Specifications

  • Product: TM5 Transformer Module
  • Manufacturer: Aerotech, Inc.
  • Model/Types: TM5 All
  • Electrical Specifications: Refer to Table 1-2
  • Mechanical Specifications: Refer to Section 1.2.2
  • Environmental Specifications: Refer to Table 1-4
  • AC Power Input: Refer to Section 1.2.5
  • +24 VDC Output: Refer to Section 1.2.7

GLOBAL TECHNICAL SUPPORT

  • Go to the Global Technical Support Portal for information and support about your Aerotech, Inc. products. The website supplies software, product manuals, Help files, training schedules, and PC-to-PC remote technical support.
  • If necessary, you can complete Product Return (RMA) forms and get information about repairs and spare or replacement parts. To get help immediately, contact a service office or your sales representative. Include your customer order number in your email or have it available before you call.
  • This manual contains proprietary information and may not be reproduced, disclosed, or used in whole or in part without the express written permission of Aerotech, Inc. Product names mentioned herein are used for identification purposes only and may be trademarks of their respective companies.
  • Copyright © 2005-2025, Aerotech, Inc. | All rights reserved.
  • See the latest version of Aerotech’s Terms of Use, Privacy Policy, and Cookie Policy online at aerotech.com.

EU Declaration of Conformity

  • Manufacturer Aerotech, Inc.
  • Address 101 Zeta Drive
  • Pittsburgh, PA 15238-2811
    USA
  • Product TM5
  • Model/Types All

This is to certify that the aforementioned product is in accordance with the applicable requirements of the following directive(s):

  • 2014/35/EU Low Voltage Directive
  • EU 2015/863 Directive, Restricted Substances (RoHS 3)

and has been designed to be in conformity with the applicable requirements of the following standard(s) when installed and used in accordance with the manufacturer’s supplied installation instructions.

EN 61010-1:2010 Safety Requirements for Electrical Equipment

  • AuthorizedAEROTECH-TM5-Transformer-Module-image (1)
  • Representative: / Jochen Jäger
  • Operations Manager
  • Aerotech GmbH
  • Gustav-Weißkopf-Str. 18
  • 90768 Fürth
  • Germany
  • Engineer VerifyingAEROTECH-TM5-Transformer-Module-image (2)
  • Compliance: / AlexWeibel
  • Aerotech, Inc.
  • 101 Zeta Drive
  • Pittsburgh, PA 15238-2811
  • USA
  • Date: 11/26/2024

UKCA Declaration of Conformity

  • Manufacturer Aerotech, Inc.
  • Address 101 Zeta Drive
  • Pittsburgh, PA 15238-2811
  • USA
  • Product TM5
  • Model/Types All

To which this declaration relates, meets the essential health and safety requirements and is in conformity with the relevant UK Legislation listed below:

  • Electrical Equipment (Safety) Regulations 2016
  • Hazardous Substances in Electrical and Electronic Equipment Regulations 2012

Using the relevant section of the following UK Designated Standards and other normative documents when installed in accordance with the installation instructions supplied by the manufacturer.

EN 61010-1:2010 Safety Requirements for Electrical Equipment

  • AuthorizedAEROTECH-TM5-Transformer-Module-image (3)
  • Representative: / Simon Smith
  • Managing Director
  • Aerotech Ltd
  • The Old Brick Kiln
  • Ramsdell, Tadley
  • Hampshire RG26 5PR
  • UK
  • Engineer Verifying Compliance:AEROTECH-TM5-Transformer-Module-image (4) / AlexWeibel
  • Aerotech, Inc.
  • 101 Zeta Drive
  • Pittsburgh, PA 15238-2811
  • USA
  • Date: 11/26/2024

Agency Approvals
The TM5 transformers have been tested by the following NRTL(s) and have been certified to the standards that follow:

  • Approval: CUS NRTL
  • Approving Agency: TÜV SÜD America Inc.
  • Certificate #: U8 068995 0026
  • Standards: CAN/CSA C22.2 No. 61010-1:2012 ,
  • UL 61010-1:2012

Visit https://www.tuev-sued.de/product-testing/certificates to view Aerotech’s TÜV SÜD certificates. Type the certificate number listed above in the search bar or type “Aerotech” for a list of all Aerotech certificates.AEROTECH-TM5-Transformer-Module-image (5)

Safety Procedures and Warnings
IMPORTANT: This manual tells you how to carefully and correctly use and operate the transformer module.

