1. Introduction
The LILYTECH ZL-7918A is an intelligent temperature and humidity controller designed for incubators, climate chambers, warehouses, and similar applications. It offers stable and convenient operation with advanced control features to ensure optimal environmental conditions.
Video: Overview of the LILYTECH ZL-7918A Incubator Controller.
2. Specifications
- Model Number: ZL-7918A
- Power Supply: 100 ~ 240Vac, 50/60Hz
- Sensors: One temperature sensor (L = 2.0 meter), one humidity sensor (L = 2.0 meter)
- Setting Range: Humidity 0~99% RH, Temperature 1~75℃
- Display Range: Humidity 0~99% RH, Temperature -9.9~99°C
- Measuring Accuracy: Humidity ±3%@25°C, Temperature ±1%@25°C
- Output Control: 7 outputs (main-heater, aux-heater, lamp, humidity, egg-right-turning, egg-left-turning, fan)
- Output Load: Heater ≤ 1500W, Lamp ≤ 100W, Humidity, egg-turning and fan ≤ 1A/250Vac
- Hatched Day Counter: Maximum value 99 days
- Egg Turn Control: Turn period: 1 ~ 999 minutes, Turn driving time: 0 ~ 999 seconds, Turn times counter: 0~999 times
- Air Exhaustion Control: Period: 1 ~ 999 minutes, Exhausting time: 0~999 seconds
- Lamp Control: Period: 1 ~ 999 minutes, Illuminating time: 0~999 seconds
- Operation Environment: -10 ~ 45°C, less than 90% RH without dew
- Device Dimensions: 160 * 80 * 95 mm
- Installation Drilling Size: 151.5 * 76.5 mm
- Weight: 0.695 kg
3. Package Contents
The standard package for the ZL-7918A controller includes:
- 1 x ZL-7918A Incubator Controller Unit
- 1 x Temperature Sensor (2.0m cable)
- 1 x Humidity Sensor (2.0m cable)

Image: LILYTECH ZL-7918A Controller with ZL-SHr05A sensor.

Image: LILYTECH ZL-7918A product packaging.
4. Installation and Setup
4.1. Wiring Diagram
Carefully follow the wiring diagram below for proper installation. Incorrect wiring can damage the device or connected components.

Image: Detailed wiring diagram for the ZL-7918A controller, showing connections for humidity and temperature sensors, power supply, fan, egg turning, humidifier, lamp, and heaters.
4.2. Terminal Connections
- Humidity Sensor: Connect RED, YELLOW, BLACK, ORANGE wires to terminals 1-4 respectively.
- Temperature Sensor: Connect to terminals 5-6.
- Power Supply (100-240Vac): Connect Neutral (N) to terminal 13 and Live (L) to terminal 14.
- Outputs:
- FAN: Connect to terminals 15-16.
- TURN EGG (LEFT/RIGHT): Connect to terminals 17-18 (LEFT) and 19-20 (RIGHT).
- HUMIDIFIER: Connect to terminals 21-22.
- LAMP: Connect to terminals 23-24.
- AUX. HEATER (HEAT2): Connect to terminals 21-22 (shared with humidifier, ensure proper load management).
- MAIN HEATER (HEAT1): Connect to terminals 23-24 (shared with lamp, ensure proper load management).

Image: Rear view of the LILYTECH ZL-7918A controller, highlighting the terminal block for wiring connections.
4.3. Firmware Information
Upon initial power supply, the display will briefly show the model "7918A" and version "A6.0".
4.4. Initial Settings (Temperature and Humidity Setpoint)
The device is shipped with factory default settings suitable for normal hatching requirements. These settings can be used directly without further adjustment for basic operation.
- To enter the temperature and humidity setpoint setting status, press and hold the [Set] button for 2 seconds.
- Press [Enter] to switch between temperature setting status (SV window displays "***" + "tt") and humidity setting status (SV window displays "***" + "HH").
- Use the [▲] or [▼] buttons to adjust the setpoint. Holding the button will allow for faster adjustment.
- To save settings and exit, press and hold [Enter] for 2 seconds. The controller will automatically generate control parameters (P-).
- If no key operation occurs for 15 seconds, the setting status will exit without saving.
Factory Default Setpoints:
- Temperature Setpoint (P3): 38°C (Range: 1 ~ 75°C)
- Humidity Setpoint (P9): 60%RH (Range: 0~99%RH)
4.5. Advanced Settings (Temperature and Humidity Control Parameters P-)
Note: Adjusting these parameters will override the automatically generated values from the initial setpoint configuration. Proceed with caution.
- To enter the temperature and humidity control parameter (P-) setting status, press [Set] and [▲] simultaneously.
- Press [Enter] to select parameters. The SV window will display selections from "***" + "PO" to "***" + "PH".
- Use the [▲] or [▼] buttons to adjust the parameter value.
- To save settings and exit, press and hold [Enter] for 2 seconds.
- If no key operation occurs for 15 seconds, the setting status will exit without saving.
