GEYA GRI8-01/02 Current Monitoring Relay

Contents

GEYA GRI8-01/02 Current Monitoring Relay Instruction Manual

Model: GRI8-01/02 | Brand: GEYA

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA GRI8-01 and GRI8-02 Current Monitoring Relays. These devices are designed for reliable current monitoring in various electrical applications.

1.1 Applications

  • Monitoring of heating in rail-switches.
  • Monitoring of heating cables.
  • Monitoring of consumption of one-phase motors.
  • Indicates current flow in electrical circuits.

1.2 Function Features

  • Adjustable delay from 0.5 to 10 seconds to eliminate short current peaks.
  • Flexible current adjustment by potentiometer with a choice of 6 ranges:
    • AC 0.05-0.5A
    • AC 0.1-1A
    • AC 0.2-2A
    • AC 0.5-5A
    • AC 0.8-8A
    • AC 1.6-16A
  • Possible to use for current scanning from a current transformer.
  • Universal supply voltage: AC 24 - 240 V or DC 24 V.
  • Relay status is indicated by an LED.
  • 1-MODULE, designed for DIN rail mounting.
  • Output: 1 SPDT (Single Pole Double Throw) contact, rated 10A/AC1.

2. Model and Connotation

The GRI8 series offers different models based on their monitoring function:

  • GRI8-01: Overcurrent Protection
  • GRI8-02: Undercurrent Protection
  • GRI8-03: Overcurrent or Undercurrent Protection
  • GRI8-04: Overcurrent and Undercurrent Protection (in window mode)

The current range is specified by a design number suffix:

  • 0.5: 0.05-0.5A
  • 1: 0.1-1A
  • 2: 0.2-2A
  • 5: 0.5-5A
  • 8: 0.8-8A
  • 16: 1.6-16A
GRI8 Model and Connotation Diagram
Figure 1: GRI8 Model and Connotation Diagram

3. Technical Specifications

ParameterSpecification
FunctionMonitoring current
Supply terminalsA1-A2
Rated supply voltageAC/DC 24V-240V
Rated supply frequency50/60Hz, 0
Burdenmax 2VA
Supply voltage tolerance-15%; +10%
Current range0.5A, 1A, 2A, 5A, 8A, 16A (specific ranges: 0.05-0.5A, 0.1-1A, 0.2-2A, 0.5-5A, 0.8-8A, 1.6-16A)
Current adjustmentpotentiometer
Time delay (Tt)adjustable 0.1-10 s
Power up delay (Tr)adjustable 0.1-10 s
Supply indicationgreen LED
Setting accuracy10%
Repeat accuracy<1%
Temperature dependency< 0.1 % /°C
Limit values tolerance5% (10% for 0.05-0.5A range)
Hysteresis5%
Temperature coefficient0.05%/°C, at=20°C (0.05%°F, at=68°F)
Output1×SPDT
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Output indicationred LED
Mechanical life1×107
Electrical life (AC1)1×105
Operating temperature-20°C to +55°C (-4°F to 131°F)
Storage temperature-35°C to +75°C (-22°F to 158°F)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP40 for front panel/IP20 terminals
Operating positionany
Overvoltage categoryIII.
Pollution degree2
Dimensions90×18×64mm
Weight69g
StandardsIEC60947-5-1
Tightening torque0.8Nm
Max. permanent current (B1-B2)0.05A-0.5A, 0.1A-1A, 0.2A-2A, 0.5A-5A, 0.8A-8A, 1.6A-16A
Technical Parameters Table
Figure 2: Technical Parameters
Functions Diagram and Dimensions
Figure 3: Functions Diagram and Dimensions (mm)

4. Installation

4.1 Wiring Diagram

The relay is designed for DIN rail mounting. Ensure all electrical connections comply with appropriate safety standards and are performed by qualified electricians.

