect the PV module when there is a current leakage of module or when there is an external current present. Please disconnect the faulty PV modules with safety protection.

General information 05/06
3.5 Handling safety
Select appropriate, suitable, and smooth transportation methods to avoid damage to component packaging. Standing, stepping, sitting, walking or jumping directly on the PV module package or PV module is prohibited.
Do not place heavy objects on the PV module; Do not place the module on a sharp surface.Do not collide or distort the edges of the components.
Do not connect the positive and negative anode cables of the same PV module together. Do not open the carton box before the PV modules arrive at the location, keep the packing box in a ventilated, dry environment. During the transportation, please refers to Chapter 4 – Storage and Transportation instructions. Any inappropriate handling and storage can result in breakage of glass or loss of electrical property, and consequently loss the use value of PV modules. Take carefully by installing PV modules. In any case, it is forbidden to lift the PV module by lifting the junction box or cable. At least two or more than two operators must hold the edges of the PV module with both hands. Do not try to dismantle the PV module or remove any nameplates or components of PV modules. Do not apply paint or other adhesives to PV module top surface. Do not damage or scratch the glass on front side and back side of PV module. Do not drill holes on the frame of PV module, which may reduce frame loading capacity and lead to frame corrosion and invalidation of the limited warranty provided for customers. Do not scratch anodized coating of aluminum alloy frame except for grounding connection. Scratch may lead to frame corrosion and reduce frame loading capacity and long-term reliability. Do not repair or modify the PV module on your own.

3.6 Fire safety
Please refer to local laws and regulations before installing any PV modules and observe their building fire safety requirements. Rooftop installations shall be placed over fire resistant roof coverings appropriate for this rating, and adequate ventilation shall be provided between the back glass and the mounting surface. The roof structure and PV module mounting method will affect the fire safety performance of the building. Inappropriate installation can lead to fire risks. To guarantee roof fire rating, the distance between PV module frame and roof surface must be greater than 10 cm. Please use the appropriate PV module accessories, e.g., fuses, circuit breakers and ground connectors, according to local laws and regulations. Please do not apply PV modules in where exposed inflammable gases are nearby.
04 Storage and Transportation Instructions
4.1 Considerations for PV Module Turnover and Handling
Upon arrival of the PV modules, please check whether the carton box is in good condition, and check whether the PV module type and quantity on the outer packaging are consistent with the delivery order. If anything ,wrong is observed, please contact AIKO logistics and sales staff immediately.
1. Crane unloading:
Crane operations require dedicated personnel to command and certified personnel to work; Before lifting the goods, conduct a visual inspection of the box and pallet, and check whether the lifting straps are firm and secure. When unloading PV modules by crane, please choose and use specialized tooling according to the weight and size of the pallet.The center of gravity of the module should be at the top of the box.Please adjust the position of the sling to keep the modules steady.
To ensure the safety of the PV module, wooden sticks, boards or other fixtures of the same width as the outer packing cases should be used on the upper part of the box to prevent the sling from squeezing the pallet and damaging the PV modules.
Please operate the spreader at a constant speed, when the lifting is close to the ground, place the box gently in a relatively flat ground.
Do not unload PV modules under the weather conditions of wind more than 6 class (in Beaufort scale).

