LILYTECH ZL-6210A+

Contents

ZL-6210A+ Digital Temperature Controller

User Instruction Manual

1. Introduction

The ZL-6210A+ series thermostat is designed for precise cooling or heating control. It features an IP65 rated front panel, a buzzer for beeping, and a warning function. This model specifically offers a 30A temperature relay output for robust performance.

ZL-6210A+ Digital Temperature Controller front view with display and control buttons.
Figure 1: Front view of the ZL-6210A+ Temperature Controller.
ZL-6210A+ Digital Temperature Controller back view showing terminal blocks for wiring.
Figure 2: Rear view of the ZL-6210A+ showing terminal connections.

For a comprehensive manual, including detailed diagrams and advanced settings, please refer to the official PDF document: https://manuals.plus/m/a839e39999d66523351452668a82d1ed208ddb1d1d07758f710fa28d313d6e91

2. Specifications

Feature Description
Model ZL-6210A+
Function Cooling or heating, Warning input, Timer defrost (cooling mode only, defrost method: stop cooling)
Power Supply 185 ~ 245Vac, 50/60Hz
Sensor NTC, 2 meters long (included)
Output R1: 30A, R2: 5A, 250Vac resistive
Setting Range -40 ~ 120°C
Display Range -40 ~ 130°C
Working Conditions -10 ~ 45°C, 5 ~ 90%RH (non-condensing)
Dimensions (W x H x D) 78 x 34.5 x 71 (mm)
Installation Drilling (W x H) 71 x 29 (mm)
Case Materials PC + ABS fire proof
Protection Level IP65 (Front side only)

NTC Sensor Selection

The ZL-6210A+ is compatible with various NTC sensors. The choice of sensor type (Metal, TPE, Water) depends on the application environment.

Table showing different NTC sensor types: Metal (copper nickel coated), TPE, and Water (long life in water), with their wire length, resistance, and B values.
Figure 3: NTC Sensor Selection Guide.
  • Metal (copper nickel coated): Wire Length: 2.5 meters, Resistance: 5.00K at 25°C 3%, B: 3470K 2% (25°C/50°C).
  • TPE: Wire Length: 2 meters, Resistance: 5.00K at 25°C 2%, B: 3470K 1% (25°C/50°C).
  • Water (long life in water): Wire Length: 5 meters, Resistance: 5.00K at 25°C 3%, B: 3470K 2% (25°C/50°C).

3. Installation

The ZL-6210A+ is designed for embedded installation. Follow these steps:

  1. Insert into drilling hole: Prepare a panel opening with dimensions W71 x H29 mm. Insert the controller into the hole.
  2. Clamp: Secure the controller in place using the provided clamps from the sides.
Diagram showing the two steps for installing the ZL-6210A+ controller: inserting into a drilling hole and clamping it.
Figure 4: Installation steps.

4. Electrical Wiring

Attention:

  • Wiring work should be manipulated by certified technicians.
  • Wrong connection could damage the controller and the loads. Power supply to pin 7,8 for ZL-62x0A, pin 5, 6 for ZL-62x0A+ to check the controller. If there is a multimeter, check the outputs, as well as input, by the help of settings.
  • Sensor and input signal wires should not be laid together with power supply wire, and even in same pipe. Sensor wire is better as short as possible. Not wind the redundant length wire to electrical noise equipment.
  • The loads should be within the specification of the controller output driving ability. If using ac/dc module as load, or tungsten lamp, or motor, following the below requirements to avoid surging current damaging or shorten the life time of the controller outputs:
    • For ac/dc module as load, the rated current should be no more 1/10th of output specification under pure resistance.
    • For tungsten lamp as load, the rated current should be no more 1/15th of output specification under pure resistance.
    • For motor, the rate current should be no more 1/5th of output specification under pure resistance.
    For example: if drive a 1500W tungsten lamp with 7A (pure resistance spec.) relay, the relay contactor will be burnt immediately.
  • Don't touch inside components.
  • Avoid installing controller in the following environment: More wet than 90%RH, or easily dew; Vibrating, or will be shocked; Possible sprayed; Under erosive air; Under explosive air.

Wiring Diagram for ZL-6210A+

Wiring diagram for ZL-6210A+ showing connections for R1 Temperature Output (30A/250V~), Alarm Input, and Temp. Sensor.
Figure 5: ZL-6210A+ Electrical Wiring Diagram.

Terminal Descriptions:

  • 1, 2: R1: Temp. Output 30A/250V~ (N1, L1)
  • 3, 4, 5, 6: Power Supply (L, N for 220V~)
  • 7, 8: Alarm Input
  • 9, 10: Temp. Sensor

5. Operation

5.1 Set Set-Point

  1. Keep the S button depressed for 3 seconds to enter into the setting status. The current set-point value will display.
  2. Press ▲ or ▼ to set the value (keeping depressed allows for fast setting).
  3. Press S again to exit the setting status and save the setting.

Note: The setting status will exit, and the setting will not be saved, if there is no key operation within 30 seconds.

