RuoShui VC71B

Contents

RuoShui 71B Signal Generator User Manual

Model: VC71B | Brand: RuoShui

1. Overview

This series of meters is categorized into the standard and thermocouple type. This manual is illustrated based on the thermocouple type.

This series of meters has the following functions:

  • 100 mV, 30 V DC voltage measurement, 20 mA DC current measurement, and switching value measurement;
  • 100 mV, 30 V DC voltage output, 20 mA DC current output and SIMULATE output;
  • V, mA manual step output, automatic waveform output;
  • Simultaneous display of V, mA and percentage;
  • Loop detection function: It simultaneously provides the 24 V loop power supply and measures the current.

The following functions are added to the thermocouple type:

  • Eight scale division (i.e., R, S, B, K, E, J, T and N) thermocouple measurement and output function;
  • Temperature display in Celsius degree and Fahrenheit degree;
  • Automatic and manual cold junction compensation function.
RuoShui 71B Signal Generator front view

Figure 1: RuoShui 71B Signal Generator

2. Safety Warnings

The design, manufacturing and test of this meter all meet the safety standard requirements of IEC61010-1. The manual contains the warnings and safety rules that users must comply with to ensure the safe use of the meter and its safe status. Please read the following instructions before use.

Warning

  • Do not use a damaged meter. Before using the meter, please check its enclosure to see if there is any crack, missing plastic part or if its outer protective cover is in place. Please pay special attention to the insulation layer of the joints.
  • Please make sure that the battery cover is locked tightly before using the meter.
  • Please remove the test leads from the meter before opening the battery cover.
  • Check the test lead to see if its insulation has any damage or it has any exposed part. Check the connectivity of the test leads. If the lead is damaged, please replace it before using the meter.
  • If the meter malfunctions, it means that the protection could have been damaged, so please do not use it. If there is any doubt, the meter should be sent for maintenance.
  • Do not use the meter near explosive gases, steam or dust.
  • The meter only uses 6LR61 batteries, so please make sure the battery is correctly installed.
  • When using a test probe, the finger should hold the back of the probe's protective layer.
  • When connecting wires, connect the common test leads first, and then connect the live test leads. When dismantling, remove the live test lead first.
  • Please carefully read and understand the manual before using the meter.
  • The requirements of the manual must be complied with at any time, and the manual should be well kept to ensure it available for reference at any time.
  • During the meter test, incorrect operation may lead to accident and damage to the meter.

Cautions

To prevent damage to the meter caused by the tested equipment:

  • The knob switch must be turned to the correct position of measurement range when conducting a measurement. The test lead and the tested circuit must be disconnected before turning the knob switch. It is strictly prohibited to switch the range during a measurement, to prevent damage to the meter.
  • When the screen shows "OL" signal, do not use the meter.
  • Do not store or use the meter in a high temperature, high humidity, combustible, explosive, or strong electromagnetic environment, or a place with excessive dew or direct exposure to sunlight.
  • Do not use abrasives or solvents to clean the meter; please use a damp cloth or neutral detergent.
  • When the meter is dampened, please dry it up before storing it.

Symbols

SymbolMeaningSymbolMeaning
~ACGrounding
---DCDouble insulation
~---AC and DC+Battery
!Critical information

3. Meter Panel Introduction

RuoShui 71B Signal Generator front panel diagram

Figure 2: Front Panel Layout

No.LocationKnob Switch Function
①TC mVDC millivolt (DCmV) measurement. Thermocouple type: TC measurement can be selected by pressing the button.
②VDC voltage (DVC) measurement
③Switching value measurement
④mADC current (DCmA) measurement
⑤24V LOOP mALoop current measurement (loop power supply)
⑥SOURCE mACurrent output
⑦SIMULATE mAAnalog transmitter
⑧VDC voltage (DCV) output
⑨TC mVDC millivolt (DCmV) output

Display Screen

Figure 2-3 and Table 2-3 are the illustrations for the screen display.