General information / Storage and transportation instructions 07/08
2. Forklift unloading:
The loading dock should be as the same height as the underside of the carrier. Driving speed control 3km/h, forklift speed control 1km/h, to avoid emergency stop, rapid start, bumpy vibration, and sharp object collision with components. The height of the forklift shelf baffle should be 1200mm, and a buffer pad should be installed on the front arm of the forklift to avoid direct contact with the components; The maximum number of forks per shipment is 1 stack.
Forklift operators must hold professional operating certificates. If the packaging box obstructs the forklift driver’s line of sight it is recommended to reverse the forklift during transportation and arrange for a dedicated person to supervise and command to ensure that the forks do not exceed the components, preventing accidents that may cause personal injury or damage to components due to the dropping of packaging boxes. After transportation to the installation site, please choose a hard ground for placement as much as possible.
4.2 Considerations for PV Module Turnover and Transportation
When using a forklift to transport components, please ensure that the fork length of the forklift meets the requirements. It is recommended that the thickness of the forklift teeth be less than 80mm, and the length of the 3/4 pallet be less than the fork length and the pallet length. When forking, the fork should be tightly attached to the ground, and the distance between the forks should be adjusted to a suitable distance to avoid uneven force that may cause the components to tilt. During the transportation of components, the component pallets shall be placed closely, and the gap between the component packaging box and the front and rear of the vehicle and container shall be filled with foam to avoid collision and damage to the components. If using box trucks or other types of vehicles for transportation, please pay attention to using carriages with guardrails. The height of the guardrails should not be less than 2/3 of the height of the components, and fastening straps should be used to fix the components to the carriages. When the components are to be transported at the project site, the transportation route should be chosen on a smooth road surface to avoid damage or hidden cracks caused by bumps, collisions, squeezing, tilting, etc.
Before unpacking, conduct an external packaging inspection, use a utility knife to remove the packing tape, prohibit violent disassembly, and prohibit sharp objects from contacting the components. When opening the carton box, please place the PV modules to be unpacked at a distance of 20-30cm from the wall or another torr of PV modules, and then remove the torr. After removing the cable tie of the fixed PV modules, slowly lean the PV modules against the wall or another torr of PV modules to prevent them from falling.
Please handle the installation PV modules gently during transportation. Do not lift the PV modules by pulling the junction box or cables under any circumstances. Two or more people must hold the edges of the PV modules with both hands.

4.3 Considerations for PV Module Storage and Placement

Please store the packing box of PV

When storing PV

V modules on fe distance, and the

In any circumstances, keep the junction box and cables of the PV Store PV

V modules and pallets

For the storage of scattered PV modules, please stack the ertical PV module

on the empty to

22

66-cell/

V module maximum of

For long condition It’ s recommended to place PV modules in a standard

n a good ehouse for long-term storage and conduct regular

05 Installation Conditions
5.1 Location and working environment
The component is not suitable for the space environment. The component must be installed on a suitable ground or building and cannot be installed on any type of movable vehicle. PV modules are recommended to be installed in a -20 to 50 environments, with an extreme working ambient temperature of -40 to 85 and a humidity less than 85%RH. Do not install PV modules in locations or areas where there is a risk of flooding, and do not install or place PV modules near open flame or flammable materials. When installed at a distance of 50m to 500m away from the seashorewe recommended to use the Sirius module. Other modules are not supported for application in such scenarios. For rooftop installations, leave a safe working area between the edge of the roof and the external edge of the PV module array. For rooftop installations, check the roof loads and make a construction organization plan to meet the applicable standards. Ensure PV module is positioned to receive adequate sunlight and it is advised to avoid shading the PV module surfaces in part or in whole (by trees, buildings etc.).

Storage and transportation instructions / Installation Conditions 09/10

PV modules shall be installed in a

ell- ntilated position to ensure

te air

circulation on the back and sides of the PV

module and al mmediate dissipation of heat

produced during PV module operation, poor

heat dissipation of the PV

the outpu

d affect the o erall

output of PV

When PV modules suffer high ind or sno

pressure, supports and ings shall be designed

according to local design standards to keep

external l

ithin the maximum mechanical

strength that PV

In are oastal areas, factories,

protected agai

r alumin

canic areas, farmland exposed to salt fog, sul de or ammonia gas, corrosion can

V

u

V modules and the mounting position must be

ucts that can be used in offshore or salt-affected are

med and

ter installing PV modules, measures such as grounding must be taken to ensure that the PV modules are protected

