1. Product Overview
The GEYA GRB8-01/02 Din Rail Twilight Switch is a photoelectric timer light sensor relay designed for automatic lighting control based on ambient light intensity. It is ideal for switching street illumination, garden lights, advertisements, and shop windows.
Key features include:
- Controls lights based on ambient light intensity.
- Monitors ambient light via an external sensor.
- Output switches according to a set light level.
- Universal supply voltage: AC 110V-240V.
- Output: 1SPST 16A/AC1.
- Status indication: Green LED for supply, Red LED for relay status.
- Compact 1-MODULE design for DIN rail mounting.
Image: GEYA GRB8-01 and GRB8-02 Twilight Switches with key features and application overview.
Model Differences:
- GRB8-01: Illumination Range 1-100Lx.
- GRB8-02: Illumination Range 1-1000Lx & 10-10000Lx, includes Zero-Crossing Protection for enhanced performance.
2. Safety Information
Caution: The products must be installed by qualified electricians. All electrical connections of the product shall comply with the appropriate safety standards.
Ensure the power supply is disconnected before any installation or maintenance work to prevent electric shock.
3. Installation and Wiring
The GRB8-01/02 is designed for DIN rail mounting. Follow the wiring diagrams carefully for proper installation.
Video: Demonstration of wiring and basic operation for the GRB8-01 twilight switch. Shows connecting to power, accessing load, and connecting the light detection sensor.
3.1. GRB8-01 Wiring Diagram
Image: Wiring diagram for GRB8-01, showing connections for L-N supply, sensor, and load. Includes a functions diagram and panel layout.
3.2. GRB8-02 Wiring Diagram
Image: Wiring diagram for GRB8-02, showing connections for L-N supply, sensor, and load. Includes a functions diagram and panel layout.
3.3. Sensor Installation
The external photosensor (PLS-01 or PLS-02) is crucial for light detection. Ensure it is mounted in a location that accurately reflects the ambient light conditions you wish to monitor, away from direct artificial light sources that could interfere with its operation.
Image: Dimensions and mounting options for PLS-01 and PLS-02 sensors, showing panel and snap fixation methods.
The sensor cable length is typically 20cm. It can be extended if needed, but ensure proper wiring and insulation for any extensions.
4. Operating Instructions
The twilight switch has different operating modes and adjustable light sensitivity.
4.1. Operating Modes
The device features an ON-AUTO-OFF switch:
- ON: The load is continuously powered, regardless of ambient light. (Normally open state)
- AUTO: The device operates automatically based on ambient light intensity detected by the sensor. The load will turn ON when light falls below the set threshold and turn OFF when light rises above it, after a 2-minute delay.
- OFF: The load is continuously unpowered. (Normally closed state)
4.2. Adjusting Light Sensitivity (Lx)
In AUTO mode, you can adjust the light sensitivity (Lx) using the knob on the device. This sets the ambient light threshold at which the switch will activate or deactivate the load.
- GRB8-01: Adjustment range 1-100Lx.
- GRB8-02: Adjustment range 1-1000Lx & 10-10000Lx.
When the external light reaches your adjusted value, the relay will switch. There is an inherent action delay time of 2 minutes to prevent flickering due to transient light changes (e.g., car headlights, lightning).
Image: Panel diagram of GRB8-01 showing the ON-AUTO-OFF switch and the Lx adjustment knob.
Image: Panel diagram of GRB8-02 showing the ON-AUTO-OFF switch, Lx adjustment knob, and x1/x10 function switch.
4.3. Contact 3 Functionality (Additional Control)
Contact 3 on the device is designed for connecting an external button. When this button is pressed and connected to neutral (zero), it can temporarily override the automatic function, typically to turn off the light while the button is engaged.
5. Specifications
Image: Detailed technical parameters table for the GRB8-01 model.
Image: Detailed technical parameters table for the GRB8-02 model.