RuoShui 71B Signal Generator display screen

Figure 3: Display Screen Indicators

DisplayIllustrations
+Low battery
INPUTThe meter works in the measurement mode
OUTPUTThe meter works in the output mode
RUNStart automatic waveform output
RJ-MManual cold junction compensation of thermocouple
RJ-AAutomatic cold junction compensation of thermocouple
-8.8.8.8.Data display area
%Percentages of voltage and current
KJRTSBENThermocouple (TC) scale division

4. Setup

Startup

To switch on the meter, please turn the knob switch to any of the function positions.

When the power is turned on, the meter starts an internal self-diagnosis with a full screen display before corresponding operations can be conducted.

To ensure correct live operation of the meter, the meter must be powered off for 5 seconds before restarting it.

Automatic Power Off

The factory setting of the meter: If the user does not perform any operation on the meter within 15 minutes, it will automatically turn off the power.

Once the meter automatically powers off, to restart it, please turn the knob switch to OFF position and then turn it on.

Users can set on their own whether to use the automatic power off function (Refer to Chapter IV "Setting Function").

Note: The meter will still consume about 1 mA current after it automatically turns off power, so it is recommended to turn the knob switch to the OFF position when not using it.

Turn on Back Light

Press the button Backlight button icon continuously to turn on the back light, and press the button Backlight button icon continuously again to turn it off.

Automatic Back Light off

The factory setting of the meter: If the user does not turn off the meter's back light within 30 seconds, the meter will automatically turn off the back light.

Users can set on their own whether to use the automatic back light off function (Refer to Chapter IV "Setting Function").

Battery Replacement

This meter uses one 9V (6LR61) alkaline battery. Please follow the following steps to replace the battery:

  1. Turn off the meter power and disconnect all test leads;
  2. Remove the screw on the battery box with a cross screwdriver, and remove the battery cover.
  3. Take off the old battery and fasten a new battery to the battery buckle. Then put it into the battery compartment;
  4. Put the battery in the lower case and tighten the screw.

Video: Unboxing, test leads, and battery compartment access.

Packaging accessories including test leads and manual

Figure 4: Packaging Accessories

5. Operating Instructions

Measurement of DC Voltage

  1. Turn the knob switch to the white "V" or "TC mV" position;
  2. Insert the black probe into "COM" plughole and the red probe into "INPUT" plughole;
  3. Connect the probes to the circuit to be measured and read the measured value after stabilization.
Displayed voltage valuePercentage display
0~10V1~5V
0.00V0.0%-25.0%
1.00V10.0%0.0%
5.00V50.0%100.0%
10.00V100.0%225.0%
30.00V300.0%750.0%

Measurement of Current

  1. Turn the knob switch to the white "mA" position;
  2. Insert the black probe into "COM" plughole and the red probe into "INPUT" plughole;
  3. Connect the probes to the circuit to be measured and read the measured value after stabilization.
Displayed current valuePercentage display
4~20mA0~20mA
0.00mA-25.0%0.0%
4.00mA0.0%20.0%
20.00mA100.0%100.0%
22.00mA112.5%110.0%

Measurement of Circuit Current (Loop Power Supply)

This function can be used to measure the flowing current when 24V constant DC is applied.

The 24V circuit measurement function can be used to measure the transmitter circuit.

(The meter can be connected to the transmitter instead of the signal regulator.)

Input measurement examples for DCmV, DCV, DCmA, and Thermocouple

Figure 5: Input Measurement Examples

Test of Switching Value

  1. Turn the knob switch to "Switching value icon" position;
  2. Insert the black probe into "COM" plughole and red probe into "INPUT" plughole;
  3. Connect the probes to the contacts on the switch to be tested. And display "OFF" (open) or "ON" (close) according to the status of the switch. When the test result is "ON", the buzzer will tweet. When the switch resistance exceeds 20kΩ, it is considered to be in an "OFF" status.