Sunlight

5.2 Tilt angle selection
Tilt angle of PV module is the angle between the PV module and the horizontal ground. Different projects should choose different installation inclination angles according to local conditions.
All PV modules in the same array should be same orientation and angle. Different orientations and angles will result in different total solar irradiation absorbed by PV modules, leading to output mismatch that degrades system operating efficiency. In order to achieve the maximum annual generating capacity, the optimal orientation and inclination of PV modules in the installed area should be selected. When the surface of the PV module is perpendicular to sunlight, the output power reaches the maximum output value. AIKO recommend the installation angle should not less than 10°. The optimal tilt angle of PV arrays should be designed by taking into account the multi-year average monthly irradiance, direct irradiance, scattering irradiance, wind speed and other climate conditions at the location. PV modules should be tilted at an angle to receive the maximal annual irradiance. Angles shall be selected by considering natural conditions such as local wind load, snow load and avoidance of water and dust collection on module surfaces.
For details on the optimal tilt angle for installation, refer to consult a reliable local solar system installation company.
06 Mechanical Installation
6.1 General Requirements
Make sure that the PV modules are properly installed and the mounting structure are adequately fastened. PV module mounting system shall be constructed of anticorrosive, ultraviolet resistant materials. Installation bracket system shall be tested and inspected by the third-party testing institution with static mechanical analysis capacity in accordance with local national standards or international standards. In regions with heavy snowfall in winter, adjust the height of the mounting system so that the lower edge of the PV module is not covered by snow. In addition, ensure the lower part of PV module is not in the shadow of plants, trees. For rooftop installations, the minimum gap between the PV module frame and the roof shall be 10cm which is good for air circulation to achieve better performance of PV module. The module frames can encounter thermal expansion and cold contraction. There will be a certain amount of bending deformation at different temperatures, which will not affect the performance and reliability of the module. The minimum mounting distance between adjacent PV modules is 10mm. If there are special requirements, please contact AIKO for more details on installation methods. The minimum mounting distance between adjacent PV modules is 10 mm. Make sure that backside of PV modules will not be in contact with bracket or building structures that can pierce into the inside of the PV modules, especially when the PV module surface is imposed by pressure.

Installation conditions / Mechanical Installation 11/12
Maximum static load of the PV module is downforce 5400 Pa and uplift force 2400 Pa, which can vary from different mounting methods of the modules (please refer to the following installation guidance), the described load in this manual is for the test load. The PV module loads described herein are test values. According to IEC 61215-2021 installation requirements, when computing the corresponding maximum design load, it is necessary to divide by at least 1.5 times the safely factor in conmpliance with the local laws or regulations. In additions, project design loads must be based on project location, climate, mounting structure and applicable standards. Design loads are determined by bracket suppliers and professional engineering and technical personnel. please observe both the local laws and regulations and the instructions of structural engineers.
6.2 Mechanical Installation of PV Modules
PV modules can be connected to the racking system using pressure clamps and bolts. PV Modules must be mounted as recommended and illustrated below. Other mounting configurations may be used provided that consultation is made with, and prior written consent is received from AIKO. Failure to do so will invalidate our warranty.
6.2.1 PV Module Installation Method: Mounting pressure Clamps
Specialized pressure clamps are used to mount modules as shown below.

Side clamp Bolt
Gasket Gasket
Nut

Module Frame Racking

Middle clamp
Module
Gasket Frame Gasket
Nut

Bolt Module Frame
Racking

Under no circumstances should the clamp touch the glass or deform the frame.
Be sure to avoid shadowing effect from the pressure clamp.
When installing the modules, be cautious not to block the drain hole of the frame.
Pay attention to the matching of the height of the frame with the pressure clamp.
Be sure that pressure clamps will not fail due to deformation or corrosion while the entire PV module is under load. Pressure clamps of material 6005-T6 are recommended. The length should be 50mm and the thickness should be 4mm. The overlapped distance between the pressure clamps and the module frame should be at least 10mm, but no more than 12mm.
Clamp positions are of crucial importance for the reliability of the installation. The clamp centerlines must only be positioned within the ranges indicated in table below, depending on the configuration and load.