  • Read all parts of this manual before you install or operate the transformer module or before you do maintenance to your system.
  • To prevent injury to you and damage to the equipment, obey the precautions in this manual.
  • All specifications and illustrations are for reference only and were complete and accurate as of the release of this manual. To find the newest information about this product, refer to www.aerotech.com.

If you do not understand the information in this manual, contact Aerotech Global Technical Support.

IMPORTANT: This product has been designed for light industrial manufacturing or laboratory environments. If the product is used in a manner not specified by the manufacturer:

  • The protection provided by the equipment could be impaired.
  • The life expectancy of the product could be decreased.

Safety notes and symbols are placed throughout this manual to warn you of the potential risks at the moment of the safety note or if you fail to obey the safety note.

  • AEROTECH-TM5-Transformer-Module-image (6)The voltage can cause shock, burn, or death.
  • AEROTECH-TM5-Transformer-Module-image (7)You are at risk of physical injury.
  • AEROTECH-TM5-Transformer-Module-image (8)You could damage the transformer module.
  • AEROTECH-TM5-Transformer-Module-image (9)A surface can be hot enough to burn you.
  • AEROTECH-TM5-Transformer-Module-image (10)Your actions, the temperature of the system, or the condition of the atmosphere that surround the system could start a fire.
  • AEROTECH-TM5-Transformer-Module-image (11)Components are sensitive to electrostatic discharge.
  • Unsecured cables could cause you to:
    • trip and fall
    • drag the product off of its mounting location
    • damage the cable connections.
  • AEROTECH-TM5-Transformer-Module-image (12)A blue circle symbol is an action or tip that you should obey. Some examples include:
    • General tip
    • Read the manual/section
    • AEROTECH-TM5-Transformer-Module-image (13)Wear protective safety equipment (eye protection, ear protection, gloves)
    • If applicable, do not lift unassisted

DANGER: To decrease the risk of electrical shock, injury, death, and damage to the equipment, obey the precautions that follow.

  1. Restrict access to the transformer module when it is connected to a power source.
  2. Before you do maintenance to the equipment, disconnect the electrical power.
  3. Before you connect wires to this product, disconnect the electrical power.
  4. To decrease the risk of electrical shock and injury, you must supply operators with the necessary precautions and protection from live electrical circuits.
  5. Make sure that all components are grounded correctly and that they obey the local electrical safety requirements.
  6. Make sure that you install the necessary precautions to supply safety and protection to the operator.
  • DANGER: System travel can cause crush, shear, or pinch injuries. Restrict access to all motor and stage parts while your system is connected to a power source.
  • WARNING: To prevent damage to the equipment and decrease the risk of electrical shock and injury, obey the precautions that follow.
  1. Make sure that all system cables are correctly attached and positioned.
  2. Do not use the cables or the connectors to lift or move this product.
  3. Use this product only in environments and operating conditions that are approved in this manual.
  4. Only trained operators should operate this equipment.

Chapter 1: Transformer Module

  • The TM5 transformer module provides and distributes isolated AC bus supply voltages for up to four Aerotech controllers. It is configured at the factory to provide 28 VAC, 56 VAC, 115 VAC or a combination of these voltages with a maximum transformer output power capability of 500 watts.
  • The TM5 also provides Control Supply outputs to power the control power inputs of up to four Aerotech products and an optional 24 VDC power supply that provides the user with 24 VDC output with a current capacity of up to 4 A.

AEROTECH-TM5-Transformer-Module-image (14)

Table 1-1: TM5 Configuration Options

TM5 0.5 kVA Isolation Transformer
Line Voltage
-A 115 VAC Input Line Voltage
-B 230 VAC Input Line Voltage
-C 100 VAC Input Line Voltage
-D 200 VAC Input Line Voltage
Output Bus Voltage VBus1 VBus2
-28VAC-28VAC 28 VAC for 40 VDC Bus
-56VAC-56VAC 56 VAC for 80 VDC Bus
-28VAC-56VAC 28 VAC 56 VAC for 40/80 VDC Bus
-56VAC-28VAC 56 VAC 28 VAC for 80/40 VDC Bus
-56VACCT-28VAC 56 VAC Center Tap 28 VAC for 80/40 VDC Bus
-56VACCT-56VAC 56 VAC Center Tap 56 VAC for 80 VDC Bus
-28VAC-56VACCT 28 VAC 56 VAC center tap for

