Eastron SDM630MCT-MV

Contents

Eastron SDM630MCT-MV Three Phase DIN Rail Energy Meter User Manual

Model: SDM630MCT-MV

Multifunction Meter, 0.333V CT Connected, 220V/230V

1. Introduction

The Eastron SDM630MCT-MV is an advanced three-phase multi-function energy meter designed for DIN rail mounting. It operates with RS485 333mV CT (Current Transformer) connections and is suitable for monitoring energy consumption and various other electrical parameters in 220V/230V systems. This unit requires an auxiliary power supply (AC or DC) for operation and is compatible with 333mV input CTs. It features built-in pulse and RS485 Modbus RTU outputs, providing versatile data communication capabilities. The SDM630MCT-MV has been assessed and certified by RCM by SAA, with the instrument traceable number SAA220473.

Front view of the Eastron SDM630MCT-MV energy meter
Figure 1: Front view of the SDM630MCT-MV meter.

2. Product Features

  • CT & PT operated for comprehensive measurement.
  • Equipped with 2 Pulse Outputs and RS485 Modbus for data integration.
  • Supports bi-directional measurement, suitable for various energy flow scenarios.
  • Compact 4-module wide design (72mm) for DIN rail mounting.
  • Capable of multi-measurement, including kWh, kvarh, W, Var, VA, PF (Power Factor), Hz (Frequency), dmd (Demand), V (Voltage), etc.
  • Compatible with 3P4W (Three Phase 4 Wire), 3P3W (Three Phase 3 Wire), and 1P2W (Single Phase 2 Wire) systems.
Eastron SDM630MCT-MV meter with a current transformer (CT)
Figure 2: SDM630MCT-MV meter shown with a compatible Current Transformer (CT).

3. Specifications

General Specifications

Attribute Value
Model NumberSDM630MCT-MV
Dimensions72mm * 94.5mm
Operating Temperature-25°C to 55°C
Rated Voltage230V
Output Voltage230V
Max Operating Current150A & Above
Accuracy ClassBetter than class 1.0
Measuring Energy Range0-9999999.9
PhaseThree Phase
Power SupplyAC
Display TypeLCD
DIY SuppliesElectrical
Battery IncludedNo
High-concerned chemicalNone

Electrical Characteristics

Parameter Description/Value
Type of MeasurementRMS including harmonics on three phase AC system (3P4W)
Measurement ActivityPower, Active Energy, Reactive Energy, Voltage, Current, Frequency, Power Factor
StandardsIEC 62053-21 Class 1.0, IEC 62053-23 Class 2.0

Input & Output

Parameter Description/Value
CT Primary1-9999A
CT Secondary333mV
Voltage Input230V L-N / 120V L-N
OutputSDM630MCT w/RS485 Series, 2 Pulse Output + RS485 Modbus

Modbus Communications

Parameter Description/Value
ProtocolRS485 and MODBUS RTU
Device ID1-247
Transmit Distance1000m Maximum
ParityNone (default), Odd, Even
Response Time<100 ms
Table of detailed product parameters including electrical characteristics, input/output, and Modbus communications
Figure 3: Detailed Product Parameters.

4. Installation and Setup

The SDM630MCT-MV is designed for DIN rail mounting. Ensure proper electrical safety procedures are followed during installation. Refer to the wiring diagram and dimensions below for correct setup.

4.1 Wiring Diagram

Wiring diagram for the SDM630MCT-MV meter showing connections for voltage inputs L1, L2, L3, N, and current transformer inputs
Figure 4: Wiring Diagram. This diagram illustrates the connections for voltage inputs (L1, L2, L3, N) and current transformer inputs. Ensure all connections are secure and follow local electrical codes.

4.2 Dimensions

Dimensional drawing of the SDM630MCT-MV meter showing height 94.5mm, width 72mm, and depth 65mm
Figure 5: Dimensions of the SDM630MCT-MV meter (72mm width, 94.5mm height). The image provides a detailed view of the meter's physical size for installation planning.

5. Operating Instructions

Once installed and powered, the SDM630MCT-MV will display various electrical parameters on its LCD screen. Use the navigation buttons (U/I, M, Up, Down, P, E) on the front panel to cycle through different measurement values such as kWh, kvarh, W, Var, VA, PF, Hz, dmd, and V. Specific button functions for menu navigation and parameter viewing are typically detailed in the full product datasheet.

Close-up views of the SDM630MCT-MV meter's display, connection terminals, and DIN rail latch
Figure 6: Detail Display showing LCD and control buttons.

6. Maintenance

The Eastron SDM630MCT-MV is designed for reliable, long-term operation with minimal maintenance. Keep the device clean and free from dust and moisture. Periodically check all wiring connections to ensure they remain secure. No user-serviceable parts are inside. For any issues, refer to the troubleshooting section or contact support.

7. Troubleshooting

If the meter is not displaying readings or functioning as expected, consider the following:

  • No Display: Check the auxiliary power supply connections and ensure the voltage is within the specified range.
  • Incorrect Readings: Verify that the CT connections are correct (polarity and phase) and that the CT ratio setting (if configurable) matches the installed CTs. Ensure the meter is correctly configured for your system type (3P4W, 3P3W, 1P2W).
  • Communication Issues (RS485 Modbus): Check RS485 wiring for correct polarity (A/B), termination resistors, and ensure the Modbus ID, baud rate, and parity settings match the master device.

For complex issues, it is recommended to consult the full datasheet or contact technical support.

8. User Tips

  • Datasheet Access: For detailed technical specifications, Modbus register maps, and advanced configuration instructions, download the official datasheet from the Eastron website: www.eastrongroup.com.
  • Modbus Protocol: If you plan to integrate the meter with a Modbus system, ensure you obtain the Modbus protocol instruction and register map from Eastron support for seamless integration.

9. Certifications

The Eastron SDM630MCT-MV complies with various international standards and directives, ensuring quality and safety.

Certifications for the Eastron SDM630MCT-MV including HTW Test Verification, SGS EU Directive, Occupational Health and Safety, RoHS, and CE
Figure 7: Product Certifications. Includes HTW Test Verification of Conformity, SGS EU Directive 2014/30/EU, Occupational Health and Safety Management System, and Certificate of Compliance (RoHS, CE).

10. Warranty and Support

10.1 Warranty

This product comes with an 18-month warranty from the date of purchase. Please retain your proof of purchase for warranty claims.

10.2 Technical Support

For technical assistance, inquiries about Modbus protocol instructions, or any other support needs, please contact Eastron customer service. Contact details can typically be found on the official Eastron website.

11. Frequently Asked Questions (FAQ)

Q: What is the difference between MID and non-MID meters?
A: The Measuring Instruments Directive (MID) is a directive introduced by the European Commission. MID approval is required for any electrical meters used for billing purposes in Europe. For CT meters with MID approval, the CT ratio can only be set once.
Q: Where can I get a Datasheet?
A: The datasheet can be downloaded from our official website: www.eastrongroup.com.
Q: What is the warranty period for your products?
A: Our products typically come with an 18-month warranty.
Q: Can you provide Modbus protocol instructions or a Modbus register map?
A: Yes, we can. Please contact us, and we will be happy to assist you with the necessary documentation.
Illustration of a person with a laptop and large FAQ letters, representing frequently asked questions
Figure 8: Frequently Asked Questions.
Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.