When choosing clamp-mounting, please be sure to use at least four clamps on each PV module. Depending on the local wind and snow loads, if excessive pressure load is expected, at least six clamps should be required to ensure the PV module can bear the load (more details, please contact AIKO technical personnel).
Do not drill additional holes or modify the PV module frame. Doing so will void the PV module’ s warranty.
Use appropriate corrosion-proof fastening materials. All mounting hardware (bolts, spring washers, flat washers, nuts) should be hot dip galvanized or stainless steel. Install and tighten the PV module clamps to the mounting rails using the torque stated by the mounting hardware manufacturer.
M8 bolt tightening torques must be within 16~20Nm and M6 bolt tightening torques must be within 8~12Nm, respectively depending on bolt classes. For the bolt grade, the technical guidelines from the fastener suppliers should be followed. Different recommendations from specific clamping hardware suppliers should prevail.
6.2.2 PV Module Installation Method: Bolts Mounting
Using bolts to secure the PV module on the bracket through the mounting holes at the back of PV module’ s frame. PV modules come standard with 4 or 8 mounting holes, matching M8 or M6 bolts, as figure below:

Accessories
Bolt Spring washer
Washer
Nuts

Module Mounting Holes

Model
M8

Accessories
Bolt

8

Spring washer

2 pcs, thickness 1.7mm and outside diameters = 16mm
M8

Washer Nuts

Bolt Washer frame bracket Washer Spring washer Nuts
Model
M6
6
2 pcs, thickness 1.7mm and outside diameters = 12-16mm
M6

It is important to ensure the bolts do not fail due to deformation or corrosion during the overall load of the PV module.
AIKO recommend the thickness of washer should 1.7mm and use M8 and M6 bolt tightening torques must be within 16~20Nm and 8~12Nm, respectively, depending on bolt classes.
For the bolt grade, the technical guidelines from the fastener suppliers should be followed. Different recommendations from specific clamping hardware suppliers should prevail.

PV Model 54/60

mounting holes diagram

Mechanical installation 13/14

78

1100(Inner four-hole bolts mounting) 1400(Outer four-hole bolts mounting)

72

1200(Inner four-hole bolts mounting) 1600(Outer four-hole bolts mounting)
790(Inner four-hole bolts mounting) 1400(Outer four-hole bolts mounting)

6.2.3 Installation and Mechanical Load of Mono Glass Module
Mono glass modules can be mounted by bolts or clamps. The mounting method and maximum test load are shown as follow (The unit of distance and length in the table below is millimeter (mm), and the unit of pressure is Pascal (Pa)).

Outer four-hole bolts mounting Mounting rails cross the long frame. (Method 1)

Inner four-hole bolts mounting Mounting rails cross the long frame. Method 2

Outer four-hole bolts mounting

Inner four-hole bolts mounting

Mounting rails run parallel to the long side. (Method 3) Mounting rails run parallel to the long side. Method 4

Clamps mounting on the long side Mounting rails run parallel to the long side frame. (Method 5

Clamps mounting on the long side Mounting rails cross the long frame. (Method 6

Clamps mounting on the short side Mountingrails run parallel to the short frame. (Method 7

Clamps mounting on the short side Mounting rails cross the short frame. (Method 8

Clamps are mounted at the corners of short frame. (Method 9)

Mechanical installation 15/16

Mechanical loads information of 54-cells and 60-cells with framed mono glass modules

Module Type

Module Size L*W*H(mm)

Bolts Mounting Method 1 Method 2

Method 5

Clamps Mounting Method 6 Method 7 Method 8

+5400/-2400 +1600/-1600

AIKO-Axxx-MAH54Mw 1722*1134*30
AIKO-Axxx-MAH54Mb

+2400/-2400 +5400/-2400

Pa

Pa

/

PaClamps PaClamps

Mounting Mounting

range :

range :