40/80 VDC Bus

-56VAC-56VACCT 56 VAC 56 VAC center tap

for 80 VDC Bus

-56VACCT-56VACCT 56 VAC center tap for 80 VDC Bus
-115VAC-115VAC 115 VAC, for 160 VDC Bus
Bus Split VBus1 VBus2
/1-3 Output 1 Output 2, 3, and 4
/2-2 Output 1 and 2 Output 3 and 4
/3-1 Output 1, 2, and 3 Output 4
/NOSPLIT VBus1 and VBus2 tied together and wired to all axes
Power Supply
PS24-1 24 VDC, 4 A Power Supply for Brake Control
Brake Cable
C24-xx Two conductor brake cable with flying leads. “-xx” = cable length
  • 06 = 0.6 m
  • 09 = 0.9 m
  • 12 = 1.2 m
  • 15 = 1.5 m
  • 18 = 1.8 m
(example: C24-15)
Output Cables
Control and bus cable for Aerotech HPe or CP drives
“C#” = output number                                         “-xx” = cable length
/C#AB-xx

(example: /C3AB-18)

  • 06 = 0.6 m
  • C1 is for output 1
  • 09 = 0.9 m
  • C2 is for output 2
  • 12 = 1.2 m
  • C3 is for output 3
  • 15 = 1.5 m
  • C4 is for output 4
  • 18 = 1.8 m
Line Cord Options
/US115VAC US 115 VAC compatible line cord
/US230VAC US 230 VAC compatible line cord
/ENGLAND U.K. compatible line cord
/GERMANY German compatible line cord
/ISRAEL Israel compatible line cord
/INDIA India compatible line cord
/AUSTRALIA Australia compatible line cord

Electrical Specifications

Table 1-2: Electrical Specifications

AC Input Configurations 100 VAC, 115 VAC, 200 VAC or 230 VAC
Peak AC Input Inrush Current 200 Apk (1/2 cycle)
Operating Frequency 50/60Hz
Maximum Continuous Transformer Output Power 500 Watts, Max. @ 20°C
Peak Transformer Output Power 800 Watts, Max. @ 20°C
Short Circuit /

Over Current Protection

AC input breaker/switch 100/115 VAC 10 A, 200/230 VAC 5 A (Supplementary protection only)
100 VAC / 115 VAC configurations contain 8 A Slow Blow fuse connected to transformer primary winding
200 VAC / 230 VAC configurations contain 4 A Slow Blow fuse connected to transformer primary winding
Thermal Production Integral transformer thermal switch is normally closed. Thermal switch opens when internal temperature of transformer reaches 110°C.
Secondary Winding Configuration 28 VAC (40 VDC Bus)
56 VAC (80 VDC Bus)
112 VAC (160 VDC Bus)
+24 VDC Output 4 A maximum user supply (1 A maximum for TM5 units purchased before April, 2016)

Installation and Mounting
WARNING: To prevent damage to the equipment and decrease the risk of electrical shock and injury, obey the precautions that follow.

  • Allow all system components to adjust to room temperature before they are installed.
  • Do not install or apply power to system components if there is condensed moisture on the components.
  • Securely mount all system components before you connect cables and apply power. Refer to Table 1-3 for more information.

Handling and Transportation

  • WARNING: Do not use the cables or the connectors to lift or move this product.
  • Pick up and hold the TM5 by the chassis. If you need to transport the transformer module to a different location, place it into a protective antistatic bag and then into a box with the appropriate packing material.

Mechanical Specifications

Mounting and Cooling
Table 1-3: Mounting Specifications

TM5
Customer-Supplied Enclosure IP54 Compliant
Weight 7.54 kg (16.6 lbs)
Mounting Hardware M5 [#10] screws (four locations, not included)
Mounting Orientation Vertical (typical)
Dimensions Refer to Section 1.2.2.2.
Minimum Clearance Airflow ~25 mm
Connectors ~100 mm
(Optional) Customer-Supplied Cooling Direct air into the bottom vents of a vertically or horizontally mounted TM5 enclosure to achieve the optimal cooling airflow.
Operating Temperature Refer to Section 1.2.3.

