Contents

TECNR FX3U-24MR/MT PLC Industrial Control Board User Manual

Model: FX3U-24MR/MT Series

1. Product Overview

The TECNR FX3U-24MR/MT is a versatile Programmable Logic Controller (PLC) industrial control board designed for various automation applications. It features 14 digital inputs, 10 digital outputs, 6 analog inputs (AD), and 2 analog outputs (DA). Depending on the specific model, it may include RS485 communication capabilities and a Real-Time Clock (RTC) for time-sensitive operations. The series offers both Relay (MR) and Transistor (MT) output types to suit different load requirements.

TECNR FX3U-24MR/MT PLC Industrial Control Board
Figure 1: TECNR FX3U-24MR/MT PLC Industrial Control Board
Comparison of MR Relay and MT Transistor output types
Figure 2: Visual comparison between MR (Relay) and MT (Transistor) output types, highlighting the different components.

2. Specifications

The following tables detail the specifications for various models within the FX3U series. Please refer to your specific model for exact features.

2.1. FX3U-14/24/30 Series Specifications

FeatureFX3U-14MRFX3U-14MTFX3U-24MRFX3U-24MTFX3U-30MR
Output typeRelayTransistorRelayTransistorRelay
Download speed38.4kb38.4kb38.4kb38.4kb38.4kb
Memory capacity80008000800080008000
Input Voltage24V 220V24V DC24V 220V24V DC24V 220V
Output Current5A1A5A1A5A
Digital Input Point88141416
Digital Output Point66101014
Analog InputAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MA
Analog Output2DA 0-10V2DA 0-10V2DA 0-10V2DA 0-10V2DA 0-10V
RS485/RTCOptionalOptionalOptionalOptionalOptional
MODBUSOptionalOptionalOptionalOptionalOptional
CAN////Optional
SoftwareGX Developer OR GX Works2GX Developer OR GX Works2GX Developer OR GX Works2GX Developer OR GX Works2GX Developer OR GX Works2

2.2. FX3U-32/48/56 Series Specifications

FeatureFX3U-32MTFX3U-48MRFX3U-48MTFX3U-56MRFX3U-56MT
Output typeTransistorRelayTransistorRelayTransistor
Download speed38.4kb38.4kb38.4kb38.4kb38.4kb
Memory capacity80008000800080008000
Input Voltage24V DC24V 220V24V DC24V 220V24V 220V
Output Current1A5A1A5A1A
Digital Input Point1624243232
Digital Output Point1624242424
Analog InputAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MAAD0~AD2 0-10V, AD3~AD5 0-20MA
Analog Output2DA 0-10V2DA 0-10V2DA 0-10V2DA 0-10V2DA 0-10V
RS485/RTCOptionalOptionalOptionalYESYES
MODBUSOptionalOptionalOptionalYESYES
CANOptionalOptionalOptionalYESYES
SoftwareGX Developer OR GX Works2GX Developer OR GX Works2GX Developer OR GX Works2GX Developer OR GX Works2GX Developer OR GX Works2

2.3. FX3U-24MR/MT Specifics

FeatureFX3U-24MRFX3U-24MT
Output typeRelayTransistor
Input Voltage24V DC24V DC
Output Current5A1A
Input Point1414
Output Point1010
Analog Input6AD6AD
Analog Output2DA2DA
High-speed counting6 channel 3K (6 channel 60K optional)6 channel 3K (2 channel 60K optional)
Pulse outputNo4 channel 12K (4 channel 100K optional)
Floating pointSupportSupport
Step motorNot SupportSupport
Memory capacity8000 steps8000 steps
Download typeDownload directlyDownload directly
RS485OptionalOptional
MODBUSOptionalOptional
Support text displayYESYES
Support HMI Touch ScreenYESYES
SoftwareGX Developer OR GX Works2GX Developer OR GX Works2

3. Setup and Wiring

Proper setup and wiring are crucial for the safe and correct operation of your PLC. Ensure all connections are secure and follow the diagrams below.

3.1. Power Supply

The PLC requires a 24V DC power supply. Ensure the power supply is stable and provides sufficient current for the PLC and connected loads.

24V 2A 50W Switch Power Supply
Figure 3: Example of a compatible 24V 2A 50W switch mode power supply.

