1. Introduction
The HoldPeak HP-4300 is a professional digital earth resistance tester designed for accurate measurement of earth resistance and earth voltage. This instrument is suitable for testing the grounding resistance of various electrical equipment, indoor wiring, and mechanical installations. It also supports measuring soil resistivity and ground voltage.
Key features include data hold, a 1999-count display, manual range selection, automatic power-off for energy saving, an auto backlight for visibility in dark conditions, and an HV (High Voltage) indication lamp.
Figure 1: HoldPeak HP-4300 Digital Earth Resistance Tester and included accessories.
2. Safety Warnings
WARNING: Failure to follow these safety instructions may result in severe injury or death.
- Read and understand the entire instruction manual before use. Keep the manual accessible for future reference.
- Always operate the instrument according to the instructions provided.
- Do not use the instrument if it is damaged, or if any metal parts of the instrument or test leads are exposed.
- Ensure the range switch is set to the correct position before making any measurements.
- Do not measure in environments with flammable gases, as sparks could cause an explosion.
- Avoid connecting test leads or probes to the instrument with wet hands or when the instrument surface is wet.
- Do not input over-range values during testing.
- Do not open the battery cover during measurement.
- Do not switch the range switch when test leads or probes are connected to the object under test.
- Do not install replacement parts or modify the instrument. If the instrument is damaged, return it to the dealer or manufacturer for repair.
- Do not use or store the instrument in direct sunlight, high temperatures, humidity, or wet conditions.
- Do not clean the instrument with abrasives or organic solvents. Use a neutral detergent or a damp cloth.
- Ensure the instrument is dry before storage.
CAUTION: Improper operation may cause personal injury or damage to the instrument.
- Do not mix old and new batteries.
- Pay attention to battery polarity during installation.
3. Instrument Layout
Figure 2: Front panel and terminal layout of the HP-4300.
- LCD display
- HOLD key (Data Hold)
- CDS sensor (for Auto Backlight)
- TEST key (Press to Test)
- Resistance test lamp (LED indicator)
- Function switch (Range Selector)
- Earth electrode (E terminal)
- Current pole (C(H) terminal)
- Electric potential pole (P(S) terminal)
Figure 3: Rear view showing battery compartment and terminal connections.
4. Setup
4.1. Battery Installation
The HP-4300 requires 6 x 1.5V R6P AA (SUM-3) batteries. Batteries are not installed at the time of purchase.
- Ensure the function switch is set to "OFF".
- Remove any connected test leads and probes.
- Unscrew the battery cover on the back of the instrument.
- Insert 6 new 1.5V R6P AA batteries, paying close attention to the correct polarity.
- Replace the battery cover and tighten the screws.
4.2. Checking Battery Voltage
Turn on the instrument. If the battery replacement indicator (✍) is displayed, replace the batteries as described in section 4.1.
4.3. Connecting Test Leads and Auxiliary Grounding Rods
The instrument comes with a set of grounding test leads and auxiliary grounding rods. Ensure all connections are secure to avoid measurement errors.
Figure 4: Standard connection method for earth resistance measurement.
To connect the auxiliary grounding rods:
- Starting from the object under test, insert the auxiliary grounding rods (P and C) into the ground in a straight line, approximately 5 to 10 meters apart.
- Connect the green, yellow, and red test leads from the E, P, and C terminals of the instrument to the object under test, auxiliary grounding rod P, and auxiliary grounding rod C, respectively.
Important:
- Insert the auxiliary grounding rods into moist soil whenever possible. If the soil is dry, rocky, or sandy, moisten the area around the rods with water.
- If measuring on concrete, lay the auxiliary grounding rods flat, moisten them with water, or place a wet cloth underneath them.
- When using the simple test probe (not standard auxiliary rods), short-circuit the P and C terminals.
5. Operating Instructions
5.1. Earth Voltage Measurement
Before measuring earth resistance, it is recommended to check the earth voltage to ensure accuracy.
- With the test leads connected as shown in Figure 4, set the function switch to "EARTH VOLTAGE".
- The display will show the measured earth voltage.
- If the voltage is above 10V, it may cause significant errors in earth resistance measurements. In such cases, turn off the power to the equipment under test and wait for the earth voltage to drop below 10V before proceeding with earth resistance measurement.
- If the display shows "1..." (over-range), immediately stop the measurement. Voltages exceeding 200V can damage the instrument.
5.2. Earth Resistance Measurement (Precision Method)
This method uses the auxiliary grounding rods and the three-terminal measurement technique.
- Ensure the test leads and auxiliary grounding rods are connected as described in section 4.3.
- Set the function switch to the desired resistance range (e.g., 2000Ω).
- Press the "TEST" button. The LED indicator will light up, and the measurement will begin.
- The measured earth resistance value will be displayed on the LCD.
- If the resistance value is too low for the selected range, switch to a lower range (200Ω or 20Ω) sequentially.
- If the display shows "1..." (over-range), it indicates that the auxiliary grounding resistance of rod C is too high, preventing the rated current from flowing. Recheck the connections and the auxiliary grounding resistance.
Figure 5: Measuring earth resistance in an electrical wiring application.
Figure 6: Measuring earth resistance for a generator.
Figure 7: Measuring earth resistance in soil using auxiliary rods.
5.3. Earth Resistance Measurement (Simple Method)
This method does not use auxiliary grounding rods and is suitable when an existing grounding electrode with known low resistance is available (e.g., metal water pipes, commercial power grounding, lightning rods).
- Connect the instrument's E terminal to the object under test.
- Connect the instrument's P and C terminals to the existing low-resistance grounding electrode.