Dimensions

AEROTECH-TM5-Transformer-Module-image (15) Environmental Specifications
The environmental specifications are listed below.

Table 1-4: Environmental Specifications

Ambient Temperature Operating: 5 °C to 40 °C (41 °F to 104 °F)
Storage: -20 °C to 70 °C (-4 °F to 158 °F)
Humidity

Non-condensing

The maximum relative humidity is 80% for temperatures that are less than 31 °C and decreases linearly to 50% relative humidity at 40 °C.
Operating Altitude 0 m to 2,000 m (0 ft to 6,562 ft) above sea level.
Pollution Pollution Degree 2

Typically only nonconductive pollution occurs.

Operation Use only indoors
Environment Indoor, Light Industrial Manufacturing, Laboratory

System Interconnection
System interconnection examples are shown below. Cables can be purchased from Aerotech.

Figure 1-3: System Interconnect Example (iXC4/XC4 and iXC4e/XC4e)AEROTECH-TM5-Transformer-Module-image (16)

  • CONNECT ALL WIRING BEFORE A FOLLOW ALL APPLICABLE WIRING
  • HAZARDOUS VOLTAGES PRESENT.
  • FOLLOW AND SAFETY CODES. POWERING THE TM3.
  1. The TM5 depicted is for 115V line voltage (other line cord/voltage options are available).
  2. Recommended Wiring Wire Size 1.3 mm2 (16AWG), Conformity UL /
  3. ALIX SUPPLY (Control Supply) AC output voltage is always the same as the AC input Voltage.

AC Power Input
DANGER: The voltage from this product can kill you. To decrease the risk of electrical shock, injury, and death, you must obey the precautions that follow.

  1. The AC Power inlet power connection is the Mains disconnect.
  2. Make sure that the applied AC voltage matches the voltage listed on the rating tag.
  3. Before you connect wires to this product, disconnect the electrical power.
  4. Make sure that all components are grounded correctly and that they obey the local electrical safety requirements.

Supply AC power to the TM5 through the AC inlet located next to the power switch/circuit breaker. Use the standard line cord that is supplied with the transformer module. The AC power input ratings are listed on the power label on the TM5 transformer module.

Power Output Connections (TB1-TB4)

  • Each output connector provides two supply sources: a Main Supply output and an Aux Supply output.
  • The MAIN SUPPLY output is an application-dependent AC or DC voltage. The output is designed to be connected to the Motor Supply connection of an Aerotech controller. The MAIN SUPPLY is normally referenced to ground. A fuse in the TM5 primary circuit provides short circuit protection for the MAIN SUPPLY output.

The AUX SUPPLY output is an application-dependent AC or DC voltage. The output is designed to be connected to the Control Supply connection of an Aerotech controller. AUX SUPPLY outputs that are configured for off-line AC power are protected by a switch/circuit breaker. This is the green rocker-switch located on the front panel near the AC power inlet. For operation instructions, refer to Section 1.3. Operation.

  • For 100 & 115 V configurations, the switch/circuit breaker is a 10 A rated part.
  • For 200 & 230 V configurations, the switch/circuit breaker is a 5 A rated part.

AUX SUPPLY outputs that are configured for DC power are protected by fuses in the primary circuit of the TM5 transformer module.

Table 1-5: Power Output Connections (TB1-TB4)

Pin Description Connector
1 AC output  
2 AC output
3 Protective Ground (required for safety)
4 AC output
5 AC output
6 Protective Ground (required for safety)

AEROTECH-TM5-Transformer-Module-image (17)

Table 1-6: Motor Supply Mating Connector Ratings

Specification Description
Type 6-Pin Terminal Block
Part Numbers Aerotech: ECK02596
Phoenix: 1248128(1)
Conductor Cross Section One conductor, stranded with ferrule and plastic sleeve 10…24 AWG (0.2…4 mm2)
Two conductors (same cross-section), stranded, twin ferrule with plastic sleeve 12…20 AWG (0.5.. 2.5 mm2)
Tightening Torque 0.5   0.6 N·m
Conductor Insulation Strip Length 7 mm (0.25 in)
(1) Refer to the manufacturer website for additional information.

