1. Product Overview
The YHDC SCT016T-D is a split core current transformer designed for non-invasive measurement of AC current. It provides galvanic separation between the primary AC current circuit and the secondary DC output circuit, ensuring safety and reliability. This device is ideal for applications requiring current monitoring without interrupting the main circuit.

The transformer features a safety lock buckle for easy installation and a built-in rectifier with screw terminal output. It is available in various input current ratings (30A, 50A, 60A, 80A, 100A) and corresponding voltage outputs (1V, 3V, 5V DC) with an accuracy of 1%.
2. Setup and Installation
Installation of the SCT016T-D is designed to be straightforward due to its split-core design, allowing for placement without disconnecting the primary conductor.
2.1 Installation Steps
- Open the Buckle: Gently press the safety lock buckle to open the transformer's core.
- Clip the Wire: Position the primary conductor (the wire carrying the current to be measured) within the opening of the transformer.
- Fasten the Buckle: Close the transformer, ensuring the safety lock buckle clicks securely into place.
- Connect Cables: Connect the secondary output terminals to your measurement or monitoring device using appropriate cables. Refer to the wiring diagram for correct polarity.


2.2 Wiring Diagram
The schematic diagram below illustrates the voltage output type and connection points. Ensure the secondary is NOT short-circuited.

2.3 Visual Installation Guide
For a visual demonstration of the installation process, please watch the following video:
Video 1: YHDC SCT016T-D Split Core Current Transformer Installation Guide.
3. Operating Instructions
Once installed and wired correctly, the SCT016T-D will provide a DC voltage output proportional to the AC current flowing through the primary conductor. This voltage signal can then be read by a compatible measurement device, such as a multimeter, data logger, or PLC.
3.1 Measurement Principle
The split core current transformer operates on the principle of electromagnetic induction. The AC current in the primary conductor creates a magnetic field, which is concentrated by the ferrite core. This magnetic field induces a current in the secondary winding, which is then converted into a proportional DC voltage output by the built-in rectifier circuit.
3.2 Output Interpretation
The output voltage (1V, 3V, or 5V DC) corresponds to the maximum rated input current (30A, 50A, 60A, 80A, or 100A) for the specific model. For example, if you have a 100A/5V DC model, a 5V output indicates 100A flowing through the primary conductor. Lower currents will result in proportionally lower voltage outputs.
Important Safety Note: The secondary circuit of the current transformer must NEVER be short-circuited. Doing so can lead to dangerous high voltages and damage the device.
4. Maintenance
The YHDC SCT016T-D is designed for long-term, reliable operation with minimal maintenance. Follow these guidelines to ensure optimal performance and longevity:
- Cleaning: Keep the exterior of the current transformer clean and free from dust, dirt, and moisture. Use a soft, dry cloth for cleaning. Avoid using abrasive cleaners or solvents.
- Inspection: Periodically inspect the device for any signs of physical damage, such as cracks in the housing or damage to the safety lock buckle. Ensure the screw terminals are tight and connections are secure.
- Environmental Conditions: While the device has an IP00 waterproof grade, it is recommended to avoid exposing it to excessive moisture, corrosive environments, or extreme temperatures outside its specified operating range.
- No User-Serviceable Parts: The internal components of the current transformer are not user-serviceable. Do not attempt to open or repair the device, as this will void the warranty and may cause damage or injury.
5. Troubleshooting
If you encounter issues with your SCT016T-D current transformer, consider the following troubleshooting steps:
- No Output or Incorrect Readings:
- Verify that the primary conductor is correctly positioned within the transformer's core and that the safety lock buckle is fully closed.
- Check all wiring connections to ensure they are secure and correctly match the schematic diagram (Figure 4).
- Confirm that the secondary circuit is NOT short-circuited. This is a critical safety and operational requirement.
- Ensure the input AC current is within the rated range of your specific SCT016T-D model.
- Verify that your measurement device is properly configured to read DC voltage and is compatible with the transformer's output range (1V, 3V, or 5V).
- Intermittent Readings:
- Check for loose connections at the screw terminals or within your measurement setup.
- Ensure the primary conductor is stable and not moving within the transformer's core.
- Physical Damage:
- If the housing is cracked, the buckle is broken, or there is any other visible damage, discontinue use immediately. Contact support for assistance.
6. Specifications
The following table details the technical specifications for the YHDC SCT016T-D Split Core Current Transformer:
| Feature | Specification |
|---|---|
| Model Number | SCT016T-D |
| Coil Structure | Split core current transformer |
| Coil Number | Current transformer |
| Phase | SINGLE |
| Input Current Range | 30A, 50A, 60A, 80A, 100A |
| Output Voltage Options | 1V, 3V, 5V DC |
| Accuracy | 1% |
| Mounting Type | Free hanging (In-Line) |
| Core Material | Ferrite |
| Housing Material | Flame-retardant ABS Injection Shell |
| Operating Temperature | -25ºC ~ +60ºC |
| Storage Temperature | -30ºC ~ +90ºC |
| Frequency Range | 50Hz-1KHz |
| Waterproof Grade | IP00 |
| Dielectric Strength (Input/Output) | AC 800V/1min 50Hz |
| Dielectric Strength (Output/Housing) | AC 3.5KV/1min 50Hz |
| Weight | 70g |
| Certification | CE |
6.1 Dimensions
Dimensions are provided in millimeters (mm) with a tolerance of ±0.5mm.

7. Warranty and Support
YHDC is committed to providing high-quality products and excellent customer service.
- Warranty: The SCT016T-D Split Core Current Transformer comes with a 1-year warranty from the date of purchase, covering manufacturing defects.
- Technical Support: Should you encounter any issues or require technical assistance during the use of your product, please contact our support team. We aim to provide timely replies within 24 hours and offer comprehensive technical support.
- Contact Information: For support, please refer to the seller's contact information or visit the official YHDC website at www.poweruc.com.
8. User Tips
- Proper Sizing: Always ensure the selected current transformer's input current range (e.g., 30A, 50A, 100A) matches or exceeds your application's maximum expected current to maintain accuracy and prevent saturation.
- Secure Installation: After clipping the primary wire, double-check that the safety lock buckle is fully closed and secured. A loose connection can lead to inaccurate readings or potential hazards.
- Avoid Secondary Short Circuits: As a critical safety measure, never short-circuit the secondary output terminals. This can generate dangerously high voltages and permanently damage the transformer or connected equipment.
- Environmental Considerations: Although robust, the device is rated IP00. For outdoor or harsh industrial environments, consider additional protective enclosures to shield it from excessive moisture, dust, and extreme temperatures.
- Calibration: For highly precise applications, periodic calibration of your entire measurement system (including the current transformer and reading device) is recommended to ensure continued accuracy.