Temperature and Humidity Control Parameters (P-) Table:
| Code | Function | Range | Note | Factory Default |
|---|---|---|---|---|
| PO | High temperature warning point | 0~75℃ | 38.7 | |
| P1 | Exhaustion temperature up limit | 0~75°C | Start exhausting for cooling | 38.2 |
| P2 | Exhaustion temperature low limit | 0~75°C | Stop cooling exhausting | 38.0 |
| P3 | Main temperature up limit | 0~75°C | Main heater stops heating | 38.0 |
| P4 | Main temperature low limit | 0~75°C | Main heater starts heating | 37.9 |
| P5 | Aux temperature up limit | 0~75°C | Aux heater stops heating | 37.7 |
| P6 | Aux temperature low limit | 0~75°C | Aux heater starts heating | 37.5 |
| P7 | Low temperature warning point | 0~75℃ | 37.2 | |
| P8 | High humidity warning point | 0~99% | 70 | |
| P9 | Humidity up limit | 0~99% | Humidify load stops humidifying | 60 |
| Pb | Humidity low limit | 0~99% | Humidify load starts humidifying | 58 |
| Pc | Exhaustion humidity up limit | 0~99% | Start ventilation for de-humidifying | 65 |
| Pd | Exhaustion humidity low limit | 0~99% | Stop de-humidifying ventilation | 60 |
| PE | Over wet exhaustion protection | 0/1 | 0: disable; 1: enable | 0 |
| PP | Low humidity warning point | 0~99% | 50 | |
| PH | Sensor selection | 0/1 | 0: ZL-SHr03A; 1: ZL-SHr05A or ZL-SHr05B | 1 |
4.6. Function Control Parameters (F-)
- To enter the function control parameter (F-) setting status, press [Set] and [▼] simultaneously.
- Press [Enter] to select parameters. The SV window will display selections from "***" + "F1" to "***" + "Fb".
- Use the [▲] or [▼] buttons to adjust the parameter value.
- To save settings and exit, press and hold [Enter] for 2 seconds.
- If no key operation occurs for 15 seconds, the setting status will exit without saving.
Function Control Parameters (F-) Table:
| Code | Function | Range | Note | Factory Default |
|---|---|---|---|---|
| F1 | Egg turn period | 1~999 min | 90 | |
| F2 | Egg turn time | 0~999 sec | 0: no egg turning function | 180 |
| F3 | Egg turn times | 0~999 times | 0: turn for ever | 0 |
| F4 | Air exhausting period | 1~999 min | 120 | |
| F5 | Air exhausting time | 0~999 sec | 0: no air exhausting | 30 |
| F6 | Temperature calibration | -9.9~9.9℃ | 0.0 | |
| F7 | Humidity calibration | -20~20% | 0 | |
| F8 | Illumination period | 0~999 min | 0: shut off timer illumination | 0 |
| F9 | Illumination time | 0~999 sec | 120 | |
| FF | Incubated days | 0~99 day | Can reset only | 0 |
| Ft | Egg turn period time saving | 0/1 | 0: not saving. 1: saving | 0 |
| FM | Egg turned counter | 0~999 times | Can reset only | 0 |
| FE | Egg turned counter reset | 0/1 | 0: reset to 0 if turned offline or power supplied; 1: keeps after turned offline or power supplied | 0 |
| Fb | Buzzing when alarming | 0/1 | 0: No buzzing when alarming; 1: buzzing when alarming | 1 |
5. Operation
5.1. On/Off Operation
To switch the controller between online and offline modes, press and hold the [Lamp - I/O] button for 2 seconds.
5.2. Illumination Control
- Manual Control (Online/Offline): Press [Lamp - I/O] to turn the lamp on for the duration set in F9 (Illumination time). Press it again to turn the lamp off.
- Timer Control (Online Only): The lamp will turn off for every period set in F8 (Illumination period), then turn on for the duration set in F9 (Illumination time).
5.3. Temperature Control
- Main Heater: Turns on when room temperature ≤ P4 (Main temperature low limit) and off when room temperature ≥ P3 (Main temperature up limit).
- Auxiliary Heater: Turns on when room temperature ≤ P6 (Aux temperature low limit) and off when room temperature ≥ P5 (Aux temperature up limit).
- Exhaustion Fan: Turns on when room temperature ≥ P1 (Exhaustion temperature up limit) and off when room temperature ≤ P2 (Exhaustion temperature low limit).
5.4. Humidity Control
- Humidifier: Turns on when room humidity ≤ Pb (Humidity low limit) and off when room humidity ≥ P9 (Humidity up limit).
- Exhaustion Fan (Over Wet Protection):
- If PE (Over wet exhaustion protection) = 1: The exhaustion fan turns on when room humidity ≥ Pc (Exhaustion humidity up limit) and turns off when room humidity ≤ Pd (Exhaustion humidity low limit).
- If PE = 0: No protection exhaustion occurs when over wet.
5.5. Egg Turn Control
- Timer Egg Turning: For every F1 (Egg turn period), the egg turn output will activate for F2 (Egg turn time). The left and right turning outputs will alternate. One left turn + one right turn equals one egg-turn. The egg turned counter (FM) increases by 1 for each egg-turn. When FM reaches F3 (Egg turn times), egg turning stops, and the "UP" and "DOWN" indicators will blink.