+24 VDC Output [PS24-1]
The optional +24 VDC output has a maximum current output of 4 amps @ 20º C. The 24 VDC output is accessible at the 2-pin terminal block connector. The negative side of the 24 V supply is connected to chassis (ground).

Table 1-7: +24 VDC Output Connections

Pin Label Description Connector
1 + +24 VDC Output AEROTECH-TM5-Transformer-Module-image (18)
2 – Side of supply (connected to chassis, ground)

Table 1-8: +24 VDC Output Connector Ratings

Specification Description
Type 2-Pin Terminal Block
Part Numbers Aerotech: ECK02389
Phoenix: 1756256(1)
Conductor Cross Section One conductor, stranded with ferrule and plastic sleeve 12…24 AWG (0.2.. 2.5 mm2)
Two conductors (same cross-section), stranded, twin ferrule with plastic sleeve 12…20 AWG (0.5.. 2.5 mm2)
Tightening Torque 0.5   0.6 N·m
Conductor Insulation Strip Length 7 mm (0.25 in)
(1) Refer to the manufacturer website for additional information.

IMPORTANT: For a TM5 purchased before April 2016:

The +24 VDC output has a maximum current output of 1 amps @ 20º C.

Operation
DANGER: The voltage from this product can kill you. To decrease the risk of electrical shock, injury, and death, you must obey the precautions that follow.

  1. The AC Power inlet power connection is the Mains disconnect.
  2. Make sure that the applied AC voltage matches the voltage listed on the rating tag.
  3. Before you connect wires to this product, disconnect the electrical power.
  4. Make sure that all components are grounded correctly and that they obey the local electrical safety requirements.

When power is applied to the transformer box and the power switch is in the ON position the Green power switch will be illuminated. The power switch can also be left in the ON position and the power to the transformer module can be turned ON and OFF remotely.

Chapter 2: Maintenance

IMPORTANT: For your own safety and for the safety of the equipment:

  • Do not remove the cover of the TM5
  • Do not attempt to access the internal components.

DANGER: If you must remove the covers and access any internal components be aware of the risk of electric shock.

  1. Disconnect the Mains power connection.
  2. Wait at least one (1) minute after removing the power supply before doing maintenance or an inspection. Otherwise, there is the danger of electric shock.
  3. All tests must be done by an approved service technician. Voltages inside the controller and at the input and output power connections can kill you.

Table 1-9: Troubleshooting

Symptom Possible Cause and Solution
No output power The TM5 might not be receiving input power.
  • Make sure that the Power Switch is ON and illuminated.
  • Make sure that AC Mains is connected to the TM5 inlet.
  • Make sure that there is AC power to the TM5.

If the power switch is illuminated, check the state of the F1 fuse.

Power switch will not stay on There could be an overload or short on output.
  • Remove all output cables.
  • Locate the short and correct the problem.
Output turns off after TM5 unexpectedly The transformer inside the chassis could be too hot. This could mean that the air flow to or through the chassis is inadequate or that the power rating of the transformer has been exceeded.

Make sure that:

  • the Main Supply outputs are not overloaded.
  • the TM5 is configured for the AC line voltage supplied to it. Fix or increase the air flow through the chassis.
F1 fuse opens
  • Make sure that the fuse is the correct value and type.
  • Check for a short or overload on the outputs.
There is no +24 Volt output Make sure that +24V supply is not overloaded or shorted (disconnect the +24V connector to check).

Fuse Replacement
The TM5 transformer Module contains one user replaceable fuse (F1) located on the primary circuit of the transformer module and functions to protect the transformer against shorts and severe overloads on the transformer output (Main Supply outputs). This fuse must be a Slow Blow fuse in order to handle the high inrush currents when the TM5 is turned on. The current rating of the fuse is determined by the TM5 configuration.

Table 1-10: TM5 Fuse Replacement Part Numbers

Fuse Configuration Third Party P/N Aerotech P/N Size
F1 100VAC (-C)

115 VAC (-A)

Bussmann PN: MDA8 EIF00122 8 A. S. B. (3AG)
200 VAC (-D)

230 VAC (-B)

Littelfuse PN: 313004 EIF00104 4 A. S. B. (3AG)

Preventative Maintenance
DANGER: The voltage from this product can kill you. To decrease the risk of electrical shock, injury, and death, you must obey the precautions that follow.

