1. Introduction
The YHDC SCT024TS is an industrial split-core current transformer designed for precise power monitoring and energy metering applications. It offers a wide rated input range from 50A to 400A, with output options of 1A or 5A, and an accuracy of 0.5% or 1%. This device is suitable for various low-to-high current scenarios in factories, PV plants, and commercial buildings.
Its split-core design allows for tool-free and wire-cutting-free installation, significantly reducing downtime and installation time compared to traditional non-split current transformers.

2. Key Features
- Wide Input Range: Covers 50A to 400A, suitable for diverse current monitoring needs.
- Easy Installation: 180° full split latch with safety buckle allows for tool-free, wire-cutting-free, single-person installation in approximately 30 seconds.
- High Accuracy: Available with 0.5% or 1% accuracy for precise measurements.
- Durable Construction: Features a laminated silicon steel core for low magnetic loss and 3.5KV dielectric strength.
- Dust Protection: IP00 waterproof grade.
- Global Compliance: CE Certified and meets GB20840-2014 standard, ensuring no export barriers to EU, China, and Southeast Asia markets.
- Stable Operation: 0.35mm thin sheets ensure stable current measurement even during long-term AC 50Hz, 1min operation, safe for high-voltage industrial grids.
3. Specifications
General Technical Index
- Mounting Type: Free hanging (In-Line)
- Material of Core: Laminated silicon steel
- Applicable Standard: GB20840-2014
- Operating Temperature: -25°C to +60°C
- Storage Temperature: -30°C to +90°C
- Frequency Range: 50Hz-60Hz
- Waterproof Grade: IP00
- Dielectric Strength:
- Input (bare conductor)/Output: AC 800V/1min 50Hz
- Output/Housing: AC 3.5KV/1min 50Hz
- Weight: 204g
Electrical Parameters (5A Output Type)
| Rated Input | Rated Output | Turns Ratio | Accuracy | Power |
|---|---|---|---|---|
| 100A | 5A | 1:20 | 0.5% / 1% | 0.1VA / 0.5VA |
| 150A | 5A | 1:30 | 0.5% / 1% | 0.1VA / 0.5VA |
| 200A | 5A | 1:40 | 0.5% / 1% | 1VA / 2.5VA |
| 250A | 5A | 1:50 | 0.5% / 1% | 1VA / 2.5VA |
| 300A | 5A | 1:60 | 0.5% / 1% | 1VA / 2.5VA |
| 400A | 5A | 1:80 | 0.5% / 1% | 1VA / 2.5VA |
Electrical Parameters (1A Output Type)
| Rated Input | Rated Output | Turns Ratio | Accuracy | Power |
|---|---|---|---|---|
| 50A | 1A | 1:50 | 1% / 0.5% | 0.5VA |
| 100A | 1A | 1:100 | 1% / 0.5% | 1VA |
| 200A | 1A | 1:200 | 1% / 0.5% | 1.5VA |
| 300A | 1A | 1:300 | 1% / 0.5% | 2VA |
| 400A | 1A | 1:400 | 1% / 0.5% | 2VA |
Dimensions (in mm±0.5)


4. Installation
The SCT024TS is designed for easy and quick installation, typically achievable by a single person in 30 seconds without the need for specialized tools or cutting wires.
Installation Steps:
- Ensure Safety: Before installation, ensure the power line or equipment where the current transformer will be installed is de-energized to prevent electrical hazards.
- Open the Latch: Locate the 180° full split latch on the current transformer. Gently press the safety buckle and open the transformer.
- Position the Transformer: Place the open current transformer around the conductor (wire) you wish to measure. Ensure the conductor passes through the center of the transformer's opening.
- Close the Latch: Close the transformer until the safety buckle securely latches. Verify that the transformer is firmly closed around the conductor and there are no gaps.
- Connect Output Wires: Connect the output screw terminals of the current transformer to your monitoring or metering device. Refer to the wiring diagram on the product or in the specifications section for correct polarity (IP and OL terminals).
- Verify Connection: Double-check all connections to ensure they are secure and correctly wired.
- Restore Power: Once installation is complete and verified, restore power to the system.
Important Note: The secondary circuit of the current transformer is NOT allowed to be open-circuited while the primary circuit is energized. This can lead to dangerously high voltages across the secondary terminals.
5. Operation
The YHDC SCT024TS Split Core Current Transformer functions by inducing a proportional current in its secondary coil based on the current flowing through the primary conductor. This induced current can then be measured by compatible monitoring or metering equipment.
Typical Applications:
- Current measurement and monitoring for electrical wiring and equipment.
- Power and energy measurement for electric motors, lighting, air compressors, heating and ventilation systems, air-conditioning equipment, and automation-control systems.
- Integration into current, power, and energy monitoring devices.
- Use in relay protection devices.
- Applications in charging piles and data centers.
Once installed, the current transformer continuously provides current signals to the connected device, enabling real-time monitoring and data collection.
6. Maintenance
The SCT024TS current transformer is designed for long-term, reliable operation with minimal maintenance. Adhering to the following guidelines will help ensure its longevity and performance:
- Regular Inspection: Periodically inspect the physical condition of the transformer, including the housing, latch, and terminal connections. Ensure there are no signs of damage, corrosion, or loose connections.
- Environmental Conditions: Ensure the operating environment remains within the specified temperature range (-25°C to +60°C) and humidity levels.
- Dust Protection: The device has an IP00 waterproof grade, meaning it offers no special protection against water ingress. While it has some dust protection, avoid excessive dust accumulation, especially around the terminals. Clean gently with a dry, soft cloth if necessary.
- Avoid Mechanical Stress: Do not subject the transformer to excessive mechanical stress, impact, or vibration, which could compromise its integrity or accuracy.
- Terminal Security: Ensure the screw terminals remain tight to maintain good electrical contact.
7. Troubleshooting
If you encounter issues with your SCT024TS current transformer, consider the following common problems and solutions:
- No Output or Incorrect Readings:
- Check Connections: Verify that the output terminals are correctly wired to your monitoring device and that all connections are secure. Incorrect polarity can lead to negative or erroneous readings.
- Primary Current Flow: Ensure there is actual current flowing through the primary conductor.
- Device Compatibility: Confirm that your monitoring device is compatible with the 1A or 5A output of the current transformer.
- Open Secondary Circuit: Ensure the secondary circuit is not open while the primary is energized. This is critical for safety and proper operation.
- Physical Damage:
- Inspect the housing and latch for any cracks or damage. If the core is exposed or damaged, the transformer may need replacement.
- Inconsistent Readings:
- Interference: Check for strong electromagnetic interference from nearby equipment that might affect readings.
- Overload: Ensure the primary current does not exceed the rated input of the transformer.
For persistent issues, contact technical support for further assistance.
8. User Tips
- For optimal accuracy, ensure the primary conductor is centered within the transformer's opening.
- Always double-check the wiring diagram for correct terminal connections (IP and OL) to ensure proper current direction sensing.
- When selecting a current transformer, choose a model with a rated input current that matches or slightly exceeds the maximum expected current in your application for best performance and safety.
9. Warranty and Support
YHDC provides a 1-year warranty for the SCT024TS Split Core Current Transformer. This warranty covers manufacturing defects and ensures the product meets its specified performance criteria under normal use.
For technical support, troubleshooting assistance, or warranty claims, please contact YHDC customer service. Our technical team is available to provide support and guidance for any issues encountered during use.
Contact Information: Refer to the official YHDC website or your purchase documentation for the most current support contact details.