Coolmay CM-6024

Contents

Coolmay CM-6024 Power Supply User Manual

Model: CM-6024 | Brand: Coolmay

1. Introduction

The Coolmay CM-6024 power supply is designed for PLC controllers and HMI panels, providing a dedicated 24V DC output at 2.5A. It incorporates an imported exclusive driver chip and high-precision, heat-resisting electronic components. Utilizing international advanced PWM technology, this power supply offers robust protection against short circuits, overloads, and overvoltage, ensuring stable and reliable operation. It is capable of amplifying and converting output power when connected with various PLCs.

Coolmay CM-6024 Power Supply front view

Figure 1: Coolmay CM-6024 Power Supply

2. Key Features

  • Advanced PWM Technology: Ensures efficient and stable power conversion.
  • Exclusive Driver Chip: Utilizes an imported, high-precision driver chip for optimal performance.
  • Wide Input Voltage Range: Supports 88-264VAC or 125-373VDC, with resilience to 300VAC surge input for 5 seconds.
  • High-Temperature Electrolytic Capacitor: Guarantees enhanced reliability and longevity.
  • Soft Starting Current: Effectively reduces instantaneous voltage surge during startup.
  • Comprehensive Protection: Includes short circuit protection, overload protection, and overvoltage protection.
  • Natural Radiating Heat: Designed for stable and reliable operation without active cooling.
  • Long Lifespan: Rated for up to 100,000 hours in average under room temperature 25°C.
  • Compact Design: Mini and exquisite dimensions of 90*60*32mm.
  • Convenient Installation: Supports DIN-rail mounting (35mm).

3. Technical Specifications

Parameter Value
ModelCM-6024
Input Voltage88-264VAC or 125-373VDC (without damage while standing 300VAC surge input for 5S)
Input Frequency47-63Hz
Output VoltageDC24V
Output Current2.5A
Impulse Current45A/230VAC
Output Accuracy±1%
Output Efficiency0.86
No-load Consumption<0.5W
Overload ProtectionRated output 110%-180%, Hiccups protected mode, automatically recovered once errors are removed.
Overvoltage Protection27.6-32.4V
Short-circuit ProtectionAutomatic protection once there is a short out (LED shut down), automatically recovered once errors are removed.
Insulation ResistanceI/P-O/P:3KVA, I/P-FG:1.5KVA, O/P-FG:0.5KVA, 1min
Operating Temperature-20 ~ +70°C
Operation Humidity20-90%RH (Non-condensing)
Storage Temperature-40 ~ +85°C
Storage Humidity10-95%RH
Safety StandardsCE-EN60950, UL508, UL60950, TUV-60950
Life Time100,000 hours (average, at 25°C room temperature)
InstallationDIN-rail mounting (35mm)
Dimensions90*60*32mm
Wireless FunctionalityNo
Battery IncludedNo
EU LVD VoltageLow voltage: Below 50Vac or 75Vdc
High-concerned chemicalnone
OriginMainland China
Motor CompatibilityStepper Motor

4. Installation

4.1 Mounting

The CM-6024 power supply is designed for DIN-rail mounting (35mm). Ensure the mounting surface is stable and provides adequate ventilation for heat dissipation. Mount the unit vertically for optimal performance.

4.2 Wiring Diagram

Refer to the diagram below for proper wiring connections. Ensure all connections are secure before applying power.

Coolmay CM-6024 Wiring Diagram

Figure 2: CM-6024 Wiring Diagram (Note: This image is a placeholder for the actual wiring diagram from the PDF. Please refer to the original PDF for the precise diagram.)

Wiring Connections:

  • Input (AC220V): Connect the Live (L) and Neutral (N) wires to the corresponding terminals.
  • Ground (GND): Connect the ground wire to the designated ground terminal.
  • Output (DC24V): Connect the positive (+) and negative (-) wires to the DC24V+ and DC24V- terminals respectively.

Always ensure power is disconnected before performing any wiring or installation procedures.

5. Operating Instructions

5.1 Power On/Off

Once properly installed and wired, apply the specified input voltage (88-264VAC or 125-373VDC) to the power supply. The unit will automatically power on and begin providing DC24V output.

5.2 Status Indicators

  • DC ON LED: Illuminates when the DC output is active and within normal operating parameters.
  • ADJ (Adjustment): This potentiometer allows for fine-tuning of the output voltage within a small range, if necessary. Use a small screwdriver to adjust carefully.

6. Maintenance

The CM-6024 power supply is designed for long-term, reliable operation with minimal maintenance. Follow these guidelines to ensure optimal performance and longevity:

  • Cleaning: Periodically clean the exterior of the unit to prevent dust accumulation, which can hinder natural heat dissipation. Use a soft, dry cloth. Do not use liquid cleaners.
  • Ventilation: Ensure that the installation area maintains good airflow and is free from obstructions that could block the unit's ventilation slots.
  • Environmental Conditions: Operate the power supply within the specified operating temperature (-20 ~ +70°C) and humidity (20-90%RH non-condensing) ranges.
  • Connection Checks: Periodically inspect all wiring connections to ensure they remain tight and free from corrosion.

7. Troubleshooting

This section outlines common issues and their potential solutions. The CM-6024 power supply includes built-in protection features that often allow for automatic recovery from faults.

Problem Possible Cause Solution
No DC output / DC ON LED off
  • No input power.
  • Input voltage outside specified range.
  • Short circuit at output.
  • Overload condition.
  • Check input power source and connections.
  • Verify input voltage is 88-264VAC or 125-373VDC.
  • Disconnect load, check for short circuits, then reconnect. The unit should auto-recover.
  • Reduce load, ensure it's within 2.5A. The unit should auto-recover.
Intermittent output / Hiccups mode
  • Overload condition (110%-180% of rated output).
  • Overvoltage condition.
  • Reduce load to below 2.5A. The unit is designed to auto-recover.
  • Check for stable input voltage and proper load.
Output voltage incorrect
  • ADJ potentiometer misadjusted.
  • Faulty load.
  • Adjust the ADJ potentiometer carefully to achieve the desired 24V DC output.
  • Test the load independently to ensure it is not drawing excessive current or causing issues.

If problems persist after attempting these solutions, please contact Coolmay customer support.

8. User Tips

  • For critical applications, consider using a multimeter to verify the output voltage after installation and adjustment.
  • Ensure the DIN-rail mounting is firm to prevent vibrations that could affect connections.
  • Always double-check wiring polarity (+/-) for DC connections to avoid damage to connected devices.

9. Support & Contact

For technical assistance, warranty inquiries, or further information regarding your Coolmay CM-6024 power supply, please contact Coolmay PLC Official Store directly through their official channels.

You can also refer to the official user manual PDF for detailed diagrams and instructions: Coolmay Power Supply User Manual (PDF)

10. About Coolmay

Coolmay is an automation expert specializing in PLC, HMI, and related industrial control products. They emphasize high-precision manufacturing, advanced technology, and comprehensive quality control. The company is committed to providing reliable and efficient automation solutions.

Play video
Watch video online

Video: Coolmay Company Overview - Showcasing their facilities, R&D, and product range.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.