1. Introduction
This manual provides essential information for the safe and efficient use of the Kinco GL070 and GL070E Human Machine Interface (HMI) Touch Screens. These devices are designed for industrial control applications, offering a 7-inch display with 800*480 resolution. The Kinco GREEN series HMI products utilize ARM Cortex-A7 architecture industrial-grade processors, ensuring long-term reliability and improved performance for green and efficient operation.

2. Safety Information
Please read and understand all safety instructions before installing, operating, or maintaining the device. Failure to follow these instructions may result in personal injury or equipment damage.
- Ensure the power supply matches the device's specifications (DC24V).
- Disconnect power before performing any wiring or maintenance.
- Do not expose the device to excessive moisture, dust, or extreme temperatures.
- Only qualified personnel should install and service this equipment.
- Ground the device properly using the FG (Frame Ground) terminal.
3. Product Overview
The Kinco GL070 and GL070E models are 7-inch Human Machine Interfaces designed for robust industrial applications. Key features include:
- 7-inch TFT Display with 800*480 Resolution
- 32-bit 800MHz RISC Processor
- 128M FLASH + 64M DDR2 Memory
- 1 USB Host port for expandable memory or peripheral connection
- 512KB + RTC for Recipe memory and Real-Time Clock
- Multiple COM ports: RS232/RS485/RS422
- GL070E model includes an Ethernet port for network connectivity.
3.1. Component Identification


The back panel of the HMI units features the following connections:
- DC24V, GND, FG: Power input terminals (24V DC) and Frame Ground.
- USB HOST: For connecting USB devices like flash drives for data transfer or external peripherals.
- USB SLAVE: For connecting the HMI to a PC for programming and data exchange.
- Ethernet (GL070E only): RJ45 port for network communication.
- COM0/COM2: Serial communication ports (RS232/RS485/RS422).
- COM1/CAN: Serial communication port (RS232/RS485/RS422) or CAN bus interface.
- LINE OUT: Audio output.
4. Specifications
| Attribute | Value |
|---|---|
| Brand Name | TECNR |
| Model Number | Kinco GL070 GL070E |
| Origin | Mainland China |
| Certification | CE |
| Display | 7" TFT |
| Resolution | 800*480 |
| Processor | 32-bit 800MHz RISC |
| Memory | 128M FLASH + 64M DDR2 |
| Expandable memory | 1 USB Host |
| Recipe memory RTC | 512KB + RTC |
| COM port | RS232/RS485/RS422 |
5. Setup
5.1. Mounting
The HMI unit is designed for panel mounting. Ensure adequate space for ventilation and access to ports. Refer to the product's dimensional drawings for precise cutout requirements.
5.2. Wiring
- Power Connection: Connect a stable 24V DC power supply to the DC24V and GND terminals. Ensure correct polarity. Connect the FG (Frame Ground) terminal to a reliable earth ground.
- USB Connections:
- USB HOST: Use this port to connect USB flash drives for project transfer, data logging, or other USB peripherals.
- USB SLAVE: Connect this port to your PC using a standard USB cable for programming the HMI.
- Serial Communication (COM Ports): Connect your PLC or other serial devices to the COM0/COM2 or COM1/CAN ports as required. These ports support RS232, RS485, and RS422 protocols. Refer to your PLC's documentation for specific wiring diagrams.
- Ethernet Connection (GL070E only): For the GL070E model, connect an Ethernet cable to the RJ45 port for network communication with PLCs or other network devices.
- Audio Output (LINE OUT): If audio functionality is required, connect an audio device to the LINE OUT port.
6. Operating Instructions
6.1. Powering On
After all connections are securely made, apply 24V DC power to the HMI. The device will boot up and display the configured project.
6.2. Programming Software
The Kinco HMI units are programmed using dedicated Kinco software, such as Kinco DTools. This software allows you to design the user interface, configure communication protocols, and define logic for your industrial application.
- Download the appropriate Kinco programming software from the official Kinco website.
- Install the software on your PC.
- Connect the HMI to your PC via the USB SLAVE port.
- Use the software to create or modify your HMI project.
- Transfer the compiled project to the HMI unit.
6.3. Communication with PLCs
The HMI supports various communication protocols, including Modbus RTU and Modbus TCP (for GL070E). Ensure your HMI project is configured with the correct protocol and parameters to communicate with your specific PLC model (e.g., Siemens S7-200, Siemens S7-1200, Delta DVP-MC).
7. Maintenance
- Cleaning: Use a soft, dry cloth to clean the screen and casing. Do not use abrasive cleaners or solvents.
- Firmware Updates: Periodically check the Kinco website for firmware updates to ensure optimal performance and access to new features.
- Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent damage.
- Cable Integrity: Regularly inspect all connected cables for wear or damage and replace them if necessary.
8. Troubleshooting
- No Power: Check the 24V DC power supply and ensure all power connections are secure and correctly polarized.
- Display Not Working: Verify power, check for loose connections, or try restarting the device.
- Communication Issues with PLC:
- Ensure the correct communication protocol (e.g., Modbus RTU, Modbus TCP) is selected in the HMI project and matches the PLC.
- Verify serial port settings (baud rate, data bits, parity, stop bits) or Ethernet IP settings.
- Check physical cable connections.
- Confirm PLC is powered on and communicating.
- Touch Screen Unresponsive: Perform a calibration if available in the system settings. If the issue persists, contact support.
- Project Transfer Failure: Ensure the USB SLAVE cable is properly connected and the correct drivers are installed on your PC. Check for software errors during compilation or transfer.
9. User Tips
- Software Compatibility: The Kinco HMI is programmed using Kinco's proprietary software (e.g., Kinco DTools). It is not compatible with third-party software like WinCC Flexible or TIA Portal.
- PLC Connectivity: When connecting to a PLC, ensure you select the correct HMI model and PLC family within the Kinco programming software. The HMI is known to work well with Delta DVP-MC PLCs via Modbus TCP.
- Modbus Support: Both GL070 and GL070E models support Modbus RTU. The GL070E model additionally supports Modbus TCP via its Ethernet port.
- Font Support: The HMI supports various fonts, including Russian fonts, which can be configured within the programming software.
- Email Alerts: The HMI can be configured to send email alerts, a useful feature for remote monitoring and notifications.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your vendor or the official Kinco support channels. Keep your purchase records handy when seeking support.