Measurement of Thermocouple

  1. Turn the knob switch to white "TC mV" position and select the corresponding scale division of thermocouple (TC).
  2. Insert the thermocouple into "COM" and "INPUT" plugholes. Ensure that the thermocouple plug with + symbol is inserted into "INPUT" plughole of the meter.
  3. Read the measurement result from the display.

The main display area shows the temperature value and the auxiliary display area shows the cold junction temperature value. Users can select automatic compensation (screen display RJ-A, automatic compensation once every 10 seconds) or manual compensation (screen display RJ-M) for cold junction temperature; or select to close cold junction compensation. Whether to open the cold junction compensation is up to the user himself (Refer to Chapter IV "Setting Function").

Use of Voltage Output Function

  1. Turn the knob switch to yellow "V" position or "TC mV" position;
  2. Insert the black probe into "COM" plughole and red probe into "OUTPUT" plughole;
  3. Connect the probes to the input end of user's meter;
  4. Press the button Up adjustment key icon or Down adjustment key icon to select the output setting position; press the button Up adjustment key icon or Down adjustment key icon to change the value of setting position, which can increase or decrease automatically. Keep pressing the button, and the value can be changed consecutively after 1 second.

Use of Thermocouple Output Function

  1. Turn the knob switch to yellow "TC mV" position; press the button Up adjustment key icon to select the corresponding scale division of thermocouple (TC);
  2. Insert the black probe into "COM" plughole and red probe into "OUTPUT" plughole;
  3. Connect the probes to the input end of user's meter;
  4. Press the button Up adjustment key icon or Down adjustment key icon to select the output setting position; press the button Up adjustment key icon or Down adjustment key icon to change the value of setting position, which can increase or decrease automatically. Keep pressing the button, and the value can be changed consecutively after 1 second.

The main display area displays the temperature setting value, and the auxiliary display area displays the cold junction temperature value. Users can select automatic compensation (screen display RJ-A, automatic compensation once every 10 seconds) or manual compensation (screen display RJ-M) for cold junction temperature; or select to close cold junction compensation. Whether to open the cold junction compensation is up to the user himself (Refer to Chapter IV "Setting Function").

Use of Current Output Function (SOURCE Mode)

This meter provides two output modes: SOURCE mode: Current is provided from the meter; SIMULATE mode (analog): The meter absorbs the current from the external voltage source.

Constant Current Output (SOURCE Mode)

  1. Turn the knob switch to the "SOURCE mA" position and the output is set as 0mA;
  2. Insert the black probe into "COM" plughole and red probe into "OUTPUT" plughole;
  3. Connect the lead wire to the circuit to be measured;
  4. Press the button Up adjustment key icon or Down adjustment key icon to select the output setting position; press the button Up adjustment key icon or Down adjustment key icon to change the value of setting position, which increase or decrease automatically. Keep pressing the button, and the value can be changed consecutively after 1 second.

Constant Current Output (SIMULATE Mode)

SIMULATE (analog) mode refers to simulation of a set of current circuit transmitters by using the meter. When the external DC voltage (5 to 28V) and the measured current circuit are in series, SIMULATE mode should be selected.

Warning

Before connecting test leads to current circuit, set the knob switch in some position of mA output first. Otherwise, the low impedance from other positions of the knob switch may occur in the circuit, resulting in the current up to 35mA flowing in the circuit.

Output function examples for DCmV, DCV, DCmA, and Thermocouple output

Figure 6: Output Function Examples

Manual Step Output

Under 10V voltage and current output, press the button Up adjustment key icon to select 25% or 100% manual step output function in turn, the screen shows: Switching value icon.

Press the button Up adjustment key icon or Down adjustment key icon to increase or decrease the voltage or current by 25% step or 100% step.

