1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the EARU EAPDX series Din Rail Adjustable Over/Under Voltage and Over Current Protective Relay with kWh Energy Meter. For optimal performance and safety, please read this manual thoroughly before using the device and keep it for future reference.
The EARU EAPDX series is designed to protect electrical circuits and equipment from damage due to voltage fluctuations (over/under voltage) and excessive current (over current). Some models also include a kWh energy meter for monitoring power consumption.
2. Important Safety Instructions
WARNING:
- This product does not feature an explosion-proof structure and must not be used in flammable environments, such as those containing flammable gases, liquids, or explosives.
GENERAL SAFETY INFORMATION:
- Please use this product in accordance with the instructions in this manual.
- Do not disassemble this product by yourself.
- Pay attention to the rated voltage for use.
- Installation should only be performed by qualified personnel.
3. Product Overview
The EARU EAPDX series offers various models with different functionalities and current ratings. All models are designed for Din Rail mounting and provide clear digital displays for monitoring electrical parameters.
Figure 1: Overview of EARU EAPDX Product Styles
The product automatically detects over-voltage, under-voltage, and over-current conditions. When the voltage or current exceeds the set limits, the device will automatically disconnect the load side power supply. Once the line voltage/current returns to normal, it will automatically shut down and restore power supply after a set delay.
Figure 2: Automatic Detection and Power Restoration
4. Specifications
Figure 3: Product Dimensions and General Parameters
4.1 General Specifications
| Parameter | Value |
|---|---|
| Rated Supply Voltage | 220V |
| Operating Frequency | 50/60Hz |
| Altitude | ≤2000m |
| Humidity | ≤50% at 40°C (Without Condensation) |
| Output Contact | 1NO |
| Insulation Voltage | 400V |
| Operating Temperature | -50°C - 55°C |
| Voltage Range | 12-250V AC |
| Certification | CE |
| Display Type | Analog-Digital |
| Accuracy Class | ±1 |
4.2 Model-Specific Protection Ranges
Figure 4: Model-Specific Protection Ranges
| Feature | EAPDX-40 / EAPDX-40-RG | EAPDX-63 / EAPDX-63-RG | EAPDX-63VAE-RGB |
|---|---|---|---|
| Over Current Protection Range | 1-40A | 1-63A | 1-63A (Adjustable) |
| Over Voltage Protection Range | 240~300V | 240~300V | 230~300V |
| Under Voltage Protection Range | 140~200V | 140~200V | 80~210V |
| Start/Reset Delay | 1s~300s | 1s~300s | 1s~600s |
| Display Parameter | Voltage, Current | Voltage, Current | Voltage, Current, kWh |
5. Installation
The device is designed for Din Rail mounting. Ensure the power supply is disconnected before installation.
5.1 Wiring Connections
Connect the input (IN) terminals to the main power supply (L for Live, N for Neutral) and the output (OUT) terminals to the load. Ensure correct polarity and secure connections.
Figure 5: Wiring Diagram for EAPDX-63VAE-RGB
Figure 6: Wiring Diagram for EAPDX-40/63 and EAPDX-40-RG/63-RG
Note: The device is single-phase. For three-phase systems, three separate units are required, one for each phase.
6. Operating Instructions
The device features a digital display and control buttons for setting protection parameters. The display shows real-time voltage, current, and for some models, kWh consumption.
Video 1: Product demonstration and basic operation.
6.1 Function Setting (EAPDX-63VAE-RGB)
Figure 7: EAPDX-63VAE-RGB Function Setting
To enter the setting state, press and hold the "SET" button for more than 3 seconds. Use the UP and DOWN arrow buttons to adjust values. The parameters include:
- PE (Power-on delay time): 1s-600s
- rE (Protection recovery delay): 1s-600s
- oU (Over-voltage protection setting): 230V-300V
- oUr (Over-voltage recovery setting): 225V-295V
- UU (Under-voltage protection setting): 80V-210V
- UUr (Under-voltage recovery setting): 85V-215V
- oLE (Over-current protection value): 1-63A
- oLt (Over-current action time): 0.1s-10s
- oLC (Over-current continuous times): 0-20
- CAL (Calibration Voltage Value): -9.9V-9.9V
- CAd (Current Calibration): -9.9A-9.9A
- PC (Power range setting): 1-999
- CLP (Reset mode): CLP 000 (Reset mode), CLP 009 (Reset power level), CLP 009 (Restore Factory Settings)
The device displays Voltage (V), Current (A), and kWh consumption. The rightmost button is for Power On/Off.
6.2 Function Setting (EAPDX-40/63, EAPDX-40-RG/63-RG)
Figure 8: EAPDX-40/63, EAPDX-40-RG/63-RG Function Setting
To enter the setting state, press and hold the "SET" button for more than 3 seconds. Use the UP and DOWN arrow buttons to adjust values. The parameters include:
- Display voltage: Shows current voltage.
- P-1 (Overvoltage setting): 240-300V (OFF option available)
- P-2 (Undervoltage setting): 140-200V (OFF option available)
- P-3 (Overcurrent setting): 1A-40A/63A/80A (adjustable)
- P-4 (Reset/start delay): 1s-300s
- P-5 (Relay recovery delay): 1s-300s
- P-6 (Overcurrent Recovery Delay): 1s-300s
The device displays Voltage and Current. The rightmost button is for Power On/Off.
6.3 Saving Settings
Settings are generally saved automatically after adjustment. In case of power loss, the device retains its last configured settings. To restore factory settings, refer to the CLP 009 option in the EAPDX-63VAE-RGB model's function settings.
7. Maintenance
- Keep the device clean and free from dust.
- Ensure proper ventilation around the device.
- Do not expose the device to excessive moisture or extreme temperatures outside its operating range.
- Regularly check wiring connections for tightness and signs of wear.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Device does not power on. | No input power; incorrect wiring. | Check main power supply. Verify IN/OUT wiring connections. |
| No output voltage to load. | Device in protection mode (over/under voltage, over current); manual shutdown. | Check display for protection indicators. Ensure input voltage/current is within limits. Press the power button to turn on if manually shut off. |
| Incorrect amperage readings. | Calibration needed; internal fault. | Perform current calibration (CAd setting for EAPDX-63VAE-RGB). If issue persists, contact support. |
| Device trips frequently. | Protection settings too sensitive; unstable power supply; excessive load. | Adjust over/under voltage and over current settings to appropriate levels. Check power supply stability and load requirements. |
| Settings reset after power loss. | (Rare) Internal memory issue. | Settings should be retained. If not, ensure proper operation and consider factory reset or contacting support. |
9. User Tips
- Calibration: If you suspect inaccurate readings, use the calibration functions (CAL for voltage, CAd for current) to fine-tune the device.
- Current Rating: When choosing a model, it's often recommended to select a device with a slightly higher current rating (e.g., 63A if your main input is 25A) to allow for flexibility in setting protection limits.
- Automatic Reconnection: The device is designed to automatically reconnect after a fault clears and the set delay time passes. This feature is crucial for maintaining continuous power supply.
- Zero Line Protection: While the device primarily switches the phase line, it is designed to protect against issues like neutral wire breaks by monitoring voltage.
- Installation Environment: Install the device in a standard electrical enclosure. Avoid installing it in environments with flammable materials or excessive heat.
10. Warranty and Support
For detailed warranty information and technical support, please refer to the official EARU documentation or contact your vendor. A user manual in PDF format is available for download:
Please ensure you have your product model number (e.g., EAPDX-40, EAPDX-63VAE-RGB) ready when seeking support.