5.2 Set Parameters

  1. Keep the P button depressed for 3 seconds; the display will show "00".
  2. Press ▲ or ▼ to input the password (range 00-99).
  3. Press S to confirm: If the password is correct, you will enter the parameter setting status. Otherwise, "Err" will be displayed, and the unit will exit.
  4. In parameter setting status: Press ▲ or ▼ to select the parameter code.
  5. Press S to display the value of the code.
  6. Press ▲ or ▼ to set the value.
  7. Press S to return to parameter code selection.
  8. Keep P depressed for 3 seconds to exit parameter setting status and save the settings.

Note: The parameter setting status will exit, and the settings will not be saved, if there is no key operation for 30 seconds.

6. Parameter Code Table

Code Function Range Remark Default
U10Minimum time for R1 to keep de-energized0 ~ 100 min3
U11Minimum time for R1 to keep energized0 ~ 100 min3
U12Frequency for R1 to be on / off0 ~ 80: disable5
U20Sensor calibration-9.9 ~ +9.9°C0.0
U22Hysteresis for temp. control0.1 ~ +10.0°CU22 < U54, U551.0
U30Defrost period0 ~ 180 hour0: never defrost12
U31Defrost time1 ~ 180 min30
U33Dripping water time0 ~ 180 min5
U34Overtemp. alarming delay after defrosted0 ~ 180 hour0: disable2
U35Defrost after online0 / 10: disable / 1: enable0
U36Delay for defrost after online0 ~ 180 min0
U38Defrost method0 / 10: by heater, 1: by hot gas
U52Over temp. alarming delay0 ~ 180 min30
U531st over temp. alarming delay0 ~ 180 hour0: disable2
U54Hysteresis for high temp. alarmingU22 ~ 60.0°C / OFFOFF (> 60.0°C): disable alarmingOFF
U55Hysteresis for low temp. alarmingU22 ~ 60.0°C / OFFOFF (> 60.0°C): disable alarmingOFF
U60External input warning mode0 ~ 40: disable, 1: NO locked, 2: NO unlocked, 3: NC locked, 4: NC unlocked0
U61Delay for external input warning0 ~ 120 min0
U62Buzzing alarming0 / 10: no alarming / 1: enable alarming0
U90Control modeCO: cool / HE: heatCO
U99Password00 ~ 9911

7. Control Functions

7.1 Cooling Control (U90 = C0)

7.1.1 Temperature control

  • If Troom ≥ Set-point + U22, and R1 has been de-energized for U10, then R1 energized.
  • If Troom ≤ Set-point, and R1 has been energized for U11, then R1 de-energized.

Example: If set-point = 18, U22 = 0.2, then the controller will control the temperature between 18.2°C and 18.0°C.

7.1.2 Forced cooling

Keep ▲ depressed for 5 seconds to force R1 energized under following conditions:

  • R1 has been de-energized for U10.
  • Troom is between (Set-point + U22) and (Set-point).
  • Not in defrosting and dripping water status.

The forced cooling will finish, R1 will be de-energized, when Troom arrives at Set-point.

7.1.3 Stop forced cooling

During forced cooling, if R1 has been energized for U11, keeping ▼ depressed for 5 sec. will stop forced cooling.

7.2 Heating Control (U90 = HE)

7.2.1 Temperature control

  • If Troom ≤ Set-point - U22, and R1 has been de-energized for U10, then R1 will be energized.
  • If Troom ≥ Set-point, and R1 has been energized for U11, then R1 will be de-energized.

Example: If set-point = 18, U22 = 0.2, then the controller will control the temperature between 17.8°C and 18.0°C.

7.2.2 Forced heating

Keep ▲ depressed for 5 seconds to force R1 energized under following conditions:

  • R1 has been de-energized for U10.
  • Troom is between (Set-point - U22) and (Set-point).

The forced heating will finish, R1 will be de-energized, when Troom reaches Set-point.

7.3 Delay Protection

  • After power supplied, R1 could be energized after U10.
  • After R1 de-energized, it could be energized again after U10.
  • After R1 energized, it could be de-energized again after U11.

7.4 Protecting Run (Function Disabled when U12 = 0)

When sensor fails, R1 will be energized and de-energized periodically.

  • For every 30 minutes, R1 will be energized for U12* 3 minutes, de-energized for (30-U12*3) minutes.

Example: U12 = 2, if sensor fails, R1 will be energized for 2*3 = 6 min., de-energized for 30 -2 * 3 = 24 min., periodically.

7.5 Defrost

7.5.1 Periodically defrost

When R1 has been energized for U30, defrost for U31.

Note: After defrosted, start dripping water for U33. R1 keeps de-energized during dripping water.

7.5.2 Forced defrost

During non-defrost status, keeping ▲ depressed for 7 seconds will start forced defrost. When defrosted, start dripping water.

When defrosting, keeping ▼ depressed for 7 seconds will stop defrost, and start dripping water.

