1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA GRI8-01 and GRI8-02 Current Monitoring Relays. These devices are designed for reliable current monitoring in various electrical applications.
1.1 Applications
- Monitoring of heating in rail-switches.
- Monitoring of heating cables.
- Monitoring of consumption of one-phase motors.
- Indicates current flow in electrical circuits.
1.2 Function Features
- Adjustable delay from 0.5 to 10 seconds to eliminate short current peaks.
- Flexible current adjustment by potentiometer with a choice of 6 ranges:
- AC 0.05-0.5A
- AC 0.1-1A
- AC 0.2-2A
- AC 0.5-5A
- AC 0.8-8A
- AC 1.6-16A
- Possible to use for current scanning from a current transformer.
- Universal supply voltage: AC 24 - 240 V or DC 24 V.
- Relay status is indicated by an LED.
- 1-MODULE, designed for DIN rail mounting.
- Output: 1 SPDT (Single Pole Double Throw) contact, rated 10A/AC1.
2. Model and Connotation
The GRI8 series offers different models based on their monitoring function:
- GRI8-01: Overcurrent Protection
- GRI8-02: Undercurrent Protection
- GRI8-03: Overcurrent or Undercurrent Protection
- GRI8-04: Overcurrent and Undercurrent Protection (in window mode)
The current range is specified by a design number suffix:
- 0.5: 0.05-0.5A
- 1: 0.1-1A
- 2: 0.2-2A
- 5: 0.5-5A
- 8: 0.8-8A
- 16: 1.6-16A

3. Technical Specifications
| Parameter | Specification |
|---|---|
| Function | Monitoring current |
| Supply terminals | A1-A2 |
| Rated supply voltage | AC/DC 24V-240V |
| Rated supply frequency | 50/60Hz, 0 |
| Burden | max 2VA |
| Supply voltage tolerance | -15%; +10% |
| Current range | 0.5A, 1A, 2A, 5A, 8A, 16A (specific ranges: 0.05-0.5A, 0.1-1A, 0.2-2A, 0.5-5A, 0.8-8A, 1.6-16A) |
| Current adjustment | potentiometer |
| Time delay (Tt) | adjustable 0.1-10 s |
| Power up delay (Tr) | adjustable 0.1-10 s |
| Supply indication | green LED |
| Setting accuracy | 10% |
| Repeat accuracy | <1% |
| Temperature dependency | < 0.1 % /°C |
| Limit values tolerance | 5% (10% for 0.05-0.5A range) |
| Hysteresis | 5% |
| Temperature coefficient | 0.05%/°C, at=20°C (0.05%°F, at=68°F) |
| Output | 1×SPDT |
| Current rating | 10A/AC1 |
| Switching voltage | 250VAC/24VDC |
| Min. breaking capacity DC | 500mW |
| Output indication | red LED |
| Mechanical life | 1×107 |
| Electrical life (AC1) | 1×105 |
| Operating temperature | -20°C to +55°C (-4°F to 131°F) |
| Storage temperature | -35°C to +75°C (-22°F to 158°F) |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP40 for front panel/IP20 terminals |
| Operating position | any |
| Overvoltage category | III. |
| Pollution degree | 2 |
| Dimensions | 90×18×64mm |
| Weight | 69g |
| Standards | IEC60947-5-1 |
| Tightening torque | 0.8Nm |
| Max. permanent current (B1-B2) | 0.05A-0.5A, 0.1A-1A, 0.2A-2A, 0.5A-5A, 0.8A-8A, 1.6A-16A |


4. Installation
4.1 Wiring Diagram
The relay is designed for DIN rail mounting. Ensure all electrical connections comply with appropriate safety standards and are performed by qualified electricians.

4.2 Connection Terminals
- A1-A2: Supply Voltage Terminals
- B1-B2: Monitoring Current Terminals
- 11, 12, 14: 1 SPDT Output Contact (11-14 is Normally Open, 11-12 is Normally Closed)

4.3 Example Wiring Case (GRI8-01 Overcurrent Monitoring)

In the GRI8-01 wiring case, terminals 11-14 are normally open and will close after an overcurrent event. Terminals 11-12 are normally closed and will disconnect after an overcurrent event.

5. Operation
5.1 Setting Current Range and Threshold
The current monitoring range is selected by a rotary switch on the front panel. The precise current threshold (Imax for overcurrent, Imin for undercurrent, or Iset for combined) is adjusted using a potentiometer within the selected range.


5.2 Setting Time Delays
Two time delays can be adjusted using potentiometers:
- Tr (Power up delay): Delays the start of monitoring after power-up.
- Tt (Tripping delay): Delays the relay output action after a current anomaly is detected, helping to eliminate short current peaks.
5.3 Relay Status Indication
- Green LED: Indicates power supply status.
- Red LED: Indicates relay output status.
6. Troubleshooting
- Relay not activating/deactivating as expected: Check the current threshold settings (Imax/Imin/Iset) and ensure they are appropriate for your application. Verify the time delay settings (Tr, Tt) are not preventing immediate action.
- LEDs flashing (GRI8-04): If using GRI8-04 (Over/Undercurrent in window mode), ensure the set over-current threshold value is larger than the under-current threshold value. If not, the LEDs will flash, and the output relay will be disconnected.
- Inaccurate delay time: Some users have noted that the delay time for turning off might not be very accurate. If precise timing is critical, consider external timers or further calibration.
- No power indication: Check the supply voltage connections to A1-A2. Ensure the voltage is within the AC/DC 24V-240V range.
- No output action: Verify the load connected to the 11, 12, 14 contacts is correctly wired and within the 10A/AC1 rating.
7. Maintenance
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
- Inspection: Periodically inspect the wiring connections for tightness and signs of wear or damage.
- Environmental Conditions: Ensure the operating environment adheres to the specified temperature and humidity ranges to prevent malfunction.
- Disposal: All electrical waste should be disposed of in compliance with current WEEE regulations.
8. User Tips
- Pump Dry-Run Protection: This relay is well-suited for pump dry-run protection. Adjust the undercurrent threshold precisely to switch off the pump when the current draw drops below a safe operating level.
- Precise Adjustment: Take time to precisely adjust the current potentiometers for optimal performance in your specific application.
- Home Use: For home use, this product offers excellent functionality and value compared to more expensive alternatives.
- Wiring Diagrams: Always refer to the detailed wiring diagrams provided in this manual and on the device itself for correct installation.
9. Warranty and Support
For warranty information and technical support, please refer to the official GEYA website or contact your local distributor. A comprehensive user manual in PDF format is available for download: User Manual (PDF).
10. Contact Information
GEYA ELECTRICAL CO.,LTDAdd: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
Mobile: 0086-13567770207
E-mail: sale@cngeya.com
Web: www.geya.net
11. Safety and Disposal
11.1 Caution
WARNING: The products must be installed by qualified electricians. All and any electrical connections of the product shall comply with the appropriate safety standards.
11.2 Disposal of Electrical Waste
All electrical waste should be disposed of in compliance with current WEEE regulations.