/

295-395mm 100-240mm

Method 9 /

+2400/-2400 +5400/-2400 +1600/-1600 +2400/-1600 +1600/-1600

AIKO-Axxx-MAH54Mw AIKO-Axxx-MAH54Mb 1757*1134*30

PaClamps PaClamps

+2400/-2400 +5400/-2400

Pa

Pa

Mounting range :

Mounting range :

PaClamps Mounting range :

PaClamps PaClamps Mounting Mounting range : range :s=0

350-450mm 310-410mm 100-240mm 100-240mm

+5400/-2400

AIKO-Axxx-MCE54Mw AIKO-Axxx-MCE54Mb

1762*1134*30

+2400/-2400 +5400/-2400

Pa

Pa

/

PaClamps Mounting range :

/

/

/

310-410mm

AIKO-Axxx-MAH54Tm 1762*1134*30

/

+3600/-2400

PaClamps

/

/

Mounting

/

/

/

range :

400-500mm

+5400/-2400

AIKO-Axxx-MAH60Mw 1954*1134*30
AIKO-Axxx-MAH60Mb

+3600/-2400 +5400/-2400

Pa

Pa

/

PaClamps Mounting range :

/

/

/

345-415mm

Mechanical loads information of 72-cells with framed mono glass modules

Module Type
AIKO-Axxx-MAH72Mw

Module Size L*W*H(mm)
2278*1134*30

Bolts Mounting
Method 1 +5400/-2400Pa

AIKO-Axxx-MAH72Mw

2323*1134*30/33

+5400/-2400Pa

AIKO-Gxxx-MCH72Mw

2382*1134*33

+5400/-2400Pa

AIKO-Gxxx-MCH72Mw

2382*1134*30

+5400/-2400Pa

Clamps Mounting
Method 6
+5400/-2400PaClamps Mounting range :450-500mm
+5400/-2400PaClamps Mounting range :470-520mm
+5400/-2400PaClamps Mounting range :420-470mm
+5400/-2400PaClamps Mounting range :500-550mm

Note: 1. The above data is based on the static load requirements of lEC61215 standard (Tested by AlkO or thirdparty certification institution), please contact AlkO for more details on other installation methods and load capacity not listed.. 2. ”/ ” identifies that there is no such installation.

6.2.4 Installation and Mechanical Load of Dual Glass Module
Dual glass modules can be mounted by bolts or clamps. The mounting method and maximum test load are shown as follow (The unit of distance and length in the table below is millimeter (mm), and the unit of pressure is Pascal (Pa)).

Outer four-hole bolts mounting Mounting rails cross the long frame. (Method 1)

Inner four-hole bolts mounting Mounting rails cross the long frame. Method 2

Outer four-hole bolts mounting

Inner four-hole bolts mounting

Mounting rails run parallel to the long side. (Method 3) Mounting rails run parallel to the long side. Method 4

Clamps mounting on the long side Mounting rails run parallel to the long side frame. (Method 5

Clamps mounting on the long side Mounting rails cross the long frame. (Method 6

Clamps mounting on the short side Mountingrails run parallel to the short frame. (Method 7

Clamps mounting on the short side Mounting rails cross the short frame. (Method 8

Clamps are mounted at the corners of short frame. (Method 9)

Mechanical installation 17/18

Mechanical loads information of 54-cells and 60-cells with framed dual glass modules

Module Type AIKO-Axxx-MAH54Db

Module Size L*W*H(mm)

Bolts Mounting Method 1 Method 2

1722*1134*30

+2400/-2400 +5400/-2400

Pa

Pa

Clamps Mounting

Method 5 Method 6 Method 7

+5400/-2400 +1600/-1600

PaClamps PaClamps

/

Mounting

Mounting

range :

range :