7.5.3 Dripping water after defrosted

After defrosted, start dripping water for U33. R1 keeps de-energized during dripping water.

7.5.4 Left time of defrost or dripping water

When defrosting or dripping water, press ▲ will show the left time.

Attention: If the key is kept depressed for 7 seconds, it will switch the defrost status.

7.6 Beeping

There will be a short beep for normal key press, a long beep for confirmation of setting, and three short beeps for error operation.

When there is failure, or external warning input: If U62 = 0, no beep warning. If U62 = 1, there will be continuous warning beeping.

The warning will stop if you press P, or the warning condition disappears.

7.7 Over Temperature Alarming

When Troom ≥ Set-point + U54, there will be high temperature alarming if the following conditions meet.

When Troom ≤ Set-point – U55, there will be low temperature alarming if the following conditions meet.

  • If power just supplied, and U53 has passed.
  • The Troom keeps the up condition for U52.
  • If just defrosted, and U34 has passed.

Note: Over temperature alarming does not affect the temperature control and defrost process.

7.8 External Warning Input

  • NO: normal open. If open, no warning; if closed, warning.
  • NC: normal close. If closed, no warning; if open, warning.
  • Locked: Warning keeps after the external warning disappeared. Press P to stop warning.
  • Unlocked: Warning stops after the external warning disappeared.

Note: When there is external warning, the output(s) will be de-energized.

7.9 Sensor Calibration

The sensor can be calibrated by U20.

7.10 Restore to Factory Default Settings

Keep P and ▲ depressed simultaneously for 5 sec, there will be a beep, and "UnL" displays.

Press S twice, there will be a beep, all settings will be restored to factory default settings.

8. Display and Indicators

8.1 Sign Icons

Icon Function On Off Blinking
Temp. control output (R1)R1 energizedR1 de-energizedWithin protecting delay
DefrostDefrostingNot defrosting nowDripping water
Work modeCooling modeSetting set-point
Work modeHeating modeSetting set-point
Maintenance---No failureHas failure
AAlarm---No alarmAlarming

8.2 Character Displays

Display Remark
E01Sensor failure (short or open)
HiRoom temp. is higher than the high limit
LoRoom temp. is lower than the low limit
EEMemory error
ErrPassword error
¡AExternal warning
dEFDefrosting
UnLParameters Will restore to factory default settings

8.3 Display after power supplied

Upon power-up, the controller will display all segments, model, and version one by one (e.g., ZL-62X0A, then ZL-62X0A+ (P = plus)).

9. Troubleshooting

  • E01 Error: This indicates a sensor failure (short or open circuit). Check the sensor connection and the sensor itself. Ensure it is properly connected to terminals 9 and 10.
  • Settings Not Saving: If settings are not saved after power cycling, ensure you press the 'S' button to confirm and exit the setting status. The unit will exit without saving if there is no key operation for 30 seconds.
  • Display Glitches: If the display shows incorrect segments or combines modes, check the power supply stability and ensure the unit is installed in a suitable environment (avoiding high humidity, vibration, or corrosive air).
  • Incorrect Temperature Readings: Calibrate the sensor using parameter U20 if readings are inaccurate.

10. User Tips

  • Sensor Diameter: The NTC sensor typically has a diameter of 6mm.
  • High Power Loads: For loads exceeding 3kW (e.g., 6kW heaters), it is highly recommended to use an external contactor or relay to switch the load, rather than directly connecting it to the controller's output. This prevents damage to the controller's internal relay.
  • Sensor Type for Specific Applications: For smokehouses or environments with high temperatures, a metal-cased sensor is often preferred for durability and better response. For liquid temperature control, a 'Water' type sensor is suitable.
  • Sensor Cable Length: The included sensor cable is typically 1.5 to 2 meters long. It can be extended if needed, as it uses a simple two-wire connection.
  • Accuracy: The controller offers good accuracy (typically 1%-3% error) and allows for calibration via parameter U20 to fine-tune readings.
  • Hysteresis Setting: The hysteresis (U22) can be set to as low as 0.1°C for precise temperature control, useful in applications like incubators.
  • Power Options: While the main specification lists 185-245Vac, 110Vac versions are available and function correctly for regions using that voltage.

11. Certifications

The ZL-6210A+ Temperature Controller complies with international standards for quality and safety.

CE Certification

Attestation of Compliance CE certificate for ZL-6230A+ Temperature Controller.
Figure 6: CE Attestation of Compliance.

ISO Certification

Quality Management System Certificate ISO 9001:2015 for Suzhou Lily Tech. Co., Ltd.
Figure 7: ISO 9001:2015 Quality Management System Certificate.

12. Warranty and Support

For detailed warranty information and technical support, please refer to the official product documentation or contact the manufacturer directly. Always ensure proper installation and usage as described in this manual to maintain product validity.

13. Product Overview Video

Watch this short video for a 360-degree view of the ZL-6210A+ Digital Temperature Controller.

Video 1: ZL-6210A+ Product Rotation.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.