  1. Restrict access to the transformer module when it is connected to a power source.
  2. Before you do maintenance to the equipment, disconnect the electrical power.
  3. Before you connect wires to this product, disconnect the electrical power.

Do an inspection of the TM5 and the external wiring one time each month. It might be necessary to do more frequent inspections based on:

  • The operating conditions of the system.
  • How you use the system.

Table 1-11: Preventative Maintenance

Check Action to be Taken
  • Examine the chassis for hardware and parts that are damaged or loose.
  • It is not necessary to do an internal inspection.
 Repair all damaged parts.
Do an inspection of the cooling vents. Remove all material that collected in the vents.
Examine the work area to make sure there are no fluids and no electrically conductive materials. Do not let fluids and electrically conductive material go into the TM5.
 Examine all cables and connections to make sure they are correct.
  • Make sure that all connections are correctly attached and not loose.
  • Replace cables that are worn. Replace all broken connectors.

Cleaning
Use a clean, dry, soft cloth to clean the TM5. If necessary, use a cloth that is moist with water or isopropyl alcohol. If you use a moist cloth, make sure that moisture does not go into the transformer module. Also make sure that it does not go onto the outer connectors and components. Internal contamination from the cleaning solution can cause corrosion and electrical short circuits.
Do not clean the labels with a cleaning solution because it might remove the label information.

Warranty

Appendix A: Warranty and Field Service

  • Aerotech, Inc. warrants its products to be free from harmful defects caused by faulty materials or poor workmanship for a minimum period of one year from date of shipment from Aerotech. Aerotech’s liability is limited to replacing, repairing or issuing credit, at its option, for any products that are returned by the original purchaser during the warranty period. Aerotech makes no warranty that its products are fit for the use or purpose to which they may be put by the buyer, whether or not such use or purpose has been disclosed to Aerotech in specifications or drawings previously or subsequently provided, or whether or not Aerotech’s products are specifically designed and/or manufactured for buyer’s use or purpose. Aerotech’s liability on any claim for loss or damage arising out of the sale, resale, or use of any of its products shall in no event exceed the selling price of the unit.
  • THE EXPRESS WARRANTY SET FORTH HEREIN IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE. IN NO EVENT SHALL AEROTECH BE LIABLE FOR CONSEQUENTIAL OR SPECIAL DAMAGES.

Return Products Procedure

  • Claims for shipment damage (evident or concealed) must be filed with the carrier by the buyer. Aerotech must be notified within thirty (30) days of shipment of incorrect material. No product may be returned, whether in warranty or out of warranty, without first obtaining approval from Aerotech. No credit will be given nor repairs made for products returned without such approval. A “Return Materials Authorization (RMA)” number must accompany any returned product(s). The RMA number may be obtained by calling an Aerotech service center or by submitting the appropriate request available on our website (www.aerotech.com). Products must be returned, prepaid, to an Aerotech service center (no C.O.D. or Collect Freight accepted). The status of any product returned later than thirty (30) days after the issuance of a return authorization number will be subject to review.
  • Visit Global Technical Support Portal for the location of your nearest Aerotech Service center.

Returned Product Warranty Determination
After Aerotech’s examination, warranty or out-of-warranty status will be determined. If upon Aerotech’s examination a warranted defect exists, then the product(s) will be repaired at no charge and shipped, prepaid, back to the buyer. If the buyer desires an expedited method of return, the product(s) will be shipped collect. Warranty repairs do not extend the original warranty period.

  • Fixed Fee Repairs – Products having fixed-fee pricing will require a valid purchase order or credit card particulars before any service work can begin.
  • All Other Repairs – After Aerotech’s evaluation, the buyer shall be notified of the repair cost. At such time the buyer must issue a valid purchase order to cover the cost of the repair and freight, or authorize the product(s) to be shipped back as is, at the buyer’s expense. Failure to obtain a purchase order number or approval within thirty (30) days of notification will result in the product(s) being returned as is, at the buyer’s expense.

Repair work is warranted for ninety (90) days from date of shipment. Replacement components are warranted for one year from date of shipment.

