GEYA GRL8 Level Control Relay

Contents

GEYA GRL8 Water Level Control Relay Instruction Manual

Model: GRL8 Series

Brand: GEYA

1. Product Overview

The GEYA GRL8 Water Level Control Relay is designed for precise monitoring and control of liquid levels in various applications such as wells, basins, reservoirs, and tanks. This versatile device ensures reliable operation of pumps and other systems based on predefined water levels, offering both 1-level and 2-level control modes.

2. Key Features

  • Designed for monitoring liquid levels in wells, basins, reservoirs, and tanks.
  • Offers two control configurations: 2-level control mode and 1-level control mode.
  • Selectable function for PUMP UP or PUMP DOWN operations.
  • Adjustable time delay on the output (0.1-10s).
  • Adjustable sensitivity via a potentiometer (5-100KΩ).
  • Galvanically separated supply voltage: AC/DC 24-240V.
  • Relay status indicated by LED indicators.
  • 1-MODULE, DIN rail mounting for easy installation.

3. Model Information

The GRL8 series includes different models to suit various control needs:

  • GRL8-01: Designed for 2-level control mode.
  • GRL8-02: Designed for 2-level or 1-level control mode, with additional features for pump control.
GRL8-01 Level Control Relay with Stainless Steel Sensors
Figure 1: GRL8-01 Level Control Relay with Stainless Steel Sensors (Blue Wire 1.5m, Red Wire 3.0m, White Wire 3.5m)
GRL8-02 Level Control Relay with Stainless Steel Sensors
Figure 2: GRL8-02 Level Control Relay with Stainless Steel Sensors (Blue Wire 1.5m, Red Wire 3.0m, White Wire 3.5m)

4. Technical Specifications

Parameter GRL8-01 GRL8-02
Function2 level control mode2 or 1 level control mode
Supply terminalsA1-A2
Voltage rangeAC/DC 24-240V (50-60Hz)
Inputmax. 2VA
Supply voltage tolerance-15%; +10%
Sensitivity (input resistance)adjustable in range 5 - 100 KΩ
Voltage in electrodesmax. AC 5 V
Current in probeAC <0.1 mA
Time responsemax. 400 ms
Max. capacity length800 m (sensitivity 25kΩ)200 m (sensitivity 100 KΩ)
Max. capacity of probe cable400 nF (sensitivity 25kΩ)100 nF (sensitivity 100 KΩ)
Time delay (t)adjustable, 0.1-10 s
Accuracy in setting (mechanical)±10%
Temperature coefficient0.05%/°C at 20°C (0.05%°F at 68°F)
Output1 × SPDT
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Output indicationred LED
Mechanical life1 × 107
Electrical life (AC1)1 × 105
Reset timemax. 200ms
Operating temperature-20°C to +55°C (-4°F to 131°F)
Storage temperature-35°C to +75°C (-22°F to 158°F)
HumidityUp to 95% RH (non-condensing)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP40 for front panel/IP20 terminals
Operating positionany
Overvoltage categoryIII.
Pollution degree2
Max. cable size (mm2)solid wire max. 1×2.5 or 2×1.5 / with sleeve max. 1×2.5 (AWG 12)
Tightening torque0.8Nm
Dimensions90×18×64mm
Weight70g72g
StandardsEN 62055-1

5. Setup and Installation

5.1 Mounting

The GRL8 relay is designed for DIN rail mounting (EN/IEC 60715).

5.2 Wiring Diagrams

Proper wiring is crucial for the safe and correct operation of the GRL8 relay. Refer to the diagrams below for connection details. Ensure all connections comply with local electrical codes and safety standards.

GRL8-01 Panel Diagram
Figure 3: GRL8-01 Panel Diagram (2-level control)
GRL8-02 Panel Diagram
Figure 4: GRL8-02 Panel Diagram (2-level control)
GRL8 Wiring Diagram
Figure 5: GRL8 Wiring Diagram for Level Control

Electrode Connections:

  • Max: Connects to the maximum liquid level sensor.
  • Min: Connects to the minimum liquid level sensor.
  • C: Common electrode.

Output Contact: Terminals 11, 12, 14 (SPDT relay output).

Sensor Cable Lengths: The provided sensors typically come with specific cable lengths: Blue Wire 1.5m, Red Wire 3.0m, White Wire 3.5m. If extending the sensor cables, use good quality, shielded cable to minimize interference and ensure accurate readings.

6. Operating Instructions

6.1 Function Selection (GRL8-02 only)

The GRL8-02 model allows selection between 1-level and 2-level control modes, and PUMP UP or PUMP DOWN functions. Refer to the function diagrams for detailed behavior.

