1. Introduction
The ZL-6210A+ series thermostat is designed for precise cooling or heating control. It features an IP65 rated front panel, a buzzer for beeping, and a warning function. This model specifically offers a 30A temperature relay output for robust performance.
For a comprehensive manual, including detailed diagrams and advanced settings, please refer to the official PDF document: https://manuals.plus/m/a839e39999d66523351452668a82d1ed208ddb1d1d07758f710fa28d313d6e91
2. Specifications
| Feature | Description |
|---|---|
| Model | ZL-6210A+ |
| Function | Cooling or heating, Warning input, Timer defrost (cooling mode only, defrost method: stop cooling) |
| Power Supply | 185 ~ 245Vac, 50/60Hz |
| Sensor | NTC, 2 meters long (included) |
| Output | R1: 30A, R2: 5A, 250Vac resistive |
| Setting Range | -40 ~ 120°C |
| Display Range | -40 ~ 130°C |
| Working Conditions | -10 ~ 45°C, 5 ~ 90%RH (non-condensing) |
| Dimensions (W x H x D) | 78 x 34.5 x 71 (mm) |
| Installation Drilling (W x H) | 71 x 29 (mm) |
| Case Materials | PC + ABS fire proof |
| Protection Level | IP65 (Front side only) |
NTC Sensor Selection
The ZL-6210A+ is compatible with various NTC sensors. The choice of sensor type (Metal, TPE, Water) depends on the application environment.
- Metal (copper nickel coated): Wire Length: 2.5 meters, Resistance: 5.00K at 25°C 3%, B: 3470K 2% (25°C/50°C).
- TPE: Wire Length: 2 meters, Resistance: 5.00K at 25°C 2%, B: 3470K 1% (25°C/50°C).
- Water (long life in water): Wire Length: 5 meters, Resistance: 5.00K at 25°C 3%, B: 3470K 2% (25°C/50°C).
3. Installation
The ZL-6210A+ is designed for embedded installation. Follow these steps:
- Insert into drilling hole: Prepare a panel opening with dimensions W71 x H29 mm. Insert the controller into the hole.
- Clamp: Secure the controller in place using the provided clamps from the sides.
4. Electrical Wiring
Attention:
- Wiring work should be manipulated by certified technicians.
- Wrong connection could damage the controller and the loads. Power supply to pin 7,8 for ZL-62x0A, pin 5, 6 for ZL-62x0A+ to check the controller. If there is a multimeter, check the outputs, as well as input, by the help of settings.
- Sensor and input signal wires should not be laid together with power supply wire, and even in same pipe. Sensor wire is better as short as possible. Not wind the redundant length wire to electrical noise equipment.
- The loads should be within the specification of the controller output driving ability. If using ac/dc module as load, or tungsten lamp, or motor, following the below requirements to avoid surging current damaging or shorten the life time of the controller outputs:
- For ac/dc module as load, the rated current should be no more 1/10th of output specification under pure resistance.
- For tungsten lamp as load, the rated current should be no more 1/15th of output specification under pure resistance.
- For motor, the rate current should be no more 1/5th of output specification under pure resistance.
- Don't touch inside components.
- Avoid installing controller in the following environment: More wet than 90%RH, or easily dew; Vibrating, or will be shocked; Possible sprayed; Under erosive air; Under explosive air.
Wiring Diagram for ZL-6210A+
Terminal Descriptions:
- 1, 2: R1: Temp. Output 30A/250V~ (N1, L1)
- 3, 4, 5, 6: Power Supply (L, N for 220V~)
- 7, 8: Alarm Input
- 9, 10: Temp. Sensor
5. Operation
5.1 Set Set-Point
- Keep the S button depressed for 3 seconds to enter into the setting status. The current set-point value will display.
- Press ▲ or ▼ to set the value (keeping depressed allows for fast setting).
- Press S again to exit the setting status and save the setting.
Note: The setting status will exit, and the setting will not be saved, if there is no key operation within 30 seconds.
5.2 Set Parameters
- Keep the P button depressed for 3 seconds; the display will show "00".
- Press ▲ or ▼ to input the password (range 00-99).
- Press S to confirm: If the password is correct, you will enter the parameter setting status. Otherwise, "Err" will be displayed, and the unit will exit.
- In parameter setting status: Press ▲ or ▼ to select the parameter code.
- Press S to display the value of the code.
- Press ▲ or ▼ to set the value.
- Press S to return to parameter code selection.
- Keep P depressed for 3 seconds to exit parameter setting status and save the settings.
Note: The parameter setting status will exit, and the settings will not be saved, if there is no key operation for 30 seconds.