| Parameter | GRB8-01 | GRB8-02 |
|---|---|---|
| Function | Twilight switch | Twilight switch |
| Supply terminals | L-N | L-N |
| Rated supply voltage | AC 110V-240V | AC 110V-240V |
| Rated supply frequency | 50/60Hz | 50/60Hz |
| Burden | max. 2VA | max. 2VA |
| Supply voltage tolerance | -15%; +10% | -15%; +10% |
| Illumination range | 1-100Lx | 1-1000Lx, 10-10000Lx |
| Function (mode) | ON-AUTO-OFF | ON-x1-x10-OFF |
| Supply indication | Green LED | Green LED |
| Tolerance sensor | ±35% | ±35% |
| Delay time | 2min | 2min |
| Output | 1xSPST | 1xSPST |
| Current rating | 16A/AC1 | 16A/AC1 |
| Switching voltage | 250VAC/24VDC | 250VAC/24VDC |
| Min. breaking capacity DC | 500mW | 500mW |
| Output indication | Red LED | Red LED |
| Mechanical life | 1x107 | 1x107 |
| Electrical life (AC1) | 1x105 | 1x105 |
| Operating temperature | -20°C to +55°C (-4°F to 131°F) | -20°C to +55°C (-4°F to 131°F) |
| Storage temperature | -35°C to +75°C (-22°F to 158°F) | -35°C to +75°C (-22°F to 158°F) |
| Humidity | Up to 95% RH (non-condensing) | Up to 95% RH (non-condensing) |
| Mounting/DIN rail | Din rail EN/IEC 60715 | Din rail EN/IEC 60715 |
| Protection degree | IP40 for front panel/IP20 terminals | IP40 for front panel/IP20 terminals |
| Operating position | any | any |
| Overvoltage category | III | III |
| Pollution degree | 2 | 2 |
| Max. cable size (mm²) | solid wire max. 1x2.5 or 2x1.5 / with sleeve max. 1x2.5 (AWG 12) | solid wire max. 1x2.5 or 2x1.5 / with sleeve max. 1x2.5 (AWG 12) |
| Tightening torque | 0.8Nm | 0.8Nm |
| Dimensions | 90x18x64mm | 90x18x64mm |
| Weight | 65g | 65g |
| Standards | EN 60255-1 | EN 60255-1 |
| Sensor Type | PLS-01R-0.2m | PLS-02R-0.2m |
| Special Function | None | Zero-Crossing Protection |
5.1. Types of Lamps and Max Load
| Lamp Type | Max Load (W) |
|---|---|
| Incandescent | 2000W |
| Halogen lamp | 2000W |
| Fluorescent, corrected, in series | 1000W |
| Fluorescent, corrected, in parallel (125uF) | 900W |
| Compact fluorescent | 400W |
| LED lamp (>2W) | 300W |
6. Maintenance
The GEYA GRB8-01/02 Twilight Switch is designed for reliable, maintenance-free operation under normal conditions. Periodically check wiring connections for tightness and ensure the sensor lens is clean and free from obstructions to maintain accurate light detection.
7. Troubleshooting
- Light not turning ON/OFF automatically:
- Check if the switch is set to 'AUTO' mode.
- Verify the sensor is correctly connected and positioned to detect ambient light accurately. Ensure it's not obstructed or exposed to artificial light sources.
- Adjust the light sensitivity (Lx knob) to a suitable threshold.
- Remember there is a 2-minute delay before the relay switches after the light threshold is crossed.
- Red light flashing, but lights not turning ON in AUTO mode:
- This might indicate an issue with the load connection or the relay itself. Check the load wiring and ensure the load is within the specified wattage limits.
- If the device works in 'ON' mode but not 'AUTO', the issue is likely with the sensor or its connection.
- Difficulty regulating time:
- The delay time for switching (2 minutes) is fixed and cannot be adjusted. The 'Lx' knob adjusts light sensitivity, not the delay time.
- General non-functionality:
- Ensure the power supply (AC 110V-240V) is correctly connected and active.
- Verify all wiring connections are secure and correct according to the diagrams.
8. User Tips
- Read the Instructions: Always refer to the instruction manual and wiring diagrams for correct installation and operation.
- High Wattage Loads: For lamps exceeding the specified maximum load (e.g., 2000W), it is recommended to use an additional contactor with the twilight switch to handle the higher current safely.
- Sensor Placement: Position the external sensor carefully to avoid interference from temporary light sources (like car headlights) or permanent artificial lights, which could cause unintended switching.
- Sensor Cable Extension: The sensor cable can be extended if necessary. Ensure any extensions are properly insulated and wired to maintain signal integrity.
- Contact 3 Usage: Utilize contact 3 for an external button if you require temporary manual override (e.g., to turn off lights while the button is pressed).
9. Frequently Asked Questions (FAQ)
- Q: Does this switch detect presence?
A: No, this device is a twilight switch that operates solely based on ambient light intensity. It does not have presence detection capabilities. The contact closes when it gets dark and opens when it gets light. - Q: Can this switch be used for a water heater?
A: While technically possible to switch a load, this device is specifically designed for lighting control based on ambient light. For water heaters, a dedicated timer or thermostat control is usually more appropriate and efficient. Ensure the water heater's power requirements do not exceed the switch's maximum load. - Q: Can this switch be used to turn on lights at dawn?
A: No, a twilight switch is designed to turn lights ON when it gets dark (dusk) and turn them OFF when it gets light (dawn). If you need lights to turn ON at dawn, you would typically use a different type of timer or a switch with inverse functionality. - Q: What is the purpose of contact 3?
A: Contact 3 is for connecting an external button to provide a temporary manual override. When the button is pressed and connected to neutral, it can temporarily turn off the light.
10. Warranty and Support
For any technical assistance, product inquiries, or support, please contact GEYA directly:
- Email: sale@cngeya.com
- Website: www.geya.net
Specific warranty details may vary. Please refer to your purchase documentation or contact GEYA support for more information.