GEYA W2R Automatic Transfer Switch User Manual

Model: W2R ATS | Brand: GEYA

1. Introduction

The GEYA W2R series Mini ATS (Automatic Transfer Switch) is a PC-level micro household power transfer switch designed for on-grid solar PV systems. It facilitates automatic power transfer between a PV (Photovoltaic) system and city power, ensuring continuity, reliability, and safety of the power supply. This manual provides essential information for the safe and efficient installation, operation, and maintenance of your W2R ATS.

Important Note: The rated voltage of both the common and backup power supply must be within the range of 85%-110% of the device's rated voltage. The current cannot be less than 5A; otherwise, the coil may overheat or spontaneously burn. If your city voltage is unstable, it is recommended to add voltage protectors to your system.

2. Product Overview

The GEYA W2R ATS is designed for seamless switching between your PV system and the city grid. It features a compact design suitable for Din Rail mounting.

GEYA W2R ATS 2P front view with PV and City Power labels
GEYA W2R ATS 2P front view, illustrating PV (Source A) and City Power (Source B) connections.
Detailed view of GEYA W2R ATS highlighting antiflaming body, protection cover, and operating wires
Detailed view of the ATS, showing key features like the antiflaming body and protection cover.

Key Components:

  1. Composite Terminal Block for Main Power A
  2. Main Power Indicator
  3. Standby Power Indicator
  4. Manual / Automatic Selector Switch
  5. Composite Terminal Block for Standby Power B
  6. Main Power Terminals
  7. Standby Power Terminals
  8. Mounting Hole (4P)
  9. Manual Rotary Switch
  10. Load Terminals

3. Specifications

AttributeValue
Brand NameGEYA
Model NumberW2R ATS
TypeMini Circuit breaker
Rated VoltageAC220V or 110V
Rated Frequency50/60Hz
Rated Current63A, 100A
Poles Number2P, 3P, 4P
MountingDin Rail
FunctionPV POWER TO CITY POWER
Insulation VoltageAC 690V
Rated Impulse Withstand Voltage8KV
Rated Supply Voltage UsAC220V, 50HZ
Working Condition85% Us ~ 110% Us
Switching Time<50ms
Action Time<50ms
Electrical Life2000 times
Mechanical Life5000 times
CertificationCE
EU LVD VoltageBelow 50Vac or 75Vdc

Dimensions:

Technical parameters and product size for GEYA W2R ATS 2P, 3P, 4P models
Product dimensions for 2P, 3P, and 4P models.
  • 2P Model: 103mm (Height) x 107.5mm (Width)
  • 3P Model: 103mm (Height) x 125.5mm (Width)
  • 4P Model: 103mm (Height) x 142.5mm (Width)
  • Depth (all models): 78.5mm

4. Installation

Installation and wiring must be performed by qualified personnel familiar with this manual.

4.1. DIN Rail Installation

  1. Insert the upper end of the ATS base into the DIN rail.
  2. Push the lower end of the ATS base into the DIN rail until the snap fastener locks securely.
Diagram showing DIN Rail installation steps
DIN Rail Installation.

4.2. DIN Rail Disassembly

  1. Insert a screwdriver into the round hole of the DIN rail snap fastener at the bottom of the ATS.
  2. Use a screwdriver to pry the DIN rail snap fastener downward.
  3. Tilt the ATS upwards and remove it from the DIN rail.
Diagram showing DIN Rail disassembly steps
DIN Rail Disassembly.

4.3. Screw Mounting

  1. Pull out the upper and lower snap fasteners located at the bottom of the ATS.
  2. Secure the ATS to the panel with screws.

Before installation, check the ATS for any damage or missing parts. Manually operate the mechanism using the operation handle to verify smooth movement, correct switching of all phases, and the load status of both power sources. Ensure the text on the ATS panel is visible from the front. Contact the manufacturer if the correct mounting orientation cannot be achieved due to wiring or space constraints. Install suitable circuit breakers in accordance with IEC 60947-6-1 and the distribution system design to ensure personnel and equipment safety.

GEYA W2R ATS installed in a household distribution box on a 35mm rail
The W2R ATS is designed for installation in standard household distribution boxes on a 35mm rail.

5. Wiring Instructions

Always disconnect all power supplies before performing any wiring to prevent electric shock.

Product wiring diagrams for 2P, 3P, and 4P GEYA W2R ATS models
Wiring diagrams for 2P, 3P, and 4P models. Note the common power supply, alternate control line, and load output connections.
Diagram showing how to connect external indicators to the GEYA W2R ATS
Connection diagram for external indicators (Common closing, Common opening, Backup closing, Backup opening).
  • Connect the load to the lower terminals on the backup power side using stepped wiring.
  • Remove the isolation board before wiring, connect the load, reinstall the board, and ensure proper alignment. It is recommended to connect the load before wiring the backup power.
  • Connect the phase (AR) and neutral (AN) to the main power input terminals (mandatory).
  • Connect the phase (BR) and neutral (BN) to the backup power input terminals (mandatory).
  • The power indication signal uses a dry contact output; the generator signal is taken from the common (C) and normally closed (NC) terminals.
  • Use copper wires with a cross-sectional area of at least 2.0 mm², and keep control circuit wiring as short as possible.

