1. Introduction
The DATAKOM D300 MK2 is an advanced generator controller designed for comprehensive monitoring and control of generator sets. It offers automatic start/stop functions, protection features, and a user-friendly interface for efficient power management. This manual provides essential information for the safe and effective installation, operation, and maintenance of your D300 MK2 controller.
2. Safety Information
Please read and understand all safety instructions before installing or operating the D300 MK2 controller. Failure to follow these instructions may result in personal injury, equipment damage, or death.
- Installation and servicing should only be performed by qualified personnel.
- Always disconnect power from the generator set and controller before performing any maintenance or wiring.
- Ensure proper grounding to prevent electrical shock.
- Do not operate the controller in wet or explosive environments.
- Verify all wiring connections are secure and correct according to the wiring diagrams.
3. Package Contents
Upon opening the package, please verify that all components are present and undamaged:
- DATAKOM D300 MK2 Generator Controller
- Mounting hardware (screws, clips)
- Connector plugs (pre-installed on controller)
If any items are missing or damaged, please contact your supplier immediately.
4. Product Overview
4.1 Front Panel Layout
The front panel provides the user interface for monitoring and controlling the generator set.

Image: Front view of the D300 MK2 controller, showing display, buttons, and status indicators.
Key elements:
- LCD Display: Shows operational parameters, alarms, and menu options.
- Status Indicators: LEDs for ALARM (red), WARNING (yellow), SERVICE REQUEST (blue).
- Mode Indicators: LEDs for MAINS, LOAD, GENSET.
- Buttons:
- TEST (Yellow Gear Icon): Initiates a generator test run.
- RUN (Green 'I' Icon): Starts the generator in manual mode.
- AUTO (Blue 'A' Icon): Activates automatic operation mode.
- STOP (Red 'O' Icon): Stops the generator.
- PGM (Arrow Buttons): Used for navigating menus and adjusting parameters.
- Light Bulb Icon: Backlight control.
- Mute Icon: Silences audible alarms.
4.2 Rear Connections and Specifications
The rear of the controller features various terminal blocks for power, sensor inputs, and communication.

Image: Rear view of the D300 MK2 controller, detailing terminal blocks for generator, battery, inputs, communication ports (USB, Extension/Comm. Module, CANH, CANL), and electrical specifications.
Key connections:
- BAT+ / BAT-: Battery power input (8 to 36Vdc, 500mA max).
- GEN-C, GEN-L1, GEN-L2, GEN-L3, GEN-N: Generator voltage inputs (300Vac, 0-600Hz).
- I1+, I1-, I2+, I2-, I3+, I3-: Generator current transformer inputs (0.2 to 6.0 Aac).
- MN-L1, MN-L2, MN-L3, MN-N: Mains voltage inputs.
- INT, IN1-IN8: Digital inputs.
- S1-S3, SG: Analog inputs.
- USB Port: For PC connection and programming.
- Extension/Comm. Module: Port for optional plug-in communication modules.
- CANH, CANL: CAN bus communication.
For detailed wiring diagrams, please refer to the full technical documentation provided by DATAKOM.
4.3 Product Overview Video
Video: A brief visual overview of the D300 MK2 generator controller, highlighting its physical features and connections.
5. Setup
5.1 Mounting
The D300 MK2 controller is designed for panel mounting. Ensure the mounting location is free from excessive vibration, moisture, and extreme temperatures. Cut a rectangular opening in the panel according to the controller's dimensions and secure it using the provided mounting clips or screws.
5.2 Wiring
Carefully connect all necessary wires to the terminal blocks on the rear of the controller. Refer to the detailed wiring diagrams in the full technical manual for specific connections for your generator set configuration. Pay close attention to:
- Battery Connections: Ensure correct polarity for BAT+ and BAT-.
- Generator Voltage/Current: Connect generator output and current transformers accurately.
- Mains Voltage: If using for automatic transfer switch (ATS) applications, connect mains voltage.
- Inputs/Outputs: Connect all required sensors and control outputs (e.g., fuel solenoid, starter motor).
- Communication: Connect USB for PC configuration or optional communication modules.
Double-check all connections before applying power.
5.3 Initial Power-up
Once all wiring is complete and verified, apply battery power to the controller. The display should illuminate, and the controller will perform a self-test. Follow any on-screen prompts for initial setup or calibration.
6. Operating Instructions
6.1 Operating Modes
- STOP Mode (Red 'O' button): The generator is stopped and will not start automatically. All outputs are de-energized.
- MANUAL Mode (Green 'I' button): Pressing this button will start the generator. The generator will run until the STOP button is pressed.
- AUTO Mode (Blue 'A' button): In this mode, the controller monitors the mains supply. If the mains fail, the controller will automatically start the generator. When mains power is restored, the controller will transfer the load back to the mains and stop the generator after a cool-down period.
- TEST Mode (Yellow Gear Icon button): Initiates a test run of the generator. The specific behavior (with or without load transfer) depends on the controller's configuration.
6.2 Navigating Menus
Use the PGM (arrow) buttons to navigate through the display menus to view parameters, alarms, and adjust settings. Consult the full technical manual for a detailed menu structure and parameter descriptions.
6.3 Alarm and Warning Indications
The ALARM and WARNING LEDs will illuminate to indicate fault conditions. The LCD display will provide detailed information about the specific alarm or warning. Address any indicated issues promptly to ensure safe and reliable operation.
7. Maintenance
Regular maintenance ensures the longevity and reliable operation of your D300 MK2 controller.
- Cleaning: Keep the controller's front panel clean and free of dust. Use a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Connection Checks: Periodically inspect all wiring connections for tightness and corrosion. Re-tighten as necessary.
- Software Updates: Check the DATAKOM website for any available firmware updates for your controller model.
- Battery Check: Ensure the generator's battery, which powers the controller, is in good condition and fully charged.
8. Troubleshooting
This section covers common issues you might encounter. For complex problems, consult a qualified technician.
| Problem | Possible Cause | Solution |
|---|---|---|
| Controller display is blank | No power supply to the controller. | Check battery connections (BAT+ / BAT-) and battery voltage. Ensure fuses are intact. |
| Generator does not start in AUTO mode | Mains power is present; AUTO mode not selected; fuel or battery issues. | Verify mains failure condition; ensure AUTO mode is active; check fuel level, battery charge, and starter motor. |
| Alarm LED is on | Fault condition detected (e.g., low oil pressure, high engine temperature). | Check the LCD display for the specific alarm message. Address the underlying fault. |
| Buttons are unresponsive | Controller frozen or internal fault. | Try power cycling the controller (disconnect and reconnect battery power). If issue persists, contact support. |
9. Specifications
| Feature | Specification |
|---|---|
| Operating Voltage | 8 to 36 Vdc |
| Current Consumption | 500mA max |
| Generator Voltage Input | 300Vac, 0-600 Hz |
| Generator Current Input | 0.2 to 6.0 Aac |
| Package Dimensions (L x W x H) | 25 cm x 15 cm x 10 cm |
| Package Weight | 0.6 kg |
| Origin | TR (Turkey) |
10. User Tips
- Regular Checks: Periodically check the generator's fuel, oil, and coolant levels, especially if the controller is set to AUTO mode for emergency power.
- Software Configuration: For advanced settings and customization, connect the controller to a PC using the USB port and the appropriate DATAKOM software. This allows for fine-tuning parameters to match your specific generator and application.
- Alarm Logging: The controller typically logs alarm events. Reviewing these logs can help diagnose intermittent issues or understand the cause of a generator shutdown.