3.2. Communication Cables

For programming and communication, a serial cable (USB to RS232) is typically used. The product does not include this cable by default. Customers without programming cables should acquire one according to their needs.

USB to RS232 Serial Cable
Figure 4: Example of a USB to RS232 serial cable for PLC programming.

3.3. Wiring Diagrams

Refer to the following diagrams for correct wiring of the FX3U-24MR (Relay) and FX3U-24MT (Transistor) models. Pay close attention to input/output connections, power, and communication ports.

FX3U-24MR Wiring Diagram
Figure 5: Wiring diagram for the FX3U-24MR (Relay) model. Note: Output load can only be connected to DC DC (within 3A). Do not connect to AC or AC220V. The X-point input is negative, Low level NPN. RS232 communication port pin definition is provided.
FX3U-24MT Wiring Diagram
Figure 6: Wiring diagram for the FX3U-24MT (Transistor) model. Note: Output load can only be connected to DC DC (within 3A). Do not connect to AC or AC220V. The X-point input is negative, Low level NPN. RS232 communication port pin definition is provided.

4. Operating Instructions

The FX3U-24MR/MT PLC operates by executing programs stored in its memory. These programs define the logic for controlling outputs based on input signals.

4.1. Programming

Programming of the PLC is typically done using specialized software such as GX Developer or GX Works2. These software suites allow users to create ladder logic diagrams or other programming languages to define the control sequence. The program is then downloaded to the PLC via an RS232 serial connection (or RS485 if the option is present).

4.2. Input/Output Operation

  • Digital Inputs (X-points): These inputs receive signals from external devices (e.g., sensors, switches). The X-point input is negative, operating on a low-level NPN logic.
  • Digital Outputs (Y-points): These outputs control external devices (e.g., relays, motors, lights).
  • Analog Inputs (AD): The PLC supports 6 analog inputs, typically configured for 0-10V or 0-20mA signals, allowing for measurement and control of continuous variables.
  • Analog Outputs (DA): The PLC provides 2 analog outputs, typically 0-10V, for controlling devices that require variable voltage signals.

4.3. Communication

The PLC supports RS232 communication by default. Models with optional RS485 communication allow for integration into larger industrial networks. RTC (Real-Time Clock) functionality, if present, enables time-based control and data logging.

5. Maintenance

To ensure the longevity and reliable operation of your TECNR PLC, follow these general maintenance guidelines:

  • Keep Clean: Regularly clean the exterior of the PLC to prevent dust and debris accumulation, which can affect cooling and component lifespan.
  • Environmental Control: Operate the PLC within its specified environmental conditions (temperature, humidity) to prevent damage.
  • Connection Checks: Periodically inspect all wiring connections for tightness and signs of corrosion or damage. Loose connections can lead to intermittent operation or failure.
  • Firmware Updates: If available, consider applying firmware updates from the manufacturer to improve performance or address known issues.
  • Backup Programs: Always maintain backup copies of your PLC programs.

6. Troubleshooting

If you encounter issues with your PLC, consider the following troubleshooting steps:

  • Power Issues: Verify that the 24V DC power supply is correctly connected and providing the correct voltage. Check for any blown fuses.
  • Input/Output Malfunctions: Use a multimeter to check input signals at the PLC terminals. For outputs, check if the PLC is commanding the output and if the external device is receiving power.
  • Communication Problems: Ensure the correct communication cable (RS232 or RS485) is used and properly connected. Verify software settings (COM port, baud rate) match the PLC configuration.
  • Program Errors: If the PLC is not behaving as expected, review your ladder logic program for errors or incorrect logic. Use the programming software's diagnostic tools.
  • Indicator Lights: Observe any status indicator lights on the PLC. Refer to the product documentation for the meaning of different light patterns (e.g., RUN, ERROR).

7. User Tips

  • Programming Software: The recommended software for programming this PLC is GX Developer or GX Works2. These are standard programming environments for Mitsubishi-compatible PLCs.
  • Software Licensing: The programming software (GX Developer or GX Works2) typically requires a license. This license is usually not provided with the PLC hardware itself and must be acquired separately from the software vendor.
  • RS485/RTC Option: If your application requires RS485 communication or Real-Time Clock functionality, ensure you select a model that explicitly includes these features, as they are optional on some variants.

8. Warranty and Support

For warranty information and technical support, please contact the seller or manufacturer directly. Keep your purchase records handy for any inquiries.