A Safe Operating Limits:

  • Do not operate the device at control voltages below:
    • 190 V (for models with Ue: AC 220 V, 50/60 Hz)
    • 95 V (for models with Ue: AC 110 V, 50/60 Hz)
  • Operation below these limits may cause overheating and permanent damage.
Important note regarding voltage and current requirements for GEYA W2R ATS
Critical voltage and current requirements for proper operation and to prevent damage.

6. Operating Instructions

The W2R ATS offers both manual and automatic operation modes. The device is designed for quick and seamless power transfer.

GEYA W2R ATS showing manual/automatic switch and manual handle
The manual/automatic switch and manual handle for mode selection.
GEYA W2R ATS demonstrating automatic power switching time of less than 50ms
Automatic power switching occurs in less than 50ms.

Working Conditions:

  • Ambient Temperature Range: -5°C to +40°C (24-hour average must not exceed +35°C)
  • Altitude: Should be higher than the installation site and not exceed 2000 meters.
  • Operating Humidity: Up to 50% at +40°C; up to 90% at +25°C (condensation prevention required)
  • Contamination Level: Level 3
  • Mounting Orientation: The ATS can be installed vertically in cabinets.

Important Notes on Operation:

  • Manual / Automatic Operation: Electric (automatic) operation ensures reliable switching. Manual operation may cause contact wear and unstable performance due to variations in operator speed. Switch to manual mode only after power is disconnected and maintenance is completed. Keep the switch in automatic mode during normal operation, and return to automatic mode promptly after any manual operation.
  • Control Circuit TSE: The TSE is instantly energized during transfer. If internal switches malfunction after transfer, the control coil may be damaged. The coil operates reliably within 85%-110% of its rated voltage; insufficient voltage can cause overheating and failure. Ensure a stable power supply to avoid coil damage.

7. Maintenance, Inspection, and Storage

  • Maintenance and inspection must be performed by qualified personnel after disconnecting all power supplies.
  • The first inspection should be completed within 6 months of commissioning, and at least once per year thereafter. In harsh environments, increase inspection frequency as needed.
  • Key tasks include removing dust and debris, checking contact parts for damage, discoloration, or burn marks, and measuring contact resistance if necessary.
  • If the ATS is damp or idle for an extended period, dry it thoroughly and measure insulation resistance with a 500V megohmmeter (minimum 10 MΩ).
  • Store the ATS in a clean, dry environment, protected from mechanical impact.

Warning: This product has undergone insulation testing before leaving the factory. Incorrect dielectric testing will damage the control system, and it is strictly prohibited to conduct dielectric testing with ATS.

8. Troubleshooting

  • High Latency / Equipment Shutdown: If connected equipment (e.g., computers, TVs) turns off during power transfer, the transfer latency might be too high for sensitive electronics. Ensure the backup power source is stable and within the specified voltage range. Consider adding a UPS for critical loads.
  • Automatic Transfer Failure: If the ATS does not automatically transfer between power sources (e.g., from grid to PV, or vice-versa), check the control circuit wiring and ensure the voltage of both power sources is stable and within the 85%-110% rated range. Verify the manual/automatic selector switch is in the 'Auto' position.
  • Indicator Light Issues: If a power source indicator (e.g., grid indicator) remains lit even when that source is absent, it may indicate a wiring error or an internal fault. Recheck all connections according to the wiring diagrams.
  • Component Burning Out: If components burn out shortly after installation, immediately disconnect power. This is often caused by incorrect voltage, insufficient current (below 5A), or unstable power supply. Ensure all electrical parameters meet the product specifications.
  • Compatibility with 240V 50Hz Systems: The product is specified for AC220V or 110V, 50/60Hz. For 240V systems, ensure the voltage remains within the acceptable operating range (85%-110% of 220V, which is 187V-242V).

9. User Tips

  • Verify Dimensions: Before purchasing or installing, carefully check the product dimensions (Height: 103mm, Width: 107.5mm/125.5mm/142.5mm, Depth: 78.5mm) to ensure it fits your standard distribution box or panel without requiring modifications.
  • Thorough Testing: After installation, perform thorough testing of both manual and automatic transfer functions to confirm proper operation and stability before connecting all loads.
  • Stable Power Supply: Always ensure a stable power supply for both the main and backup sources to prevent damage to the ATS coil and ensure reliable operation. If voltage fluctuations are common, consider voltage protection.

10. Manufacturer Information

GEYA Electric was established in 2007 and is a private-owned enterprise specializing in the research, manufacturing, and sales of low voltage electrical and automatic controlling products. The company is located in Wenzhou City, China. GEYA products are certified to required industry standards, including CCC, CE, CB, SAA, SEMKO, TUV, and RoHS.

Official GEYA company introduction video, showcasing their manufacturing process and product range.

For further information or support, please refer to the official user manual PDF: GEYA W2R User Manual (PDF)

11. Warranty and Support

For warranty claims, technical support, or service inquiries, please contact your original point of purchase or the GEYA Official Store directly. Ensure you have your product model number and purchase details available.