GEYA GYM9+RD MCB Auto Recloser Instruction Manual

Model: GYM9+RD

Brand: GEYA

1. Introduction

1.1 General Applications

The GEYA GYM9+RD miniature circuit breaker with remote control is designed for a wide range of electrical applications. It can be used in:

  • Power grid terminal lines, such as meter boxes.
  • New energy circuit management, including PV solar control boxes.
  • Smart electricity and smart home systems.
  • New energy vehicle charging piles.

1.2 Function Features

This device offers advanced features for enhanced safety and convenience:

  • Can be matched with a circuit breaker or leakage protection switch.
  • Automatically recloses when the MCB/RCCB/RCBO trips unexpectedly, eliminating the need for manual closing and reducing maintenance costs.
  • Timely eliminates faults to improve efficiency.
  • Features 3 reclosing attempts; continuous closing failure within 15 minutes triggers an alarm via auxiliary contact.
  • Equipped with a manual/automatic selector switch.
  • Includes mechanical/electronic double locking function.
  • The shaft transmission mode ensures more stable and reliable operation.
  • Compatible with other accessories.
  • Work status is indicated by an LED.
  • Complies with IEC/EN60898-1 standards.
  • Bilateral busbar wiring capabilities for wider use.
  • Maximum connecting ability of 25mm², with a wiring torque of 3N*m, suitable for various installing equipment.

1.3 Product Overview

The GEYA GYM9+RD is a miniature circuit breaker with remote control and automatic reclose functionality. It is primarily used for protection against overload and short circuit in AC 50Hz/60Hz systems, with rated voltages of 230V/400V and rated currents from 6A to 63A. It can also be used for non-frequent on-and-off switching operations under normal circumstances.

GEYA MCB with Autoreclose Device (various poles)
Figure 1: GEYA GYM9+RD MCB with Autoreclose Device (various pole configurations)

2. Specifications

2.1 Model and Connotation

The model designation GRD9L-R indicates the following:

  • GRD9L Series: Base product series.
  • R: Auto Reclosing + AUX (Auxiliary contact).
  • Rated control supply voltage: D12 (DC12V), D48 (DC24~48V), A220 (AC220V).

When ordering, the matching MCB/RCCB/RCBO specification and model should be indicated. For example: GRD9L-R + GYM9 2P C40 or GRD9L-R + GYL9 2P 40A 30M.

2.2 Technical Parameters

Technical parametersGRD9L-R
Control modeAuto Reclosing
Supply terminalsA1-A2
Voltage rangeDC12V, DC24V-48V
Supply voltage tolerance-10%; +10%
Power inputDC max.1W(standby) max.20W(action)
Voltage rangeAC 220V (50-60Hz)
Supply voltage tolerance-10%; +10%
Power inputAC max.1VA(standby) max.20VA(action)
Supply indicationred LED
Action time≤1s
Auto reclosing times3
Auto reclosing interval time10s-60s-300s
Reset the closing timesNo trip or manual reset within 15 minutes after successful closing
Mechanical life10000
Electrical lifeRefer to MCB / RCCB / RCBO catalogue
Operating temperature-20°C to +55°C (-4°F to 131°F)
Storage temperature-35°C to +75°C (-22°F to 158°F)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP20
Operating positionany
Overvoltage categoryIII.
Pollution degree2
Max. cable size (mm²)solid wire max.1×2.5 or 2×1.5 / with sleeve max.1×2.5 (AWG 12)
Dimensions82×18×78mm
Weight80g

2.3 Dimensions

Overall and mounting dimensioned chart for GEYA MCB with Autoreclose Device
Figure 2: Overall and mounting dimensions for various pole configurations of the GEYA MCB with Autoreclose Device. Shows dimensions for 1P, 2P, 3P, and 4P units, including width, height, and depth.

3. Installation

3.1 Cooperating with RCCB/MCB

The auto reclose device is designed to integrate seamlessly with Residual Current Circuit Breakers (RCCB) or Miniature Circuit Breakers (MCB).

Diagram showing how to install the auto reclose device with an RCCB
Figure 3: Installation diagram for cooperating with an RCCB. The auto reclose device (left) connects to the RCCB (right) via a linking mechanism.
Diagram showing how to install the auto reclose device with an MCB
Figure 4: Installation diagram for cooperating with an MCB. The auto reclose device (left) connects to the MCB (right) via a linking mechanism.