GRI8 Wiring Diagram
Figure 4: General Wiring Diagram for GRI8 Relays

4.2 Connection Terminals

  • A1-A2: Supply Voltage Terminals
  • B1-B2: Monitoring Current Terminals
  • 11, 12, 14: 1 SPDT Output Contact (11-14 is Normally Open, 11-12 is Normally Closed)
GRI8 Terminal Layout
Figure 5: GRI8 Terminal Layout and Indicators

4.3 Example Wiring Case (GRI8-01 Overcurrent Monitoring)

GRI8-01 Wiring Case
Figure 6: GRI8-01 Overcurrent Monitoring Wiring Example

In the GRI8-01 wiring case, terminals 11-14 are normally open and will close after an overcurrent event. Terminals 11-12 are normally closed and will disconnect after an overcurrent event.

GRI8-01 Monitoring Current Relay Application Example
Figure 7: GRI8-01 Monitoring Current Relay Application Example (e.g., for a cooker)

5. Operation

5.1 Setting Current Range and Threshold

The current monitoring range is selected by a rotary switch on the front panel. The precise current threshold (Imax for overcurrent, Imin for undercurrent, or Iset for combined) is adjusted using a potentiometer within the selected range.

6 Range Current Adjustment Potentiometers
Figure 8: Potentiometer Settings for 6 Current Ranges
GRI8-01 Current Range Potentiometer Settings
Figure 9: Detailed GRI8-01 Current Range Potentiometer Settings

5.2 Setting Time Delays

Two time delays can be adjusted using potentiometers:

  • Tr (Power up delay): Delays the start of monitoring after power-up.
  • Tt (Tripping delay): Delays the relay output action after a current anomaly is detected, helping to eliminate short current peaks.

5.3 Relay Status Indication

  • Green LED: Indicates power supply status.
  • Red LED: Indicates relay output status.

6. Troubleshooting

  • Relay not activating/deactivating as expected: Check the current threshold settings (Imax/Imin/Iset) and ensure they are appropriate for your application. Verify the time delay settings (Tr, Tt) are not preventing immediate action.
  • LEDs flashing (GRI8-04): If using GRI8-04 (Over/Undercurrent in window mode), ensure the set over-current threshold value is larger than the under-current threshold value. If not, the LEDs will flash, and the output relay will be disconnected.
  • Inaccurate delay time: Some users have noted that the delay time for turning off might not be very accurate. If precise timing is critical, consider external timers or further calibration.
  • No power indication: Check the supply voltage connections to A1-A2. Ensure the voltage is within the AC/DC 24V-240V range.
  • No output action: Verify the load connected to the 11, 12, 14 contacts is correctly wired and within the 10A/AC1 rating.

7. Maintenance

  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Inspection: Periodically inspect the wiring connections for tightness and signs of wear or damage.
  • Environmental Conditions: Ensure the operating environment adheres to the specified temperature and humidity ranges to prevent malfunction.
  • Disposal: All electrical waste should be disposed of in compliance with current WEEE regulations.

8. User Tips

  • Pump Dry-Run Protection: This relay is well-suited for pump dry-run protection. Adjust the undercurrent threshold precisely to switch off the pump when the current draw drops below a safe operating level.
  • Precise Adjustment: Take time to precisely adjust the current potentiometers for optimal performance in your specific application.
  • Home Use: For home use, this product offers excellent functionality and value compared to more expensive alternatives.
  • Wiring Diagrams: Always refer to the detailed wiring diagrams provided in this manual and on the device itself for correct installation.

9. Warranty and Support

For warranty information and technical support, please refer to the official GEYA website or contact your local distributor. A comprehensive user manual in PDF format is available for download: User Manual (PDF).

10. Contact Information

GEYA ELECTRICAL CO.,LTD
Add: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
Mobile: 0086-13567770207
E-mail: sale@cngeya.com
Web: www.geya.net

11. Safety and Disposal

11.1 Caution

WARNING: The products must be installed by qualified electricians. All and any electrical connections of the product shall comply with the appropriate safety standards.

11.2 Disposal of Electrical Waste

All electrical waste should be disposed of in compliance with current WEEE regulations.

WEEE Disposal Symbol
Figure 10: WEEE Disposal Symbol