1. Introduction
Thank you for choosing CHFRPU Insulated Ferrule Terminals. These terminals are designed to provide a secure and reliable connection for electrical wires, enhancing safety and performance in various applications. This manual provides essential information for the proper use, installation, and maintenance of your ferrule terminals.
2. Safety Information
- Always disconnect power before working on electrical circuits.
- Use appropriate personal protective equipment (PPE) such as safety glasses and insulated gloves.
- Ensure the correct size ferrule is used for the wire gauge to achieve a proper crimp.
- Use a dedicated crimping tool designed for insulated ferrule terminals.
- Do not use damaged or altered terminals.
- This product is designed for low voltage applications (below 50Vac or 75Vdc).
3. Product Overview
CHFRPU Insulated Ferrule Terminals are tubular crimp terminals consisting of a metallic tube (brass, electro-plated tin) and an insulating sleeve (PVC/Nylon). They are used to terminate stranded wires, preventing fraying and ensuring a robust connection when inserted into terminal blocks or other connectors.

The terminals are available in various colors and sizes, corresponding to different wire gauges (A.W.G) and cable cross-sections (mm²).
3.1 Raw Materials


4. Specifications
4.1 General Specifications
| Attribute | Value |
|---|---|
| Product Name | Insulated Cord End Terminal |
| Item No. (Models) | E0508/E7508/E1008/E1508/E2508/E4009/E6012 |
| Type | Crimp Terminal, Tubular |
| Material | Brass |
| Plating | Electro-plated tin |
| Insulating Material | PVC, Nylon |
| Max Voltage | 150°C UI=300V |
| EU LVD Voltage | Low voltage: Below 50Vac or 75Vdc |
| A.W.G Range | 22-10 |
| Cable Size Range | 0.5mm²~6.0mm² |
| Certification | CE |
| Wireless Functionality | No |
| Battery Included | No |
| High-concerned chemical | None |
| Is Customized | Yes |
| Origin | Mainland China |
4.2 Dimensional Specifications

| Model | Dimension (mm) | Applicable Cable (mm²) | A.W.G | ||||
|---|---|---|---|---|---|---|---|
| F | L | W | D | d | |||
| E0508 | 8.0 | 14.0 | 2.6 | 1.3 | 1.0 | 0.5 | #22 |
| E0512 | 12.0 | 18.0 | 2.6 | 1.3 | 1.0 | 0.5 | #22 |
| E7508 | 8.0 | 14.3 | 2.8 | 1.5 | 1.2 | 0.75 | #20 |
| E7512 | 12.0 | 18.3 | 2.8 | 1.5 | 1.2 | 0.75 | #20 |
| E1008 | 8.0 | 14.3 | 3.0 | 1.7 | 1.4 | 1.0 | #18 |
| E1012 | 12.0 | 18.3 | 3.0 | 1.7 | 1.4 | 1.0 | #18 |
| E1508 | 8.0 | 14.3 | 3.5 | 2.0 | 1.7 | 1.5 | #16 |
| E1512 | 12.0 | 18.3 | 3.5 | 2.0 | 1.7 | 1.5 | #16 |
| E2508 | 8.0 | 15.4 | 4.0 | 2.6 | 2.3 | 2.5 | #14 |
| E2512 | 12.0 | 19.4 | 4.0 | 2.6 | 2.3 | 2.5 | #14 |
| E4009 | 9.0 | 16.4 | 4.5 | 3.2 | 2.8 | 4.0 | #12 |
| E4012 | 12.0 | 19.4 | 4.5 | 3.2 | 2.8 | 4.0 | #12 |
| E6010 | 10.0 | 18.5 | 6.0 | 3.9 | 3.5 | 6.0 | #10 |
| E6012 | 12.0 | 20.5 | 6.0 | 3.9 | 3.5 | 6.0 | #10 |
5. Setup and Installation
Follow these steps to properly install an insulated ferrule terminal:
- Select the Correct Ferrule: Choose a ferrule that matches the wire gauge (A.W.G or mm²) of your conductor. The insulation color often indicates the wire size.
- Strip the Wire: Carefully strip the insulation from the end of the wire, exposing the bare conductor. The length of the stripped wire should match the metal tube length (F dimension) of the ferrule.
- Insert the Wire: Twist the strands of the bare wire together to prevent fraying. Insert the twisted wire completely into the metal tube of the ferrule until the insulation meets the plastic sleeve.
- Crimp the Ferrule: Place the ferrule (with the wire inserted) into the appropriate crimping die of a dedicated ferrule crimping tool. Ensure the tool is set to the correct size for the ferrule.
- Perform the Crimp: Squeeze the crimping tool handles firmly until the crimp cycle is complete. A proper crimp will securely fasten the wire within the ferrule without damaging the insulation.
- Verify Connection: Gently tug on the wire to ensure it is securely held by the ferrule. The crimped connection should be tight and the wire should not pull out.
6. Operating Instructions
Once the ferrule terminal is properly crimped onto the wire, it is ready for connection:
- Insert the ferrule-terminated wire into the appropriate terminal block, screw terminal, or other connector.
- Ensure the ferrule is fully seated within the connector.
- Tighten the screw or engage the clamping mechanism of the connector to secure the ferrule. Do not overtighten, as this can damage the ferrule or the connector.
- Verify the connection is secure and there is no exposed bare wire.
7. Maintenance
- Store unused ferrules in a dry environment to prevent corrosion of the metallic parts.
- Keep terminals away from direct sunlight and extreme temperatures to preserve the integrity of the PVC/Nylon insulation.
- Regularly inspect crimped connections for any signs of loosening, corrosion, or damage. Re-terminate if necessary.
8. Troubleshooting
- Wire pulls out of ferrule after crimping:
- This indicates an improper crimp. Ensure the correct ferrule size is used for the wire gauge and that the crimping tool is properly adjusted and fully cycled. The wire should be fully inserted into the ferrule before crimping.
- Ferrule does not fit into the terminal block:
- Verify that the ferrule size (especially the metal tube diameter) is compatible with the terminal block opening. Ensure the crimp is not deformed or too wide.
- Insulation is damaged during crimping:
- Check if the wire was stripped too long or if the crimping tool is misaligned or set to an incorrect size. The crimp should only compress the metal tube, not the insulation.
9. User Tips
- Color Coding: Utilize the different insulation colors to easily identify wire gauges in complex wiring setups.
- Material Choice: The terminals are made of brass with electro-plated tin. For specific applications requiring different conductivity or corrosion resistance, ensure this material is suitable.
- Check Received Items: Upon receiving your order, verify that the colors and quantities match your expectations, as occasional discrepancies may occur.
- Bulk Orders: If you require specific quantities or color/size combinations not readily available, contact the seller directly for custom order inquiries.
10. Warranty and Support
For any questions, technical assistance, or warranty claims, please contact the CHFRPU Official Store directly through the platform where the purchase was made. Provide your order details and a clear description of the issue for prompt support.
11. Disposal Information
When the product reaches the end of its life, please dispose of it responsibly according to local regulations for electronic and electrical components. Do not dispose of with general household waste.