3.2 Accessories Installation

Additional accessories can be installed to enhance functionality.

Diagram showing how to install accessories with the auto reclose device
Figure 5: Diagram illustrating the installation of accessories (ARD) with the MCB/RCCB unit.

3.3 Closing Lock

The device features a closing lock mechanism for safety during circuit checks.

Diagram showing the closing lock mechanism on the auto reclose device
Figure 6: Detailed view of the closing lock mechanism. When activated, the MCB/RCCB cannot be closed, preventing accidental re-energization during maintenance.

Note: When checking the circuit, the RCCB/MCB cannot close when the lock function is activated.

4. Operation

4.1 Mode Selection

The device features a selector switch for different operational modes:

  • AUTO mode: The auto reclosing function is enabled.
  • MANU mode: The auto reclosing function is disabled. In this mode, the MCB/RCCB/RCBO can only be opened and closed manually.

4.2 Power-On Behavior

Upon power-on, the green indicator will flash for 2 seconds to allow the power supply to stabilize. After stabilization, the green indicator light will remain on. If the MCB/RCCB/RCBO fails to trip, the red indicator light will be on. During the auto reclosing delay, the red indicator will flash. After the delay, the device will automatically switch on, and the green light will be on.

Video 1: GEYA Company Overview. This video showcases the manufacturing process and quality control of GEYA electrical products, including automated assembly lines and testing procedures.

5. Wiring Diagrams

5.1 GRD9M-C, GRD9M-S, GRD9M-R Wiring

Wiring Diagram for GRD9M-C, GRD9M-S, GRD9M-R models
Figure 7: Wiring diagrams for different control modes: GRD9M-C (Switch input control), GRD9M-S (RS485 control), and GRD9M-R (Autoreclose). Each diagram shows the AC220V input and control terminals (A1, A2, OFF, ON, RS485, COM, NC, AUX).

5.2 Application Example

Application example wiring diagram for GEYA MCB with Autoreclose Device
Figure 8: Example application wiring for single-phase (L, N) and three-phase (L1, L2, L3, N) systems using the GEYA auto reclose device with MCBs. Includes an alarm lamp connection.

6. Functions Diagram

Functions Diagram for GRD9M-C, GRD9M-S, GRD9M-R models
Figure 9: Timing diagrams illustrating the operational sequences for GRD9M-C, GRD9M-S, and GRD9M-R models, showing LED status, trip times, and MCB (Auto) states. Note: The number of reclosures can be cleared by placing the panel switch in manual mode or re-energizing it.

Note: If the closing times and delay time need to be customized, please contact GEYA company.

7. Troubleshooting

Refer to the table below for common faults and their resolutions:

Fault descriptionResolvent
Unable to close or open.
  1. Confirm whether the power supply voltage is normal.
  2. Confirm whether the working mode is set in AUTO mode.
  3. Confirm the buckle of the electric operation mechanism and MCB/RCCB/RCBO.
Trip immediately after closing.
  1. Check the circuit to confirm whether there is overload / short circuit / leakage fault at the lower end of MCB / RCCB / RCBO.
  2. Check whether the circuit breaker is damaged or not, and whether it is slipped.

8. User Tips

  • The product is generally well-finished and detailed, suggesting good quality.
  • Ensure the power supply voltage is normal before operation to prevent issues.
  • Always verify the working mode (AUTO/MANU) is correctly set according to your needs.
  • If the device trips immediately after closing, thoroughly check for overload, short circuit, or leakage faults in the connected circuit.
  • The device supports a wide range of rated currents from 6A to 63A and operates at 50/60Hz.
  • Some models may require an external power input (12V or 220V) for re-initialization or specific control modes.

9. Warranty and Support

For any technical assistance, warranty claims, or further support, please contact GEYA customer service. For detailed item guides and documents, please refer to the official user manual PDF available from the seller.

10. Safety and Disposal

10.1 Safety Precautions

Caution: The products must be installed by qualified electricians. All and any electrical connections of the time relay shall comply with the appropriate safety standards.

10.2 Disposal of Electrical Waste

All electrical waste should be disposed of in compliance with current WEEE regulations to protect the environment.