SmartGen HGM1790N

Contents

SmartGen HGM1790N Genset Controller User Manual

Single Unit Automation and Monitoring Control

1. Product Overview

The SmartGen HGM1790N genset controller is designed for single unit automation and monitoring control, also suitable for pumping units. It supports both manual and remote start/stop operations. The controller monitors and protects the genset by collecting and analyzing data such as generator voltage, current, water temperature, oil pressure, and more. A graphical LCD on the front panel displays fault conditions and provides alarm signals for timely maintenance. Parameters and delay values can be adjusted via the front panel or PC software connected via a USB port.

Video: Overview of the SmartGen HGM1790N Genset Controller, showing its physical features and connections.

SmartGen HGM1790N Genset Controller in packaging.

Image: SmartGen HGM1790N Genset Controller in its packaging.

2. Specifications

  • Display: Graphical LCD (with backlight), LED indicators, touch-buttons.
  • Construction: Hard screen acrylic material, silicone panel and buttons for high/low temperature adaptation.
  • Power Supply: DC (8~35)V, compatible with 12V or 24V starter batteries.
  • Measurements (Generator): Voltage (V), Frequency (Hz), Power (kW), Current (A), Load Percentage (%).
  • Measurements (Engine): Oil Pressure (kPa), Temperature (ºC), Fuel Level (%), Total Running Time (H), Battery Voltage (V), Engine Speed (RPM), Accumulated Start Times (displayed on PC).
  • Protection: Genset fault protection and display functions.
  • Working Modes: Manual, Auto, Stop.
  • Sensor Compatibility: Multiple temperature, pressure, fuel level sensors (user-defined), can be used in parallel with annunciator.
  • Crank Disconnect Conditions: Selectable (engine speed sensor, oil pressure, generator frequency).
  • Input Ports: 1 configurable input (digital or liquid level sensor).
  • Fixed Relay Outputs: 4 (fuel, start, stop, idle).
  • Configurable Output Ports: 1 (common alarm, fail to stop, preheat, or idle control).
  • Parameter Adjustment: Front panel or PC software via type-B USB port.
  • Regulation: Digital regulation for higher reliability and stability.
  • Design: Modular, self-extinguishing ABS plastic enclosure, embedded installation.
  • Case Dimensions: 95 x 86 x 46.5 mm.
  • Origin: Mainland China.
  • Electrified: Yes.
  • High-concerned chemical: None.

3. Setup and Installation

The HGM1790N controller features a modular design for embedded installation. Ensure proper mounting in a suitable enclosure.

3.1 Wiring Connections

Refer to the wiring diagram below for detailed connection instructions. Pay close attention to the polarity and correct terminal assignments for all inputs and outputs.

Wiring diagram for the SmartGen HGM1790N Genset Controller.

Image: Wiring diagram for the SmartGen HGM1790N Genset Controller, detailing connections for magnetic pickup, engine temp, oil pressure, aux inputs, remote start, crank output, fuel output, EM.Stop input, B+, B-, Gens(L), Gens(N), Load(L*), Load(L), Aux. Output 1, 2, 3, and USB port.

  • Power Supply: Connect the DC (8-35)V power supply to the B+ and B- terminals.
  • Magnetic Pickup: Connect to terminal 10.
  • Engine Temp Input: Connect to terminal 9.
  • Oil Pressure Input: Connect to terminal 8.
  • Aux. Input: Connect to terminal 7.
  • Remote Start Input: Connect to terminal 6.
  • Crank Output: Connect to terminal 5.
  • Fuel Output: Connect to terminal 4.
  • Em. Stop Input: Connect to terminal 3.
  • Generator Connections: Gens(L) to 11, Gens(N) to 12.
  • Load Connections: Load(L*) to 13, Load(L) to 14.
  • Aux. Outputs: Aux. Output 1 to 15, Aux. Output 2 to 16, Aux. Output 3 to 17.
  • USB Port: Use the type-B USB port for PC software connection.

Caution:

  • Start and fuel output ports should use large capacity relays.
  • When the sensor port is configured as "high digital input is active", hanging in air means a high electrical level is selected; it cannot be connected to the power supply positive.

4. Operating Instructions

The HGM1790N controller features a user-friendly interface with a graphical LCD, LED indicators, and touch-buttons.

4.1 Panel Indications

HGM1790N Panel Indications

Image: Diagram showing the HGM1790N panel indications including alarm, stop, auto, and start status indicators.