Different voltage and current span can be selected through this function. (Refer to Chapter IV "Setting Function")

Voltage steppingOutput value
0~10V1~5V
0.0%0.00V1.00V
25.0%2.50V2.00V
50.0%5.00V3.00V
75.0%7.50V4.00V
100.0%10.00V5.00V
Current steppingOutput value
4~20mA0~20mA
0.0%4.00mA0.00mA
25.0%8.00mA5.00mA
50.0%12.00mA10.00mA
75.0%16.00mA15.00mA
100.0%20.00mA20.00mA

Automatic Waveform Output

Under 10V voltage and current output, press the button Switching value icon to select the automatic waveform output function with the screen display: A, and at the same time display the default output set value and output the corresponding signal.

Press the button Up adjustment key icon or Down adjustment key icon to start or stop automatic waveform output. If automatic waveform output is started, the screen displays the "RUN" character; if the automatic waveform output is stopped, the output will remain at the current value.

Different voltage and current span can be selected through this function. (Refer to Chapter IV "Setting Function")

6. Setting Function

To enter the meter setup, press the button Switching value icon under the meter shutdown status, and then turn the knob switch to any non-OFF position. In the setup mode, the screen's auxiliary display area displays the settings, and the main display area shows the factory default values. Press the button Up adjustment key icon to change the settings; press the button Switching value icon continuously to save the settings (the main display area shows SAVE, indicating that this setting has been saved). When the setup is completed, turn off the machine.

SettingsFunctionDefault Values
APOF Automatic shutdownON or OFF. Press the button Up adjustment key icon or Down adjustment key icon to select.ON
BLOF Automatic off backlightON or OFF. Press the button Up adjustment key icon or Down adjustment key icon to select.ON
IPCE Current span4-20 or 0-20. Press the button Up adjustment key icon or Down adjustment key icon to select.4-20
UPCE Voltage span0-10 or 1-05. Press the button Up adjustment key icon or Down adjustment key icon to select.0-10
TEMP Temperature unit°C or °F. Press the button Up adjustment key icon or Down adjustment key icon to select.°C
RJ-ON Cold junction compensation of thermocoupleON or OFF. Press the button Up adjustment key icon or Down adjustment key icon to select.ON
RJ-SET Cold-junction compensation methodAutomatic (AUTO) or manual operation (MANUAL). Press the button Up adjustment key icon or Down adjustment key icon to select.AUTO
RJ-TEMP Temperature on the manual cold junction-10.0°C~50.0°C (0.0°F~122.0°F). Press the button Up adjustment key icon or Down adjustment key icon for the setting position; press the button Up adjustment key icon or Down adjustment key icon to change the setting position value.23.0
FACE Return to the factory default valuePress the button Switching value icon continuously, and the main display area displays SAVE, indicating that it has returned to the factory default value.

7. General Maintenance

  • Clean the meter enclosure on a regular basis with a damp cloth and mild detergent. Do not use abrasives or solvents.
  • If the battery isn't used for a long time, it shall be taken out.
  • Dirt or wet air on the plughole can affect the reading.

Please follow the following steps to clean the connection port:

  1. Turn off the meter power and dismantle all test leads;
  2. Clean the dirt on the connection port;
  3. Clean each connection port with a new cotton swab dipped in alcohol.

8. Specifications

General Characteristics

CharacteristicValue
Display refresh2~3 times/second
Overload protection50mA/30V
Working temperature and humidity range0~40 °C and a relative humidity below 85% (no condensation)
Storage temperature and humidity range-20 °C~60 °C and a relative humidity below 90% (no condensation)
Precision ensures the temperature and humidity range23±5°C and a relative humidity below 75% (no condensation)
Temperature coefficient0.1 × basic precision/°C (temperature range <18 °C or >28 °C)
Ambient conditions for useIndoor and outdoor use (not waterproof), with an elevation of 0~2000 m
Outrange displayOL
Battery kind9V (6LR61) alkaline battery one
Power consumptionWhen alkaline battery is used: Loop current measurement and DC current output (SOURCE) 20mA (a load of 1000Ω): approx. 1000mVA. Other work function: approx. 300mVA
Low batteryDisplay battery sign
Automatic shutdownNo operation for about 15 min by default
Preheating time10 min
Close the meter enclosure for calibrationNo need for internal adjustment
Size147(L)×75(W)×42(D)mm
WeightApprox. 230 g
Calibration cycleOne year

Detailed Precision Index of Measurement

The accuracy is determined within one year after calibration when the operating temperature is 23 ± 5 °C, and the relative humidity is 75%.