6. Parameter Code Table
| Code | Function | Range | Remark | Default |
|---|---|---|---|---|
| U10 | Minimum time for R1 to keep de-energized | 0 ~ 100 min | 3 | |
| U11 | Minimum time for R1 to keep energized | 0 ~ 100 min | 3 | |
| U12 | Frequency for R1 to be on / off | 0 ~ 8 | 0: disable | 5 |
| U20 | Sensor calibration | -9.9 ~ +9.9°C | 0.0 | |
| U22 | Hysteresis for temp. control | 0.1 ~ +10.0°C | U22 < U54, U55 | 1.0 |
| U30 | Defrost period | 0 ~ 180 hour | 0: never defrost | 12 |
| U31 | Defrost time | 1 ~ 180 min | 30 | |
| U33 | Dripping water time | 0 ~ 180 min | 5 | |
| U34 | Overtemp. alarming delay after defrosted | 0 ~ 180 hour | 0: disable | 2 |
| U35 | Defrost after online | 0 / 1 | 0: disable / 1: enable | 0 |
| U36 | Delay for defrost after online | 0 ~ 180 min | 0 | |
| U38 | Defrost method | 0 / 1 | 0: by heater, 1: by hot gas | |
| U52 | Over temp. alarming delay | 0 ~ 180 min | 30 | |
| U53 | 1st over temp. alarming delay | 0 ~ 180 hour | 0: disable | 2 |
| U54 | Hysteresis for high temp. alarming | U22 ~ 60.0°C / OFF | OFF (> 60.0°C): disable alarming | OFF |
| U55 | Hysteresis for low temp. alarming | U22 ~ 60.0°C / OFF | OFF (> 60.0°C): disable alarming | OFF |
| U60 | External input warning mode | 0 ~ 4 | 0: disable, 1: NO locked, 2: NO unlocked, 3: NC locked, 4: NC unlocked | 0 |
| U61 | Delay for external input warning | 0 ~ 120 min | 0 | |
| U62 | Buzzing alarming | 0 / 1 | 0: no alarming / 1: enable alarming | 0 |
| U90 | Control mode | CO: cool / HE: heat | CO | |
| U99 | Password | 00 ~ 99 | 11 |
7. Control Functions
7.1 Cooling Control (U90 = C0)
7.1.1 Temperature control
- If Troom ≥ Set-point + U22, and R1 has been de-energized for U10, then R1 energized.
- If Troom ≤ Set-point, and R1 has been energized for U11, then R1 de-energized.
Example: If set-point = 18, U22 = 0.2, then the controller will control the temperature between 18.2°C and 18.0°C.
7.1.2 Forced cooling
Keep ▲ depressed for 5 seconds to force R1 energized under following conditions:
- R1 has been de-energized for U10.
- Troom is between (Set-point + U22) and (Set-point).
- Not in defrosting and dripping water status.
The forced cooling will finish, R1 will be de-energized, when Troom arrives at Set-point.
7.1.3 Stop forced cooling
During forced cooling, if R1 has been energized for U11, keeping ▼ depressed for 5 sec. will stop forced cooling.
7.2 Heating Control (U90 = HE)
7.2.1 Temperature control
- If Troom ≤ Set-point - U22, and R1 has been de-energized for U10, then R1 will be energized.
- If Troom ≥ Set-point, and R1 has been energized for U11, then R1 will be de-energized.
Example: If set-point = 18, U22 = 0.2, then the controller will control the temperature between 17.8°C and 18.0°C.
7.2.2 Forced heating
Keep ▲ depressed for 5 seconds to force R1 energized under following conditions:
- R1 has been de-energized for U10.
- Troom is between (Set-point - U22) and (Set-point).
The forced heating will finish, R1 will be de-energized, when Troom reaches Set-point.
7.3 Delay Protection
- After power supplied, R1 could be energized after U10.
- After R1 de-energized, it could be energized again after U10.
- After R1 energized, it could be de-energized again after U11.
7.4 Protecting Run (Function Disabled when U12 = 0)
When sensor fails, R1 will be energized and de-energized periodically.
- For every 30 minutes, R1 will be energized for U12* 3 minutes, de-energized for (30-U12*3) minutes.
Example: U12 = 2, if sensor fails, R1 will be energized for 2*3 = 6 min., de-energized for 30 -2 * 3 = 24 min., periodically.
7.5 Defrost
7.5.1 Periodically defrost
When R1 has been energized for U30, defrost for U31.
Note: After defrosted, start dripping water for U33. R1 keeps de-energized during dripping water.
7.5.2 Forced defrost
During non-defrost status, keeping ▲ depressed for 7 seconds will start forced defrost. When defrosted, start dripping water.
When defrosting, keeping ▼ depressed for 7 seconds will stop defrost, and start dripping water.
7.5.3 Dripping water after defrosted
After defrosted, start dripping water for U33. R1 keeps de-energized during dripping water.
