1. General Information
The GEYA GRV8-02 is a voltage monitoring device designed to protect electrical equipment and motors from damage due to abnormal voltage conditions. It provides comprehensive protection against both over-voltage and under-voltage scenarios.
Applications:
- Protection of electrical equipment and motors from over-voltage and under-voltage.
- Normal/emergency power supply switching.
Function Features:
- Controls its own supply voltage (True RMS measurement).
- User may select operation mode through knob.
- Voltage measurement accuracy <1%.
- Relay status is indicated by LED.
- 1-MODULE, DIN rail mounting.
Model GRV8-02:
This specific model, GRV8-02, offers combined over-voltage and under-voltage protection. For applications requiring separate over-voltage or under-voltage monitoring, please refer to the GRV8-01 model.

2. Safety Information
Please read and understand all safety instructions before installation and operation to prevent injury or damage to the device and connected equipment.
- Installation: This product must be installed by qualified electricians. All electrical connections must comply with the appropriate local and international safety standards.
- Voltage: The device is designed for low voltage applications, typically below 50Vac or 75Vdc, as per EU LVD Voltage directives.
- Disposal: All electrical waste should be disposed of in compliance with current WEEE (Waste Electrical and Electronic Equipment) regulations.
3. Setup
3.1. Mounting
The GEYA GRV8-02 is designed for easy installation on a standard DIN rail (EN/IEC 60715).
3.2. Wiring Diagram
Ensure correct wiring according to the diagram below. Incorrect wiring can lead to malfunction or damage.

- Supply/Monitoring Terminals: A1 and A2
- Output Contact Terminals (1SPDT): 11, 12, 14
3.3. Cable Connection
- Max. Cable Size: Solid wire max. 1x2.5 mm² or 2x1.5 mm²; with sleeve max. 1x2.5 mm² (AWG 12).
- Tightening Torque: Ensure terminal screws are tightened to 0.8 Nm.
3.4. Panel Controls
The front panel features several controls and indicators for configuration and status monitoring:


- Un (Green LED): Supply Indication. Illuminates when power is supplied to the device.
- R (Red LED): Relay Status Indication. Illuminates when the output relay is active.
- U> Knob: Overvoltage threshold setting. Adjust to set the upper voltage limit.
- U< Knob: Undervoltage threshold setting. Adjust to set the lower voltage limit.
- H Knob: Hysteresis setting. For GRV8-02, this is fixed at 3%.
- T Knob: Adjustable Time Delay (0.1s-10s). Sets the delay before tripping or resetting.
- AC/DC Switch: Selects between AC or DC operation mode.
4. Operation
4.1. Power On
Upon applying power to terminals A1-A2, the green 'Un' LED will illuminate, indicating the device is powered. There is a run-up delay of 0.5 seconds before monitoring begins.
4.2. Setting Protection Parameters
- Select Power Source: Use the AC/DC switch to match your supply voltage type.
- Set Over-voltage Threshold (U>): Rotate the 'U>' knob to the desired over-voltage trip level.
- Set Under-voltage Threshold (U<): Rotate the 'U<' knob to the desired under-voltage trip level.
- Set Time Delay (T): Adjust the 'T' knob to set the desired time delay (0.1s-10s). This delay prevents nuisance tripping from momentary voltage fluctuations.
4.3. Relay Response
- Over-voltage Trip: If the monitored voltage exceeds the 'U>' threshold for the set time delay, the relay will trip, and the red 'R' LED will change state (e.g., turn off if normally on, or turn on if normally off).
- Under-voltage Trip: If the monitored voltage drops below the 'U<' threshold for the set time delay, the relay will trip, and the red 'R' LED will change state.
- Automatic Reset: The GRV8-02 features an automatic reset function with a reset time of 1000ms. Once the voltage returns to the safe operating range (considering the 3% fixed hysteresis), the relay will automatically reset after this delay.
4.4. Operation Demonstration Video
Watch this video for a visual demonstration of the over-voltage and under-voltage trip conditions and the relay's response.
5. Technical Specifications
The following table details the technical parameters for the GRV8-01 and GRV8-02 models.