6.2 Time Delay Adjustment

The time delay on the output can be adjusted from 0.1 to 10 seconds using the 'Tt' potentiometer on the front panel. This helps prevent rapid switching due to minor liquid level fluctuations.

6.3 Sensitivity Adjustment

The sensitivity (input resistance) can be adjusted in the range of 5-100 KΩ using the 'Sensitivity' potentiometer. Adjust this based on the conductivity of the liquid being monitored.

6.4 LED Indicators

The relay features LED indicators to show its operational status:

  • Un (Green LED): Indicates power supply status.
  • R (Red LED): Indicates relay output status.
  • Additional LEDs (UP, DOWN, PUMP, Tt) may be present depending on the model and function, indicating specific operational states or time delay activation.
GRL8-01 and GRL8-02 Front Panel Controls
Figure 6: GRL8-01 and GRL8-02 Front Panel Controls

7. Functions Diagram

The following diagrams illustrate the operational logic for different control modes:

GRL8-01 and GRL8-02 Function Diagrams
Figure 7: GRL8-01 (2-level control) and GRL8-02 (2-level control pump up/down, 1-level control pump up/down) Function Diagrams

8. Maintenance

The GRL8 Water Level Control Relay is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended:

  • Ensure all electrical connections are secure and free from corrosion.
  • Keep the device clean and free from dust and debris.
  • Inspect sensor electrodes for buildup or damage, especially in harsh environments. Clean as necessary.

Disposal of Electrical Waste:

All electrical waste should be disposed of in compliance with current WEEE regulations to protect the environment.

9. Troubleshooting

  • Relay not activating/deactivating as expected: Check sensor connections for proper placement and continuity. Verify the sensitivity setting is appropriate for the liquid. Ensure the selected control mode (PUMP UP/PUMP DOWN) matches the desired operation.
  • Pump not turning on/off: Confirm the relay output contacts are correctly wired to the pump's control circuit. For high-power pumps (e.g., 750W or three-phase motors), an external contactor is typically required, with the GRL8 relay controlling the contactor's coil.
  • Unexpected behavior after power outage: The device is designed to resume operation according to its configured mode once power is restored. If not, check power supply and settings.
  • Inaccurate level detection: Check for sensor contamination or damage. Ensure sensor cables are not excessively long or of poor quality, which can affect signal integrity.

10. User Tips

  • Sensor Cable Extension: If you need to extend the sensor cables, it is generally possible up to 30 meters. Always use high-quality, appropriately sized, and preferably shielded cables to maintain signal integrity and prevent interference.
  • Pump Control: The GRL8 is ideal for automating pump operations. Ensure the pump's power requirements do not exceed the relay's contact rating (10A/AC1). For larger loads, use an intermediate contactor.
  • Hot Water Applications: The relay's operating temperature range is -20°C to +55°C. For applications involving hot water, ensure the ambient temperature around the relay and the water temperature do not exceed these limits.
  • Galvanic Isolation: The device features galvanically separated supply voltage, enhancing safety. However, always ensure proper grounding and installation by a qualified professional.

11. Certifications

The GEYA GRL8 Water Level Control Relay is certified to meet international standards, including:

  • CE: Conforms to European Union health, safety, and environmental protection standards.
  • RoHS: Compliant with the Restriction of Hazardous Substances Directive.
  • Additional certifications may include CCC, CB, SAA, SEMKO, TUV.

12. Dimensions

GRL8 Dimensions Diagram
Figure 8: GRL8 Dimensions (90mm x 18mm x 64mm)

13. Safety and Caution

IMPORTANT SAFETY INSTRUCTIONS:

  • The products must be installed by qualified electricians.
  • All electrical connections of the product shall comply with the appropriate safety standards and local electrical codes.
  • Before any installation, maintenance, or troubleshooting, ensure the power supply to the device is completely disconnected.
  • Do not operate the device outside its specified voltage, current, and temperature ranges.
  • Avoid direct contact with live electrical parts.

14. Warranty and Support

GEYA products are manufactured to high-quality standards. For any warranty claims or technical support, please contact GEYA Electrical Co., Ltd. directly.

Contact Information:

A detailed user manual in PDF format is also available for download from the manufacturer's website or via the provided link: User Manual (PDF).

15. Manufacturer Video

Watch the official manufacturer video for an overview of GEYA's production process and product range:

Video: GEYA Company Introduction and Product Overview

© 2024 GEYA Electrical Co., Ltd. All rights reserved.