1. Introduction
This manual provides instructions for the installation, operation, and maintenance of the DIANQI THC15A/AHC15A Electronic Weekly 7 Days Programmable Digital Timer Switch. This device is designed for automatic control of electrical appliances based on a pre-set weekly schedule, offering convenience and energy efficiency.
2. Safety Information
- Ensure the power supply is disconnected before installation or maintenance to prevent electric shock.
- Installation should be performed by a qualified electrician or knowledgeable individual.
- Do not exceed the specified voltage and current ratings.
- Keep the device away from moisture, dust, and extreme temperatures.
- Verify all connections are secure before applying power.
3. Product Overview
The THC15A/AHC15A is a digital time switch featuring daily programs and the ability to repeat schedules. It supports up to 20 ON/OFF settings and includes a manual override function. A built-in lithium battery provides power reserve for settings, and it offers automatic time error correction.

Figure 1: THC15A/AHC15A Digital Timer Switch (Type 1 and Type 2)

Figure 2: Timer Switch Contact Types (1NO1NC and 1NO)
Video 1: Product demonstration showing the timer switch from various angles and highlighting its features.
4. Specifications
| Feature | Specification |
|---|---|
| Model Number | THC15A / AHC15A |
| Voltage Rating | AC 220V 50/60Hz (Other options: 12V, 24V, 36V, 48V, 110V) |
| Voltage Limit | AC 180V~250V |
| Hysteresis | ≤1 sec/day (at 25°C) |
| ON/OFF Operation | 20 ON & 20 OFF settings |
| Power Consumption | 2VA (max) |
| Display | LCD |
| Service Life (Mechanical) | 107 operations |
| Service Life (Electrical) | 105 operations |
| Minimum Interval | 1 minute |
| Weight | Approx. 100g |
| Countdown Function | 1 sec - 99 min 56 sec |
| Pulse Function | 1 sec - 59 min 59 sec |
| Load Capacity (Contact Type) | 16A/250V AC |
| Load Capacity (Straight Type) | 10A/250V AC |
| Switching Contact | 1 changeover switch |
| Power Reserve | 3 years (Lithium battery) |
| Ambient Temperature | -10°C to +40°C |
| Ambient Humidity | 35% to 85% RH |
| Certification | CE |
| Available Set Plans | 20 plans |

Figure 3: Overall Dimensions of the Timer Switch
5. Installation
5.1 DIN Rail Mounting
The timer switch is designed for DIN rail installation. Simply clip it onto a standard DIN rail in your electrical panel. Ensure the clip is securely fastened.

Figure 4: DIN Rail Mounting Clip
5.2 Wiring Diagrams
Refer to the following diagrams for correct wiring based on your timer switch type (Contact Type or Straight Type). Always ensure power is off before making any connections.

Figure 5: Straight Type (1NO) Connection Diagram

Figure 6: Contact Type (1NO1NC) Connection Diagram
6. Operating Instructions
6.1 Initial Setup
- Press the RESET key to clear all previous settings and start the machine.
- To set the current time: After pressing RESET, press the P button. Then, use D+ (Day), H+ (Hour), and M+ (Minute) buttons to adjust the display to the current time.
6.2 Programming ON/OFF Schedules
The timer allows for up to 20 ON and 20 OFF programs. Follow these steps to enter and set your desired schedules:
| Step | Key | Action / Programming |
|---|---|---|
| 1 | P | Set 1 ON time (display shows '1 ON') |
| 2 | H+/M+ | Set hours and minutes for ON time |
| 3 | D+ | Select specific days or all days for this ON time |
| 4 | P | Set 1 OFF time (display shows '1 OFF') |
| 5 | H+/M+ | Set hours and minutes for OFF time |
| 6 | D+ | If you want the same day(s) as ON time, you do not need to press this key. Otherwise, select specific days. |
| 7 | Repeat steps 2-6 | Set programs 2 through 20 (ON/OFF times) |
| 8 | CLOCK | Exit programming mode and return to current time display |
Important Notes:
- Time settings must be entered in chronological order. Overlapping or cross-setting times is not possible.
- The system will automatically exit programming mode if there is no operation within 10 seconds, and unsaved data will be lost.
- Functions for setting Day, Hour, and Minute (D+, H+, M+) cannot be used simultaneously during programming.

Figure 7: Timer Switch Display and Control Buttons
7. Maintenance
- Regularly check wiring connections for tightness and signs of wear.
- Keep the device clean and free from dust using a dry, soft cloth.
- If the device will not be used for an extended period, press the H+ and D+ keys simultaneously for 2 seconds to turn off the display and conserve battery life.
8. Troubleshooting
- Display is blank or unresponsive: Ensure the device is receiving power. If it has been stored for a long time, the internal battery might be depleted; allow it to charge for a few minutes after connecting to power. Press the RESET button.
- Programs not executing: Verify that the current time is set correctly. Check that programs are entered in chronological order and do not overlap. Ensure the timer is in automatic mode (if applicable).
- Device unexpectedly quits programming: The system automatically exits programming if no button is pressed for 10 seconds. Ensure you complete each step within this timeframe.
- Inaccurate timing: The device has an auto time error correction of ±60 seconds per week. If significant deviation occurs, reset and reprogram.
9. User Tips
- For optimal performance, ensure all electrical connections are clean and tight. One user reported that cleaning the connector between the internal battery and the electronic board resolved issues with smooth operation.
- While installation can be straightforward, consulting online resources or a professional for complex wiring setups can be beneficial.
- Take advantage of the 20 ON/OFF settings to create detailed and efficient schedules for various applications.
10. Warranty and Support
For specific warranty information, please refer to the product packaging or contact your retailer. For additional support or inquiries, please reach out to the manufacturer's customer service.
A detailed user manual in PDF format is available for download. Please refer to the product page or manufacturer's website for the link.