7.5.4 Left time of defrost or dripping water
When defrosting or dripping water, press ▲ will show the left time.
Attention: If the key is kept depressed for 7 seconds, it will switch the defrost status.
7.6 Beeping
There will be a short beep for normal key press, a long beep for confirmation of setting, and three short beeps for error operation.
When there is failure, or external warning input: If U62 = 0, no beep warning. If U62 = 1, there will be continuous warning beeping.
The warning will stop if you press P, or the warning condition disappears.
7.7 Over Temperature Alarming
When Troom ≥ Set-point + U54, there will be high temperature alarming if the following conditions meet.
When Troom ≤ Set-point – U55, there will be low temperature alarming if the following conditions meet.
- If power just supplied, and U53 has passed.
- The Troom keeps the up condition for U52.
- If just defrosted, and U34 has passed.
Note: Over temperature alarming does not affect the temperature control and defrost process.
7.8 External Warning Input
- NO: normal open. If open, no warning; if closed, warning.
- NC: normal close. If closed, no warning; if open, warning.
- Locked: Warning keeps after the external warning disappeared. Press P to stop warning.
- Unlocked: Warning stops after the external warning disappeared.
Note: When there is external warning, the output(s) will be de-energized.
7.9 Sensor Calibration
The sensor can be calibrated by U20.
7.10 Restore to Factory Default Settings
Keep P and ▲ depressed simultaneously for 5 sec, there will be a beep, and "UnL" displays.
Press S twice, there will be a beep, all settings will be restored to factory default settings.
8. Display and Indicators
8.1 Sign Icons
| Icon | Function | On | Off | Blinking |
|---|---|---|---|---|
| Temp. control output (R1) | R1 energized | R1 de-energized | Within protecting delay | |
| Defrost | Defrosting | Not defrosting now | Dripping water | |
| Work mode | Cooling mode | Setting set-point | ||
| Work mode | Heating mode | Setting set-point | ||
| Maintenance | --- | No failure | Has failure | |
| A | Alarm | --- | No alarm | Alarming |
8.2 Character Displays
| Display | Remark |
|---|---|
| E01 | Sensor failure (short or open) |
| Hi | Room temp. is higher than the high limit |
| Lo | Room temp. is lower than the low limit |
| EE | Memory error |
| Err | Password error |
| ¡A | External warning |
| dEF | Defrosting |
| UnL | Parameters Will restore to factory default settings |
8.3 Display after power supplied
Upon power-up, the controller will display all segments, model, and version one by one (e.g., ZL-62X0A, then ZL-62X0A+ (P = plus)).
9. Troubleshooting
- E01 Error: This indicates a sensor failure (short or open circuit). Check the sensor connection and the sensor itself. Ensure it is properly connected to terminals 9 and 10.
- Settings Not Saving: If settings are not saved after power cycling, ensure you press the 'S' button to confirm and exit the setting status. The unit will exit without saving if there is no key operation for 30 seconds.
- Display Glitches: If the display shows incorrect segments or combines modes, check the power supply stability and ensure the unit is installed in a suitable environment (avoiding high humidity, vibration, or corrosive air).
- Incorrect Temperature Readings: Calibrate the sensor using parameter U20 if readings are inaccurate.
10. User Tips
- Sensor Diameter: The NTC sensor typically has a diameter of 6mm.
- High Power Loads: For loads exceeding 3kW (e.g., 6kW heaters), it is highly recommended to use an external contactor or relay to switch the load, rather than directly connecting it to the controller's output. This prevents damage to the controller's internal relay.
- Sensor Type for Specific Applications: For smokehouses or environments with high temperatures, a metal-cased sensor is often preferred for durability and better response. For liquid temperature control, a 'Water' type sensor is suitable.
- Sensor Cable Length: The included sensor cable is typically 1.5 to 2 meters long. It can be extended if needed, as it uses a simple two-wire connection.
- Accuracy: The controller offers good accuracy (typically 1%-3% error) and allows for calibration via parameter U20 to fine-tune readings.
- Hysteresis Setting: The hysteresis (U22) can be set to as low as 0.1°C for precise temperature control, useful in applications like incubators.
- Power Options: While the main specification lists 185-245Vac, 110Vac versions are available and function correctly for regions using that voltage.
11. Certifications
The ZL-6210A+ Temperature Controller complies with international standards for quality and safety.
CE Certification
ISO Certification
12. Warranty and Support
For detailed warranty information and technical support, please refer to the official product documentation or contact the manufacturer directly. Always ensure proper installation and usage as described in this manual to maintain product validity.
13. Product Overview Video
Watch this short video for a 360-degree view of the ZL-6210A+ Digital Temperature Controller.