TOMZN TOVPD1-60

Contents

TOMZN TOVPD1-60 Automatic Reconnect Over/Under Voltage Protective Device

Model: TOVPD1-60 | Brand: TOMZN

1. Safety Information

WARNING:

To avoid danger of suffocation, keep any plastic packaging away from babies and children. Do not use this bag in cribs, beds, carriages, or playpens. This bag is not a toy.

  • Installation and operation of this device should only be performed by a qualified electrical professional.
  • Do not place the device near flammable materials.
  • Ensure adequate ventilation during operation to prevent overheating.
  • Disconnect the device from power and store it properly when not in use for extended periods.
  • Always follow local electrical codes and regulations.

2. Product Overview

The TOMZN TOVPD1-60 is an automatic recovery voltage protective device designed to safeguard electrical circuits and connected appliances from damage caused by over-voltage and under-voltage conditions. When the voltage in the circuit exceeds or falls below predefined safe limits, the device will automatically cut off the power. Once the voltage returns to a normal range, the device will automatically reconnect the circuit after a recovery delay, ensuring continuous protection and minimizing manual intervention.

This device features LED indicators for power status, under-voltage protection, and over-voltage protection, providing clear visual feedback on its operational state.

Front view of TOMZN TOVPD1-60 device with labels and internal diagram

Figure 1: Front view of the TOVPD1-60 device showing terminals and indicators.

3. Specifications

Feature Specification
Brand Name TOMZN
Model Number TOVPD1-60
Type Voltage relay, Automatic Recovery Voltage Protective Device
Rated Voltage (Un) AC 230V, 50/60Hz
Rated Current (Ie) 40A
Over-voltage Protection Value 270V ± 5V
Under-voltage Protection Value 170V ± 5V
Off-time (Response Time) ≤ 1 second
Recovery Time ≤ 60 seconds
EU LVD Voltage High voltage: Above 50Vac or 75Vdc
Certification CE
Is Smart Device No
Origin Mainland China
Dimensions (W x H x D) 36mm x 82mm x 67mm
Weight 0.16 kg
Dimensions of TOMZN TOVPD1-60 device

Figure 2: Dimensions of the TOVPD1-60 device.

4. Installation

IMPORTANT: Installation must be performed by a qualified electrical professional to ensure safety and proper functionality.

  1. After receiving the product, visually inspect it for any damage.
  2. Mount the device on a standard DIN rail in your electrical panel.
  3. Connect the equipment in accordance with the wiring diagram specifications provided on the device itself (refer to Figure 3). Ensure all connections are secure and correctly polarized (Neutral and Live).
  4. The device is designed for AC 230V, 50/60Hz systems. Do not connect to systems with different voltage ratings (e.g., 110V).
  5. Ensure adequate space around the device for ventilation.
Wiring diagram for TOMZN TOVPD1-60 device

Figure 3: Wiring diagram and terminal layout. Connect 'IN' to the incoming power supply (N for Neutral, L for Live) and 'OUT' to the protected circuit.

5. Operation

The TOVPD1-60 operates automatically to protect your electrical system. Here's how it works:

  • Power On: Once correctly installed and powered, the green 'Power' LED will illuminate, indicating normal operation.
  • Over-voltage Protection: If the input voltage exceeds 270V ± 5V, the device will detect the over-voltage condition. The 'Over Volt Protection' red LED will light up, and the device will automatically cut off the power to the connected circuit within 1 second.
  • Under-voltage Protection: If the input voltage drops below 170V ± 5V, the device will detect the under-voltage condition. The 'Under Volt Protection' red LED will light up, and the device will automatically cut off the power to the connected circuit within 1 second.
  • Automatic Recovery: After a power cut-off due to over or under-voltage, the device continuously monitors the voltage. Once the voltage returns to the normal operating range (between 170V and 270V), the device will wait for a recovery time of up to 60 seconds to ensure stability, then automatically reconnect the power to the circuit.

6. Maintenance

The TOMZN TOVPD1-60 is designed for minimal maintenance. However, following these guidelines can help ensure its longevity and reliable performance:

  • Ventilation: Ensure that the area around the device remains clear and well-ventilated to prevent heat buildup.
  • Cleaning: Keep the device free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Connection Checks: Periodically, and with power disconnected, check all wiring connections to ensure they remain tight and secure.
  • Storage: If the device is to be stored for an extended period, disconnect it from power and store it in a dry, cool environment.

7. Troubleshooting

Device not powering on (Green Power LED is off):
Check the incoming power supply. Ensure the device is correctly wired and receiving the rated voltage (AC 230V). Verify that all connections are secure.
Device frequently trips (red LEDs illuminate often):
This indicates unstable voltage in your electrical system. While the device protects your appliances, consider investigating the root cause of the voltage fluctuations. Also, ensure the connected load does not exceed the device's 40A current rating, as overloading can cause unexpected behavior or damage.
Device feels hot during operation:
Ensure there is adequate ventilation around the device. Check if the current draw of the connected appliances is within the 40A limit. Persistent overheating may indicate an overload or a fault, and professional inspection is recommended.
Device does not work with 110V supply:
The TOVPD1-60 is specifically designed for AC 230V, 50/60Hz systems. It is not compatible with 110V electrical systems.
Device failed after some time:
If the device ceases to function, it may be due to a fault or prolonged exposure to extreme conditions. Professional diagnosis and replacement may be necessary.

8. User Tips

  • For optimal safety and performance, always have this device installed by a certified electrician.
  • The device's LEDs can be quite bright; this is a characteristic of the product and not a fault.
  • Ensure your electrical system's voltage is generally stable. While the TOVPD1-60 provides protection, frequent tripping due to highly unstable voltage can still impact appliance longevity.
  • The over-voltage and under-voltage protection thresholds (270V ± 5V and 170V ± 5V) are fixed and cannot be adjusted by the user.
  • The device is designed to cut both the live (L) and neutral (N) lines when protection is activated, providing comprehensive circuit isolation.

9. Applicable Regulations and Harmonized Standards

This device complies with the following European Union directives:

  • Low Voltage Directive (LVD) 2014/35/EU
  • Electromagnetic Compatibility (EMC) Directive 2014/30/EU
  • Restriction of the use of certain hazardous substances (RoHS) Directive 2011/65/EU
CE marking indicating compliance with European standards

Figure 4: CE Marking.

10. Warranty and Support

For detailed warranty information, technical support, or service inquiries, please refer to the official TOMZN website or contact your authorized retailer. Keep your purchase receipt as proof of purchase.

A comprehensive user manual in PDF format is also available for download: View User Manual (PDF)

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.