Rush Service
At times, the buyer may desire to expedite a repair. Regardless of warranty or out-of-warranty status, the buyer must issue a valid purchase order to cover the added rush service cost. Rush service is subject to Aerotech’s approval.

On-site Warranty Repair
If an Aerotech product cannot be made functional by telephone assistance or by sending and having the customer install replacement parts, and cannot be returned to the Aerotech service center for repair, and if Aerotech determines the problem could be warranty-related, then the following policy applies:

  • Aerotech will provide an on-site Field Service Representative in a reasonable amount of time, provided that the customer issues a valid purchase order to Aerotech covering all transportation and subsistence costs. For warranty field repairs, the customer will not be charged for the cost of labor and material. If service is rendered at times other than normal work periods, then special rates apply.
  • If during the on-site repair it is determined the problem is not warranty related, then the terms and conditions stated in the following “On-Site Non-Warranty Repair” section apply.

On-site Non-Warranty Repair

  • If any Aerotech product cannot be made functional by telephone assistance or purchased replacement parts, and cannot be returned to the Aerotech service center for repair, then the following field service policy applies:
  • Aerotech will provide an on-site Field Service Representative in a reasonable amount of time, provided that the customer issues a valid purchase order to Aerotech covering all transportation and subsistence costs and the prevailing labor cost, including travel time, necessary to complete the repair.

Service Locations

https://www.aerotech.com/contact-sales.aspx?mapState=showMap

  • USA, CANADA, MEXICO
    Aerotech, Inc.
    Global Headquarters
  • TAIWAN
    Aerotech Taiwan
    Full-Service Subsidiary
  • CHINA
    Aerotech China
    Full-Service Subsidiary
  • UNITED KINGDOM
    Aerotech United Kingdom
    Full-Service Subsidiary
  • GERMANY
    Aerotech Germany
    Full-Service Subsidiary

Appendix B: Legacy System Interconnection
System interconnection examples are shown below. Cables can be purchased from Aerotech.

Figure B-1: System Interconnect Example (HPe)AEROTECH-TM5-Transformer-Module-image (19)

  • CONNECT ALL WIRING BEFORE
  • HAZARDOUS VOLTAGES PRESENT POWERING THE TM5.
  • FOLLOW ALL APPLICABLE WIRING AND SAFETY CODES,
  1. Wiring Specifications: 1.3 mm2 (#16 AWG) 300 V wire.
  2. Control Supply output voltage (115 VAC in this example) is always the same as the AC Input Voltage to the unit

Figure B-2: System Interconnect Example (CP)AEROTECH-TM5-Transformer-Module-image (20)

  • CONNECT ALL WIRING BEFORE
  • HAZARDOUS VOLTAGES PRESENT POWERING THE TM5.
  • FOLLOW ALL APPLICABLE WIRING AND SAFETY CODES.
  1. Wiring Specifications: 1.3 mm2 (#16 AWG) 300 V wire.
  2. Control Supply output voltage (115 VAC in this example) is always the same as the AC Input Voltage to the unit.

Figure B-3: System Interconnect Example (CL)AEROTECH-TM5-Transformer-Module-image (21)

  • CONNECT ALL WIRING BEFORE
  • HAZARDOUS VOLTAGES PRESENT POWERING THE TM5.
  • FOLLOW ALL APPLICABLE WIRING LB AND SAFETY CODES.
  1. The TM3 or TM5 must be configured for 56CT VAC output.
  2. Transformer Wiring: 0.5 mrn2 (#20 AWG) 300 V wire.
  3. Control Supply output voltage (115 VAC in this example) is always the same as the AC Input Voltage to the unit.

Appendix C: Revision History

Revision Description
3.02 Updated: EU Declaration of Conformity (Page 5)
3.01 New Section: UKCA Declaration of Conformity
3.00 General Update
2.02 Revision changes have been archived. If you need a copy of this revision, contact Aerotech Global Technical Support.
2.01
2.00
1.02
1.01
1.00

www.aerotech.com

FAQ

  • Q: What should I do if the TM5 Transformer Module overheats?
    • A: If the module overheats, immediately disconnect power and allow it to cool down before resuming operation.
  • Q: Can I use the TM5 with other Aerotech products?
    • A: Yes, you can refer to Appendix B for Legacy System Interconnection details when using the TM5 with other Aerotech systems.