  • Stop Status Indicator: Light indicates genset is in stop mode.
  • Auto Status Indicator: Light indicates genset is in auto mode.
  • Manual Start Indicator: Light indicates genset is in manual mode.
  • Alarm Indicator: Blinks slowly (1 time/s) when a warning alarm occurs; blinks fast (5 times/s) when a shutdown alarm occurs.

4.2 Button Functions

Table of button definitions and LCD icons for the HGM1790N controller.

Image: Table of button definitions and LCD icons for the HGM1790N controller.

Key Definition Description
O Stop/Reset In auto/manual mode, press this button to shut down the genset; reset shutdown alarms when genset is in alarm status; indicator lights and LCD icons status can be tested if pressed for over 3s in stop mode; stop immediately if pressed during stop process; quick exit parameter setting menu if pressed.
⌛ Auto/Increase Pressing this button will place the module into its auto mode, and genset is controlled by remote start signals. In settings menu, moves cursor up and increases the set value.
| Start/Decrease Pressing this button will start the genset. In settings menu, moves cursor down and decreases the set value.
▼ Page Down Using this button, you can scroll pages of the LCD monitor; enter settings menu if held and pressed over 2s; move cursor and confirm setting information in parameter setting menu.

4.3 LCD Icons

Icon Definition Icon Definition
Genset start indicationFLFuel Level Indication
Boot time is counting (reaching crank disconnect condition)L1Generator Voltage Indication
Emergency Stop AlarmDCBattery Voltage Indication
Over Speed/Over Frequency AlarmkPaOil Pressure Unit
Under Speed/Under Frequency AlarmACurrent With Load Unit
High Temp. AlarmHHours Count
Low Fuel LevelHzFrequency Unit
Auxiliary AlarmºCTemperature Unit
Low Oil PressurerpmSpeed Unite (revolutions per minute)
Fail to startkWActive Power Unit
Fail to stopVVoltage Unit
Voltage Abnormal%Percentage
Over Voltage
Under Voltage
Over Current With Load

5. Maintenance

To ensure optimal performance and longevity of your SmartGen HGM1790N Genset Controller, regular maintenance is recommended.

  • Keep Clean: Regularly clean the controller's surface and ensure no dust or debris accumulates, especially around buttons and the display.
  • Check Connections: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to erratic behavior or system failure.
  • Parameter Review: Review and adjust parameters as needed using the front panel or the PC software via the USB port. Parameters are saved in internal FLASH storage and will not be lost during power off.
  • Sensor Calibration: If applicable, ensure all connected sensors (temperature, pressure, fuel level) are calibrated according to their respective manufacturer's guidelines to ensure accurate readings.

6. Troubleshooting

The HGM1790N controller is equipped with genset fault protection and display functions to assist in troubleshooting. When an issue arises, observe the indicator lights and LCD icons for diagnostic information.

  • Alarm Indicators: If the alarm indicator is blinking, refer to the LCD icons and their definitions (Section 4.3) to identify the specific fault (e.g., Emergency Stop, Over Speed, High Temp, Low Oil Pressure).
  • No Display/Power: Check the DC power supply connections (8-35V) to ensure they are secure and providing the correct voltage.
  • Incorrect Readings: Verify that all sensors are correctly wired and functioning. Check sensor compatibility and calibration.
  • Genset Fails to Start/Stop: Review the crank disconnect conditions and ensure all fixed and configurable relay outputs are correctly wired and configured.
  • Parameter Issues: If parameters are not behaving as expected, reconnect to the PC software via USB and re-verify all settings.

For complex issues or persistent problems, consult the detailed technical documentation or contact customer support.

7. User Tips

  • PC Software: The PC software for parameter adjustment is generally user-friendly, making configuration straightforward. Utilize it for precise control and detailed monitoring.
  • Understanding Features: Familiarize yourself with the controller's capabilities, including its alternator frequency (50/60Hz), USB programmable interface, LCD display with backlight, 5 relay outputs, DC supply (8-35V), English operation panel, 1 digital input, 1 analogue input, 1P2W AC system, and compact dimensions (95x86x46.5mm).
  • Sensor Configuration: Take advantage of the user-defined sensor compatibility to integrate various temperature, pressure, and fuel level sensors as needed for your specific genset setup.

8. Warranty and Support

Specific warranty information for the SmartGen HGM1790N Genset Controller is not provided in this manual. Please refer to your purchase documentation or contact the seller directly for details regarding warranty coverage and technical support.

For any technical assistance, troubleshooting guidance beyond this manual, or inquiries about replacement parts, please reach out to the MENGINEER Parts Store or your authorized distributor.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.