- Manual Egg Turning: Can be operated online or offline. Hold [▲] for left turning, and [▼] for right turning.
- Egg Turning Status Saving: The direction of egg turning changes after power is supplied or when the device comes online. If power is lost during egg turning, it will resume from where it left off once power is restored.
- Reset Egg Turned Counter (FM): If FE (Egg turned counter reset) = 0, FM resets after power supplied or offline. If FE = 1, FM retains its value after power supplied or offline. It can also be manually set to zero.
- Egg Tray Period Status Memory: If Ft (Egg turn period time saving) = 0, the period status is not saved. If Ft = 1, the period status is saved every 3 minutes. Period timing continues after power loss with a maximum error of 3 minutes.
5.6. Exhaustion Timer Control
For every F4 (Air exhausting period), the exhaustion fan will turn on for F5 (Air exhausting time).
5.7. Alarm Control
The controller will buzz and blink the room temperature/humidity display under the following conditions:
- Room temperature ≥ PO (High temperature warning point)
- Room temperature ≤ P7 (Low temperature warning point)
- Room humidity ≥ P8 (High humidity warning point)
- Room humidity ≤ PP (Low humidity warning point)
- Sensor failure (E1, E2)
During an alarm, pressing [Enter] can stop or restore the buzzing.
5.8. LED Indication
| LED | On | Blinking | Off |
|---|---|---|---|
| FAN | Fan on during Air exhausting time (F5) | Fan on because of temperature/humidity protection exhaustion | Fan off |
| HEAT1 | Main heater on | Main heater off | |
| HEAT2 | Aux. heater on | Aux. heater off | |
| UP | Egg left turning now | Egg turned counter (FM) reaches Egg turn times (F3) | No left turning |
| DOWN | Egg right turning now | Egg turned counter (FM) reaches Egg turn times (F3) | No right turning |
| WET | Humidifying output on | Humidifying output off | |
| ALARM | Temperature or humidity is over warning points, or sensor fails |
6. Calibration
The sensors have a certain tolerance and can achieve absolute 0.1 °C and 1% RH accuracy after calibration.
- Temperature Calibration: Adjust the room temperature reading by setting F6 (Temperature calibration).
- Humidity Calibration: Adjust the room humidity reading by setting F7 (Humidity calibration).
7. Maintenance
- Humidity Sensor Care: The humidity sensor will not function correctly if covered with dust, water, or dew. Always keep it clean and dry. Before cleaning the sensor, ensure there is no static electricity on your hands.
- Cleaning: Regularly clean the controller's exterior with a soft, dry cloth. Do not use abrasive cleaners or solvents.
8. Troubleshooting
8.1. Warning Codes
The controller displays warning codes to indicate specific issues:
| Code | Indication |
|---|---|
| E1 | Temperature sensor failure |
| E2 | Humidity sensor failure |
| E3 | High temperature alarm |
| E4 | Low temperature alarm |
| E5 | High humidify alarm |
| E6 | Low humidify alarm |
8.2. Common Issues and Solutions
- Humidity Calibration Issues: If humidity readings are inaccurate or calibration doesn't seem to work, ensure the sensor is clean and dry. Re-check the F7 (Humidity calibration) setting.
- Humidity Not Changing: If humidity remains static (e.g., at 50%) despite adjustments, verify the settings for P9 (Humidity up limit), Pb (Humidity low limit), Pc (Exhaustion humidity up limit), Pd (Exhaustion humidity low limit), and PE (Over wet exhaustion protection). Ensure the dehumidification function (PE=1) is enabled if needed.
- Temperature Fluctuations: If temperature changes on its own, check for sensor failure (E1 warning) or ensure heating/cooling elements are functioning correctly and within their set limits (P0-P7).
- Missing Sensor: Always verify package contents upon arrival. If a sensor is missing, contact the seller immediately.
9. User Tips
- Careful Installation: While the controller is robust, pay close attention to the wiring diagram during installation to prevent damage and ensure proper function.
- Dehumidification Feature: The dehumidification function (exhaustion fan for over-wet protection) is often disabled by default. If you require active dehumidification, remember to enable it through the P-parameters menu (set PE=1).
- Power Loss Memory: All settings are saved in memory and will not be lost during a power outage. The controller will resume operation with the last saved settings once power is restored.
- Fan Wiring: For applications requiring a constantly running fan (e.g., for air circulation), consider wiring it separately and directly to the power supply, bypassing the controller's fan output. The controller's fan output can then be used for specific ventilation cycles if desired.
- Incubated Days Counter: The FF (Incubated days) counter is saved in memory. Before starting a new incubation cycle, it is necessary to manually reset this counter to zero if you wish to track days accurately for the new batch.
10. Warranty and Support
For detailed warranty information, technical support, and further documentation, please refer to the official user manual PDF available at: LILYTECH ZL-7918A User Manual (PDF).
The manufacturer is responsible for the device itself but is not liable for losses resulting from the failure of this device.