GEYA GYL9 B Type RCCB

Contents

GEYA GYL9 Type B RCD Din Rail Earth Leakage Current Breaker Instruction Manual

Model: GYL9 B Type RCCB

1. Product Overview

The GEYA GYL9 Type B Residual Current Device (RCD) is designed to detect a wide range of earth leakage currents, offering enhanced protection against electrical hazards. Unlike standard AC type RCDs, Type B RCCBs can detect high frequency AC and pure DC earth leakage currents, significantly reducing the risk of fire and electrocution through automatic disconnection of the electrical supply.

1.1 Key Functions

  • Controls electric circuits.
  • Protects individuals against indirect contacts and provides additional protection against direct contacts.
  • Safeguards installations against fire hazards caused by insulation faults.

1.2 Application Examples

  • EV & PV installations
  • Frequency converters
  • UPS installations
  • High-frequency power converters
  • Building site power supply cabinets
Front view of the GYL9 Type B RCD

Figure 1: Front view of the GYL9 Type B RCD

Detailed markings on the GYL9 Type B RCD

Figure 2: Detailed markings on the GYL9 Type B RCD

2. Specifications

2.1 Electrical Features

Table of Electrical and Installation Specifications

Table 1: Electrical and Installation Specifications

  • Standard: IEC/EN 61008-1, IEC/EN 62423
  • Type (waveform of earth leakage sensed): B
  • Rated Current (In): 16A, 25A, 40A, 63A (also 100A variants may exist)
  • Poles: 2P, 4P
  • Rated Voltage (Ue): 2P:230V~, 4P:400V~ (AC220/400V)
  • Insulation Voltage (Ui): 500V
  • Rated Sensitivity (IΔn): 0.03A (30mA), 0.1A (100mA), 0.3A (300mA)
  • Rated Residual Making and Breaking Capacity (IΔm): 500 (In=25-40A), 630 (In=63A)
  • Short-Circuit Current (Inc=IΔc): 6KA (with SCPD fuse 10000A)
  • Rated Impulse Withstand Voltage (1.2/50)Uimp: 6000V
  • Dielectric Test Voltage at Ind. Freq. for 1min: 2.5kV
  • Electrical Life and Mechanical Life: 4000
  • Pollution Degree: 2
  • Rated Frequency: 50/60Hz
  • Certification: CE

2.2 Residual Current Waveform Detection

Table for detecting type and classification of residual current waveform

Table 2: Detection of Residual Current Waveform Types

3. Installation and Setup

3.1 Mounting

  • The device is designed for DIN rail mounting (EN 60715, 35mm) using a fast clip device.
  • Ensure the mounting location is stable and free from excessive vibration.

3.2 Wiring Connections

  • Connection Type: Cable/U-type busbar/Pin-type busbar.
  • Incoming Method: From top.
  • Terminal Size (top/bottom for cable): 35mm², 18-3.
  • Tightening Torque: 22.
Table for nominal section area of copper wire based on rated current

Table 3: Nominal Section Area of Copper Wire

3.3 Dimensions

Overall and Mounting Dimensioned Chart

Figure 3: Overall and Mounting Dimensioned Chart (2P and 4P versions)

4. Operation

  • The GYL9 Type B RCD ensures instantaneous tripping for sinusoidal AC residual currents, pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents, and smooth direct residual currents, whether applied suddenly or increasing slowly.
  • The tripping sensitivity is 30mA, providing additional protection against direct contact.
  • The device features a 'Test Monthly' button on the front panel. This button should be pressed regularly to ensure the RCD is functioning correctly.
  • A fault current indicator (NO) is present to signal when a fault has occurred.

5. Maintenance

  • Monthly Test: Press the 'Test Monthly' button on the device to verify its operational integrity. If the RCD does not trip, it should be replaced immediately.
  • Regular Inspection: Periodically inspect the device for any visible damage, loose connections, or signs of overheating.
  • Cleaning: Ensure the device is kept clean and free from dust and debris to prevent malfunction.

6. Troubleshooting

  • Device Not Tripping: If the RCD does not trip when the 'Test Monthly' button is pressed, or if a fault is detected but the device fails to trip, immediately disconnect power to the circuit and have the device inspected or replaced by a qualified electrician.
  • False Tripping: If the RCD trips without an apparent fault, check for overloaded circuits, faulty appliances, or insulation degradation in the wiring.
  • Incompatibility with DC Systems: It is critical to note that GYL9-B leakage circuit breakers cannot be used in pure DC power systems. They are designed for AC systems that may have DC components in their leakage currents.
Diagram showing typical application with frequency converter

Figure 4: Typical Application Diagram (Note: GYL9-B cannot be used in pure DC power systems)

7. User Tips

  • Environmental Protection: For installations in environments requiring additional sealing, such as in Belgium for head differential applications, consider using appropriate caps or enclosures to seal the device.
  • Certification Requirements: Always verify that the product meets specific regional certifications (e.g., Swiss certification like CH or 'S') if your installation requires them.

8. Warranty and Support

For further assistance, technical support, or warranty claims, please contact GEYA Electricals Store using the information below:

  • Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
  • Telephone: 0086-577-62926966, 0086-13567770207
  • Website: www.geya.net
  • Email: sale@cngeya.com

A detailed user manual in PDF format is also available for download: User Manual (PDF)

GEYA Contact Information

Figure 5: GEYA Contact Information

9. Company Overview

GEYA Electric, established in 2007, is a private enterprise specializing in the research, development, production, sales, and service of low-voltage electrical appliances and automation control products. The company is located in Wenzhou City, China, and adheres to principles of top quality and constant innovation.

Video 1: GEYA Company Overview and Manufacturing Process

GEYA Company Certifications

Figure 6: GEYA Company Certifications (CCC, CE, CB, SAA, SEMKO, TUV, Rosh)