The precision range can be marked as: ± ([% of the reading]+ count) (Note: "count" represents the increased or decreased number of the minimum effective digit).

Measurement FunctionRangeMeasure RangeResolutionAccuracyNotes
DC voltage100mV-10.0mV~110.0mV100uV0.2%+4
  • Input impedance: 30V: 300kΩ (nominal value) mV:>1MΩ (nominal value)
  • Common mode rejection: 50Hz or 60Hz >80dB
  • Series mode rejection: 50Hz or 60Hz > 40dB
  • Overvoltage protection:30V (peak to peak value)
30V-5.00V~30.00V10mV0.2%+4
DC current20mA0.00mA~22.00mA0.01mA0.2%+4
  • Overload protection: 50mA/30V
  • Load voltage: approx. 18mV/mA
ThermocoupleR0°C~1760°C1°C0.2%+4Thermocouple measurement adopts ITS-90 thermometric scale, whose precision does not include error of the cold junction compensation, and the impact of thermoelectrical potential
S0°C~1760°C
B400°C~1820 °C
K-200°C~1370°C
E-200°C~1000°C
J-200°C~1200°C
T-200°C~400°C
N-200°C~1300 °C

Detailed Precision Index of Output

Output FunctionRangeOutput Setting RangeResolutionAccuracyNotes
DC voltage100mV0.0mV~110.0mV100uV0.2%+4
  • Maximum output current 1mA
  • Maximum output current 5 mA (<10V)
10V0.00V~11.00V10mV0.2%+4
DC current20mA0.00~22.00mA0.01mA0.2%+420mA maximum load: 1KΩ
Analog transmitter SIMULATE-20mA0.00~-22.00mA0.001mA0.2%+4
  • External power supply: 5~28V
  • 20mA maximum load: 1KΩ
Loop power supply LOOP24V±10%Maximum output current 25mA
ThermocoupleR0°C~1760°C1°C0.2%+4Thermocouple measurement adopts ITS-90 thermometric scale, whose precision does not include error of the cold junction compensation, and the impact of thermoelectrical potential
S0°C~1760 °C
B400°C~1800°C
K0°C~1350°C
E0°C~700°C
J0°C~950°C
T0°C~400°C
N0°C~1300°C

Capacitive load≥0.01uF

9. User Tips

  • Always refer to the detailed instructions in this manual for specific measurement and output procedures to ensure accurate and safe operation.
  • Before any operation, ensure the device is powered off and test leads are properly connected or disconnected as required.
  • For optimal performance and longevity, store the device in a clean, dry environment away from extreme temperatures and humidity.

10. Warranty and Support

Warranty & Guarantee

  • We offer 100% genuine original RuoShui (Victor) instruments.
  • 1 Year warranty for all of our products. (Excluding item damaged and/or misused after receipt. Accessories come with 3-month warranty.)
  • We will bear all the shipping cost if the product is not as advertised, otherwise, Buyer shall pay the shipping cost.
  • Defective items must be reported and returned within the warranty period (and in the original packaging, if possible)

Other Terms & Conditions

  • If there is any problem with your order, Please do not contact us first, we will try our best to give you the best solution. Please don't give negative feedback before contact us, that won't help to solve your problem.
  • No battery will be sent the product due to safety reason.
  • We are not responsible for any custom duty or import tax.

Notes for Use of This Manual

This manual is subject to variation without prior notice.

The content of this manual is supposed to be correct. If the customer detects any mistake, omission, etc., please contact the manufacturer.

Our company does not undertake any responsibility for accidents or hazards caused by incorrect operations of the user.

The functions described in this manual do not be used as grounds for using the product for special purposes.

For further assistance, please refer to the official user manual PDF: View User Manual (PDF)