295-395mm 100-240mm

Method 8 /

Method 9 /

AIKO-Axxx-MAH54Db AIKO-Axxx-MAH54Dw AIKO-Axxx-MCE54Db AIKO-Axxx-MCE54Dw
AIKO-Axxx-MAH60Db

1757*1134*30

+2400/-2400 Pa

+5400/-2400 Pa

+1600/-1600

+5400/-2400Pa Clamps Mounting

+1600/-1600

Pa Clamps

range :

PaClamps

Mounting

295-395mm

Mounting

range :

+2400/-2400 Pa range :

Clamps Mounting

150-600mm

range:

100-240mm

150-600mm

+2400/-1600 PaClamps
Mounting range :
100-240mm

+1600/-1600 PaClamps
Mounting range :s=0

+5400/-2400Pa

1762*1134*30 +2400/-2400 +5400/-2400

/

Clamps Mounting

/

/

/

Pa

Pa

range :

295-395mm

1954*1134*30

/

+3600/-2400 +5400/-2400

Pa, Clamps Pa, Clamps

Mounting

Mounting

range

range

320-440mm; 320-440mm;

+2400/-2400 +2400/-2400

/

Pa, Clamps Pa, Clamps

/

/

/

Mounting

Mounting

range

range

100-320mm 200-320mm

+1600/-1600- +1600/-1600-

Pa, Clamps Pa, Clamps

Mounting

Mounting

range 0mm

range

100-200mm

Mechanical loads information of 66-cells72-cells and 78-cells with framed dual glass modules

Module Type
AIKO-Axxx-MAH72Dw
AIKO-Axxx-MAH72Dw AIKO-Axxx-MAH78Dw AIKO-Gxxx-MCH72Dw AIKO-Axxx-GRH66Dw

Module Size L*W*H(mm)

Method 1

Bolts Mounting Method 2

Method 4

2278*1134*30 +5400/-2400Pa

/

/

2323*1134*30 +5400/-2400Pa

/

/

2465*1134*30

/

+5400/-2400Pa

/

2382*1134*30 +5400/-2400Pa

/

+2400/-2400Pa

Clamps Mounting

Method 5

Method 6

/
/
/ +2400/-2400Pa Clamps Mounting range :500-600mm

+5400/-2400Pa Clamps Mounting range :380-480mm
+5400/-2400Pa Clamps Mounting range :500-550mm +5400/-2400Pa Clamps Mounting range :550-650mm +5400/-2400Pa Clamps Mounting range :500-600mm

Note: 1. The above data is based on the static load requirements of lEC61215 standard (Tested by AlkO or thirdparty certification institution), please contact AlkO for more details on other installation methods and load capacity not listed.. 2. ”/ ” identifies that there is no such installation.

6.2.5 PV Module Installation Method: Single-axis Tracking System Installation
AIKO 72 type modules come with standard four mounting holes matching M8 bolts (790mm and 1400mm mounting holes); 72 type modules have an additional four mounting holes matching M6 bolts (400mm mounting holes), used for matching Tracking system product such as NEXTracker. Using bolt to install the PV module on the bracket through the mounting hole at the back of the PV module’s frame. Installation details as below:

400mm 790mm 1400mm

Note that:M8 bolt tightening torques must be within 16~20Nm and M6 bolt tightening torques must be within 8~12Nm, respectively, depending on bolt classes. For the bolt grade, the technical guidelines from the fastener suppliers should be followed. Different recommendations from specific clamping hardware suppliers should prevail.

Module Type
AIKO-Axxx-MAH72Dw
AIKO-Gxxx-MCH72Dw AIKO-Axxx-GRH66Dw

Module Size L*W*H(mm)
2278*1134*30
2382*1134*30

Mounting Hardware
400mm mounting holes 790mm mounting holes 400mm+1400mm mounting holes 790mm+1400mm mounting holes 400mm mounting holes 790mm mounting holes 400mm+1400mm mounting holes 790mm+1400mm mounting holes

Test LoadPa
+2100/-2100 +2600/-2400 +2600/-2400 +3000/-2600 +1800/-1800 +2500/-2400
/ /

Note: 1. The above data is based on the static load requirements of lEC61215 standard (Tested by AlkO or thirdparty certification institution), please contact AlkO for more details on other installation methods and load capacity not listed.. 2. ”/ ” identifies that there is no such installation.

