TECNR FX3U-48MT/MR

Contents

TECNR FX3U-48MT/MR PLC Industrial Control Board User Manual

Models: FX3U-48MT, FX3U-48MR

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the TECNR FX3U-48MT and FX3U-48MR series Programmable Logic Controllers (PLCs). These industrial control boards are designed for a wide range of automation applications, featuring 24 digital inputs, 24 digital outputs, 6 analog inputs (AD), and 2 analog outputs (DA). They support Real-Time Clock (RTC), RS485, and CAN communication protocols, offering flexibility and robust control capabilities.

Front view of the TECNR FX3U-48MT/MR PLC industrial control board
Figure 1: Front view of the TECNR FX3U-48MT/MR PLC board.
Side view of the TECNR PLC industrial control board
Figure 2: Side view of the TECNR PLC board, showing mounting clips.

2. Specifications

The FX3U-48MT and FX3U-48MR models offer distinct output types and features. Refer to the table below for detailed specifications.

Table 1: Technical Specifications for FX3U-48MR and FX3U-48MT
Feature FX3U-48MR (Relay Output) FX3U-48MT (Transistor Output)
Output Type Relay Transistor
Download Speed 38.4kbps 38.4kbps
Memory Capacity 8000 steps 8000 steps
Input Voltage 24V DC 24V DC
Output Current 5A 1A
Digital Input Points 24 24
Digital Output Points 24 24
Analog Input (AD) 6 channels (AD0~AD2 0-10V, AD3~AD5 0-20mA) 6 channels (AD0~AD2 0-10V, AD3~AD5 0-20mA)
Analog Output (DA) 2 channels (0-10V) 2 channels (0-10V)
High-speed Counting 6 channels 3K (6 channels 60K optional) 6 channels 3K (6 channels 60K optional)
Pulse Output No 4 channels 100K (4 channels 12K optional)
Floating Point Support Support
Step Motor Control Not Support Support
Download Type Direct Download Direct Download
RS485 Communication Optional Optional
MODBUS Optional Optional
CAN Communication Optional Optional
Real-Time Clock (RTC) Supported Supported
Support Text Display Yes Yes
Support HMI Touch Screen Yes Yes
Programming Software GX Developer OR GX Works2 GX Developer OR GX Works2

Physical Dimensions and Weight:

  • Length: 11 cm
  • Width: 11 cm
  • Height: 10 cm
  • Weight: 0.65 kg

3. Setup and Wiring

Proper wiring is crucial for the safe and correct operation of your PLC. Please follow the diagrams and instructions carefully.

3.1 Power Supply Connection

The PLC requires a 24V DC power supply. Connect the 24V positive to the designated terminal and the 0V negative to its respective terminal on the board. Ensure the power supply is stable and within the specified voltage range.

24V 2A 50W Switch Power Supply
Figure 3: Example of a compatible 24V 2A 50W Switch Power Supply.

3.2 FX3U-48MT Wiring Diagram (Transistor Output)

For the FX3U-48MT model, the output load can only be connected to DC (within 3A). Do not connect AC or AC220. The X-point input is negative, low level NPN.

Wiring diagram for FX3U-48MT PLC
Figure 4: Wiring diagram for the FX3U-48MT PLC. Shows connections for loads, RS232 communication pins (GND, RX, TX), analog inputs/outputs, and 24V DC power.

3.3 FX3U-48MR Wiring Diagram (Relay Output)

For the FX3U-48MR model, the X-point input is negative, low level NPN.

Wiring diagram for FX3U-48MR PLC
Figure 5: Wiring diagram for the FX3U-48MR PLC. Shows connections for loads, RS232 communication pins (GND, RX, TX), analog inputs/outputs, and 24V DC power.

3.4 Communication Ports

The PLC features an RS232 communication port by default. If RS485 communication is required, ensure you have selected the appropriate model option. Optional programming cables may be needed for connection to a PC or HMI.

USB to RS232 Serial cable
Figure 6: Example of a USB to RS232 Serial cable for programming.
Male to Female DB9 Serial cable
Figure 7: Example of a Male to Female DB9 Serial cable, often used for PLC to HMI or PC connections.

4. Operating Instructions

4.1 Programming Software

The PLC can be programmed using GX Developer or GX Works2 software. Ensure you have the correct software version installed on your PC. Connect the PLC to your computer using a compatible programming cable (e.g., USB to RS232 serial cable).

4.2 Output Types and Compatible Loads

  • Transistor Output Type (FX3U-48MT): Suitable for controlling DC loads such as stepping motors, hydraulic valves, and intermediate relays. Maximum current is 3A.
  • Relay Output Type (FX3U-48MR): Suitable for controlling AC contactors, intermediate relays, and solenoid valves. Maximum current is 5A.
Comparison of MR Relay and MT Transistor PLC boards
Figure 8: Visual comparison highlighting the relay components on the MR board versus transistor components on the MT board.

4.3 Real-Time Clock (RTC)

Models with RTC functionality allow for time-based operations and scheduling within your automation programs. Ensure the RTC is configured correctly within your programming software if time-dependent logic is used.

5. Maintenance

To ensure the longevity and reliable operation of your PLC, follow these maintenance guidelines:

  • Keep Clean: Regularly clean the PLC and its surroundings to prevent dust and debris accumulation, which can affect performance and lead to overheating.
  • Check Connections: Periodically inspect all wiring connections for tightness and signs of corrosion. Loose connections can cause intermittent faults.
  • Environmental Conditions: Ensure the PLC operates within its specified environmental conditions (temperature, humidity) to prevent damage.
  • Firmware Updates: Check the manufacturer's website for any available firmware updates that may improve performance or address known issues.

6. Troubleshooting

If you encounter issues with your PLC, consider the following troubleshooting steps:

  • No Power: Verify that the 24V DC power supply is correctly connected and providing the correct voltage. Check fuses if applicable.
  • Communication Errors: Ensure the programming cable is securely connected to both the PLC and the PC. Confirm that the correct communication parameters (e.g., COM port, baud rate) are set in the programming software. If using RS485, ensure the correct option was purchased and configured.
  • Input/Output Malfunction: Check the wiring for the affected input or output points. Use a multimeter to verify sensor signals or actuator responses.
  • Program Not Running: Ensure the PLC is in 'Run' mode (check the running switch). Verify that the program has been successfully downloaded to the PLC and contains no errors.
  • Unexpected Behavior: Review your PLC program logic for any errors or unintended sequences.

7. User Tips

  • Communication Options: The PLC uses RS232 communication by default. If your application requires RS485 communication, ensure you select the correct model option during purchase.
  • Real-Time Clock (RTC): The RTC feature allows for time-sensitive programming. Utilize this for scheduling tasks or logging events based on time.
  • Output Load Matching: Always match the output type (Relay or Transistor) to the appropriate load. Transistor outputs are for DC loads (max 3A), while Relay outputs can handle AC contactors, intermediate relays, and solenoid valves (max 5A).
  • Programming Software: Familiarize yourself with GX Developer or GX Works2 for efficient programming and debugging.

8. Warranty and Support

For technical support, warranty claims, or further assistance, please contact the seller, Steady CNC Machine. Refer to your purchase documentation for specific warranty terms and contact information.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.