- Set the function switch to the desired resistance range.
- Press the "TEST" button to take a measurement.
- The displayed value (Re) is the sum of the actual earth resistance (Rx) and the resistance of the existing grounding electrode (re): Re = Rx + re.
- If the resistance of the existing grounding electrode (re) is known, the actual earth resistance can be calculated as: Rx = Re - re.
5.4. Data Hold Function
During measurement, press the "HOLD" button to freeze the current reading on the display. The "HOLD" symbol will appear. Press the "HOLD" button again to release the reading and resume live measurement.
5.5. Auto Backlight
The instrument features an automatic backlight function. The CDS sensor detects ambient light levels. In low light conditions, the LCD backlight will automatically turn on for improved readability. When sufficient light is detected, the backlight will turn off.
Figure 8: Backlight function for visibility in dark conditions.
6. Specifications
Figure 9: Detailed technical parameters.
| Measurement Function | Range | Accuracy |
|---|---|---|
| Earth Voltage | 0 ~ 199.9V AC | ±(1.0%rdg + 4dgt) |
| Earth Resistance | 0 ~ 19.99 Ω | ±(2.0%rdg + 0.1Ω) |
| 0 ~ 199.9 Ω | ±(2.0%rdg + 3dgt) (Earth voltage below 10V) | |
| 0 ~ 1999 Ω |
General Specifications:
- Display: 1999 counts
- Range Select: Manual
- Dimensions: 218mm (L) x 122mm (W) x 75mm (H)
- Weight: Approximately 900g
- Operating Temperature: 0℃ ~ 40℃
- Storage Temperature: -10℃ ~ 50℃
- Power Supply: 6 x 1.5V R6P AA (SUM-3) batteries
- Testing Voltage: 200V
- Accuracy Class: Class I
- Overload Protection: Earth voltage AC 300V/minute, Earth resistance E-P, E-C terminals AC 280V/10 seconds
- Insulation Resistance: >5MΩ between circuit and casing at 500V
- Withstand Voltage: AC 3700V/minute between circuit and casing
- Safety Standard: IEC 61010-1 CAT III 300V Pollution Degree 2
- Electromagnetic Compatibility: Wireless frequency electromagnetic field 3V/m: specified accuracy + range 5%
7. Maintenance
- When not in use for a long period, or for storage, remove the batteries to prevent leakage and damage to the instrument.
- Keep the instrument clean. Use a soft, dry cloth for cleaning. If necessary, a slightly damp cloth with a mild detergent can be used. Do not use abrasive cleaners or organic solvents.
- Store the instrument in a dry, cool place, away from direct sunlight, high temperatures, and high humidity.
- Avoid strong vibrations or impacts. The instrument is equipped with a thick protective case for durability.
Figure 10: The instrument's durable protective casing.
8. Troubleshooting
8.1. Power On but No Display ("000")
- Open the battery cover and check if the batteries are installed correctly and if their polarity is correct.
- Ensure the batteries are not depleted. Replace with new batteries if necessary.
8.2. Earth Voltage Measurement Displays "1..." (Over-range)
- This indicates that the input voltage is too high (above 200V). Immediately stop the measurement.
- High voltage can damage the instrument. Identify and eliminate the source of high voltage before re-attempting measurement.
8.3. Earth Resistance Measurement Displays "..." (Over-range)
This usually indicates an issue with the auxiliary grounding resistance or test lead connections.
- For Precision Measurement:
- The auxiliary grounding resistance might be too high, preventing the rated current from flowing. Try relocating the auxiliary grounding rods to a more conductive spot or inserting them deeper into the ground.
- Check the test leads. Short-circuit the C terminal test lead (red) to the auxiliary grounding rod, and moisten the rod with water. If the display shows a value close to "0.00", the instrument is functioning correctly, and the issue is with the auxiliary grounding.
- For Simple Measurement:
- Ensure the P terminal is connected to a reliable low-resistance grounding electrode (e.g., metal water pipe, commercial power grounding).
- Try connecting to a different existing grounding electrode.
8.4. Inaccurate Readings
- Ensure test leads are not tangled or touching each other, as this can cause measurement errors. Separate the test leads during measurement.
- If the auxiliary grounding resistance is too high, it can lead to significant errors. Ensure auxiliary grounding rods P and C are deeply inserted into moist soil and all connections are secure.
- Avoid using the instrument near high-frequency transmitters like mobile phones, as electromagnetic interference can affect readings.
9. User Tips
- Pre-Measurement Check: Always perform an earth voltage check before measuring earth resistance to ensure optimal accuracy.
- Soil Conditions: For best results in earth resistance measurements, ensure the soil around the auxiliary grounding rods is moist. If dry, water the area.
- Cable Management: Keep the test leads untangled and separated during measurements to prevent interference and ensure accurate readings.
- Battery Life: To prolong battery life, always turn the function switch to "OFF" when the instrument is not in use. The auto power-off feature also helps conserve battery.
- Readability: Utilize the auto backlight feature in dimly lit environments for clear readings.
10. Warranty and Support
This instrument is manufactured and tested according to IEC61010 safety standards and shipped in optimal condition. For any issues or support, please contact the manufacturer or your local dealer.
Manufacturer Contact Information:
Company: Zhuhai Jida Huapu Instrument Co., Ltd.Address: Building 4, 301 Tsinghua Science Park, Tangjiawan, High-tech Zone, Zhuhai City, Guangdong Province, China
Phone: +86-756-3374032, 6330399
Email: hp@holdpeak.com
Website: http://www.holdpeak.com
A user manual in PDF format is also available for download: Download User Manual (PDF)