Mechanical installation 19/20
07 Electrical Installation
7.1 Electrical performance
There are tolerances (±3 between the rated values of the electrical performance under STC and measured values. Including Isc, Voc and Pmax under STC (1000 W/m2 Irradiance, a cell temperature of 25 and an AM1.5). When PV modules are in series connection, the string voltage is sum of every individual PV module in one string. When PV modules are in parallel connection, the current is sum of the individual PV modules as shown in below. PV modules with different electric performance models cannot be connected in the same string.

Series connection
Overcurrent protective device Diode Connector

Parallel after series connection

If the PV module is passed through by a reverse current greater than the maximum fuse current of the PV module, the PV module shall be protected with an over current protector of the same specification. If more than two strings are connected in parallel, each PV module string shall be protected with an over current protector as shown above.
The string voltage must not exceed the maximum voltage that the system can withstand or the maximum input power of the inverter or other electrical devices installed in the system. To ensure this, the open circuit voltage of the array shall be calculated at the minimum expected ambient temperature at that location. The following formula may be used:

Where: N Voc Tmin

Maximum system voltage N×Voc×[1+*(Tmin-25)] number of modules connected in series open circuit voltage of each module (refer to product nameplate or specification) [V] temperature coefficient of open circuit voltage for the PV module (refer to the specification) [°C-1] lowest ambient temperature [°C]

7.2 Cables and Connections
PV module’s junction boxes with the lP68 protective level and composed of connected cables and IP68 connectors. The PV module has a positive and a negative PV connector connected into the junction box and a plug-and-play connector connected at the other end, Using the positive connector of the module to connect the negative connector of the adiacent module connects the two modules in series. Use specialized solar cables and appropriate connectors according to local electrical and installation standards, codes and regulations at the location, and ensure that the electrical and mechanical properties of the cables are good. Electrical connections shall comply with local electrical requlations AlKO PV modules use specialized PV cables which have a cross sectional area of 4 mm2 and are ultraviolet resistant. AlKO recommends that all cables are run in appropriate conduits and sited away from areas prone to water collection, AlKO recommend use copper cables with a minimum cross sectional area of 4mm2 which are rated for 90 and are UV resistant shall be used as PV connecting lines. The minimum bending radius of the cable is 43mm.
7.3 Connector
Take care to keep the connectors dry and clean. Make sure that the connector nuts are tightened before making any connection. Do not connect while the connectors are wet or otherwise abnormal. As connectors provide IP68 protection only when the positive and negative poles are fully mated, please connect PV modules as soon as possible after installation or take proper steps to prevent water vapor and dust from coming into the connector. Avoid exposing the connector to direct sunlight and water. Avoid exposing the connector directly to ground surface or roof. Make sure that all electrical connections are secure. Incorrect connection can result in electrical arcing and shocks. If you need to use the connection of different types of connectors,please contact AIKO customer service(cs@aikosolar.com)

Electrical installation 21/22
08 Grounding
PV modules are designed with an anodized anticorrosive aluminum alloy frame as a rigid support. PV module frames must be grounded to ensure safe use and protect the PV module against lightning and electrostatic damage. Grounding must be made with the grounding device in full contact with the interior of the aluminum alloy and penetrating the oxide film on the frame surface.
Grounding devices include grounding screws, flat washers, puncture gaskets and grounding wires. All these items shall be constructed of stainless steel except grounding wires. Grounding conductors or wires shall be copper wires. Grounding conductors shall be connected to the ground through an appropriate grounding electrode. Third-party grounding devices meeting local electrical installation standards at the location may be used for grounding AIKO PV modules. Grounding device shall be installed according to the operation manual provided by the manufacturer.