| Parameter | Specification (GRV8-02) |
|---|---|
| Function | Monitoring voltage |
| Supply terminals | A1-A2 |
| Rated supply voltage | DC12V, AC/DC24-48V, AC/DC110-240V, AC220V |
| Rated supply frequency | 45Hz-65Hz, 0 |
| Hysteresis | 3% fixed |
| Supply indication | Green LED |
| Time delay | Adjustable 0.1s-10s, 10% |
| Measurement error | ≤1% |
| Run up delay at power up | 0.5s time delay |
| Knob setting accuracy | 10% of scale value |
| Reset time | 1000ms |
| Temperature coefficient | 0.05% /℃, at=20℃ (0.05%℉, at=68℉) |
| Output | 1×SPDT |
| Current rating | 10A/AC1 |
| Switching voltage | 250VAC/24VDC |
| Min. breaking capacity DC | 500mW |
| Output indication | Red LED |
| Mechanical life | 1×107 |
| Electrical life (AC1) | 1×105 |
| Operating temperature | -20℃ to +55℃ (-4℉ to 131℉) |
| Storage temperature | -35℃ to +75℃ (-22℉ to 158℉) |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP40 for front panel/IP20 terminals |
| Operating position | Any |
| Overvoltage category | III. |
| Pollution degree | 2 |
| Max. cable size (mm²) | Solid wire max. 1x2.5 or 2x1.5 / with sleeve max. 1x2.5 (AWG 12) |
| Dimensions | 90×18×64mm |
| Weight | 59g |
| Standards | EN 60255-1, IEC60947-5-1 |
6. Troubleshooting
6.1. LEDs Flashing (Un and R simultaneously)
If both the green 'Un' LED and the red 'R' LED are flashing simultaneously, this indicates a setting error. For the GRV8-02, this typically occurs if the overvoltage threshold (U>) is set to be less than or equal to the undervoltage threshold (U<).
- Solution: Correct the voltage threshold settings to ensure U> is always greater than U<. After adjusting, power cycle the device to resume normal operation. In this error state, the output relay will be disconnected.
6.2. Relay Not Tripping or Resetting as Expected
- Check Threshold Settings: Verify that the 'U>' and 'U<' knobs are set to appropriate voltage levels for your application.
- Verify Time Delay: Ensure the 'T' knob is set to the desired time delay. The relay will only trip or reset after this delay has elapsed.
- Understand Hysteresis: Remember that the GRV8-02 has a fixed 3% hysteresis. The voltage must return to a level 3% within the safe operating range before the relay will reset.
- Confirm Power Supply: Ensure the power supply connected to A1-A2 is stable and within the rated voltage range for your specific GRV8-02 model.
6.3. No Power Indication (Green Un LED off)
- Check Connections: Verify that the power supply connections to terminals A1-A2 are secure and correct.
- Power Source: Ensure the power source itself is active and providing the correct voltage.
7. User Tips
- Coil Voltage Awareness: Depending on the specific model variant, the internal relay coil might be powered by 24V. Always double-check the rated supply voltage of your GRV8-02 unit before making any connections to avoid damage.
- Automatic Recovery: The GRV8-02 is designed for automatic recovery. If a voltage anomaly (over or under) causes a trip, the relay will automatically reset after a 1000ms delay once the voltage returns to the safe operating range (considering the 3% hysteresis).
- 220V Operation: The GRV8-02 is available in an AC220V variant, providing reliable over-voltage and under-voltage protection for 220V AC systems. Ensure you select the correct model for your specific supply voltage.
- Detailed Manual: For more in-depth information, including detailed function diagrams and specific application examples, please refer to the official user manual PDF available from the manufacturer.
8. Warranty & Support
8.1. Certifications
The GEYA GRV8-02 Voltage Monitor Device is compliant with international safety and environmental standards, holding CE, RoHS, and CB certifications.
8.2. Manufacturer Information
GEYA ELECTRICAL CO.,LTD
Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
Mobile: 0086-13567770207
E-mail: sale@cngeya.com
Website: www.geya.net