Following is the recommended grounding method:
There are 4.2 mm grounding holes on surface C of the PV module frame. Use a separate grounding wire and accessories to connect the aluminum alloy frame of PV modules and connect the grounding wire to the ground. We recommend using M4×12 mm grounding bolts accompanied by M4 nuts, star washers and flat washers.

We recommend torquing grounding bolts to 3~7 Nm and using 4 mm2 copper wires as grounding wires.

Unused PV module mounting holes on the frame may also be used for grounding purposes.

Connection mode: The star washer, flat washer, and ground wire are placed in sequence, threaded through the ground hole using screws, and tightened to secure the adjacent PV modules.

Components

Sketch map

We recommend using the following method to ground correctly, as shown in the figure.

Connection bolt and notch Washer faced hex nut
Aluminum frame Cable hole
Hex nut

Sliding Trunking block Bolt

Base Nut

Grounding/Maintenance of PV modules 23/24

09 Maintenance of PV modules
PV modules shall be inspected and maintained on a regular basis, especially within the warranty period, which is an obligatory responsibility of the user. Any damage or other visible abnormalities of the PV module shall be reported to AIKO customer service(cs@aikosolar.com) upon discovery.
9.1 Cleaning
The power output of PV modules is related to incident light intensity and can be reduced by dust collection or other shadings. Dirt on PV modules must be cleaned up immediately. The cleaning frequency depends on the degree of dirt collection. PV modules installed at an adequate tilt angle will allow rainwater to clean the PV module surfaces, thereby reducing the cleaning frequency. We recommend cleaning the glass surface of the PV module with a clear water-netted sponge. Do not clean PV modules with a detergent containing acid or alkali. Do not clean PV modules with a hair brush or other rough surface tools. We recommend cleaning PV modules in the early morning or late afternoon or other periods of time when the light is weak and the PV module temperature is comparatively lower.

Method A: High Pressure Water Cleaning
Water quality requirement
PH:6-8 Water hardness – calcium carbonate concentration: <600mg/L; Recommended use of soft water cleaning; Recommended maximum water pressure is 4MPa(40bar)

Water

Absolute ethtl alcohol

Method B: Wet Test Cleaning

If there is too much stain on the surface of the PV module, it’ s recommended to carefully use an insulating brush, sponge or other soft cleaning tool.

Dust-free gloves

Dust-free paper

Ensure that any brushes or agitating tools are made of insulating material to minimize the risk of electric shock and that they do not scratch the glass or aluminum frame.

For oil stains, it’ s recommended to use an environmentally friendly,non-corrosive cleaning cleaner.

Method C: Robot Cleaning
If the cleaning robot is used for dry cleaning, the brush material is required to be soft plastic, so that the glass surface and aluminum alloy frame of the PV module will not be scratched during and after cleaning. The weight of the cleaning robot should not be more than 40kg, the PV module damage and power degradation caused by improper cleaning with the cleaning robot are not covered by the warranty of AIKO.
9.2 Visual Checks of the PV Modules
Visually checks for visual defects on modules, such as: Whether the PV module glass is broken Whether the junction box is damaged or the cable is broken Whether the PV module is shaded by foreign matter or shadows Check whether the bolts fixing the PV module to the racking are loose or corroded and adjust or replace them if necessary Check whether the PV modules are well-grounded

Maintenance of PV modules 25/26
9.3 Checks of Connectors and Cables
It is recommended to perform preventive examinations every six months, such as: Whether the connectors are properly sealed and the cables are properly fastened Whether the sealant of the junction box is cracked
9.4 AIKO Technical Support
In order to request Technical Support: Collect evidences of the issue as (a) photos and (b) measurements. Be prepared to show the purchase invoice and module serial number. Contact your Installer.