PowMr POW-SunSmart SP5.2K

Contents

POW-SunSmart SP5.2K Hybrid Solar Inverter User Manual

Model: POW-SunSmart SP5.2K | Brand: PowMr

1. Introduction

1.1 Product Overview and Features

The POW-SunSmart series is a new all-in-one hybrid solar charge inverter that integrates solar energy storage, charging energy storage, and AC sine wave output. Utilizing DSP control and an advanced control algorithm, it offers high response speed, reliability, and industrial-grade performance.

Key features include:

  • Support for inverter and mains power hybrid output, including operation without a battery.
  • Two output modes: mains bypass and inverter output for uninterrupted power supply.
  • Four optional charging modes: Only Solar, Mains Priority, Solar Priority, and Mains & Solar hybrid charging.
  • Advanced MPPT technology with an efficiency of 99.9% for maximum power point tracking.
  • Designed with an LCD screen and 3 LED indicators for dynamic display of system data and operating status.
  • Time slot control for prioritizing mains and battery usage based on local peak and valley tariffs.
  • Power saving mode to reduce no-load loss.
  • Intelligent variable speed fan for efficient heat dissipation and extended system life.
  • Lithium battery activation by PV solar or mains, compatible with lead-acid and lithium batteries.
  • Comprehensive 360° all-around protection, including short circuit, over/under voltage, overload, and reverse protection.
  • Supports parallel operation of up to 6 units, allowing for a maximum combined AC output of 30KW.
  • Wide PV input voltage range of 120-500Vdc, with a single unit accommodating a maximum 5500W PV array.
  • Fast switching time of 10ms.
  • Multiple communication interfaces: RS485, USB, and Dry Contact.

1.2 Basic System Introduction

A complete system typically consists of the following components:

  1. PV module: Converts light energy into DC power to charge the battery or directly invert to AC power for loads.
  2. Mains or generator: Connected at the AC input to power the load and charge the battery. If not connected, the system can operate using battery and PV power.
  3. Battery: Ensures normal power supply when solar energy is insufficient or mains is disconnected.
  4. Household load: Connects various household and office appliances.
  5. All-in-one solar charge inverter: The central energy conversion unit.
Connection Diagram for POW-SunSmart SP5.2K Hybrid Solar Inverter
Figure 1: Basic System Connection Diagram. Shows connections for Solar Panels (PV Input), Mains Power/Generator (AC Input), 48V Battery, and Home Loads (AC Output). Max. AC charging current 0-40A, Charge voltage range 40-58Vdc, AC input voltage range 0-140Vac, AC output power 5000W, Single phase/split phase/three phase Output (120/208/240V AC output), 48V Lead acid or lithium battery (Minimum starting voltage 44V), Maximum charge current 100A, Support batteryless mode, Max PV input current 22A, Max PV input power 5500W, Max PV open circuit voltage 500VDC.
Video 1: Product Overview of the POW-SunSmart SP5.2K Hybrid Solar Inverter, highlighting its 110/120V AC output, 5000W AC output power, parallel capability up to 6 units (30KW), 120-500V PV input voltage range, 5500W max PV input power, power-saving mode, time-of-use charging/discharging, lithium battery activation, and multiple protection mechanisms.

2. Important Safety Instructions

Please read all instructions and cautions in this manual carefully before installation and use. Failure to follow these instructions may result in electric shock, fire, or severe injury.

  • Non-safety voltage exists inside the all-in-one solar charge inverter. Do not disassemble the unit. Contact professional maintenance personnel for repairs.
  • Keep the inverter out of reach of children.
  • Do not install the inverter in harsh environments (moist, oily, flammable, explosive, or heavily dusty areas).
  • The mains input and AC output are high voltage; do not touch the wiring terminals.
  • The inverter housing can be hot during operation; avoid touching it.
  • Do not open the terminal protective cover when the inverter is operating.
  • Attach appropriate fuses or circuit breakers to the PV array, mains, and battery terminals.
  • Always disconnect fuses or circuit breakers near PV array, mains, and battery terminals before installing or adjusting wiring.
  • After installation, ensure all wire connections are tight to prevent heat accumulation from poor connections.
  • The all-in-one solar charge inverter is off-grid. It must be the sole input device for the load. Do not use it in parallel with other AC power sources to avoid damage.
  • When installing batteries, wear safety goggles. If battery acid contacts skin, rinse immediately with clean water.
  • Do not place metal objects near the battery to prevent short circuits.
  • Ensure good ventilation as acid gas may be generated during battery charging.
  • Leave sufficient space around the inverter for heat dissipation. Do not install the inverter and lead-acid battery in the same cabinet to prevent corrosion.
  • Only charge batteries that meet the inverter's requirements.
  • Poorly connected or corroded wires can cause excessive heat, melting insulation, and potential fires. Ensure connections are tight and wires are secured.
  • System connection wires should be selected for a current density not exceeding 5A/mm².
  • Avoid direct sunlight and rainwater infiltration for outdoor installations.
  • High voltage may remain inside the unit even after power-off. Do not open or touch internal components until capacitors are fully discharged.
  • Ensure correct battery polarity; reversed polarity can damage the device.
  • Do not touch the fan when it is working.

3. Setup and Installation

3.1 Select the Mount Location

Determine the installation position on a wall surface. Ensure at least 200mm of space to the left and right air outlets for natural convection heat dissipation. A minimum of 500mm clearance above and below the unit is recommended.

Installation Diagram with Clearance Requirements
Figure 2: Recommended clearances for installation. 500mm above and below, 200mm on sides.

WARNING: Danger of explosion! Never install the all-in-one solar charge inverter and lead-acid battery in the same confined space, or in a confined place where battery gas may collect.

3.2 Preparation

Before connecting any wiring, remove the bottom cover of the inverter.

3.3 Wiring Specifications and Circuit Breaker Selection

All wiring and installation must comply with national and local electrical codes.

PV Input Wiring

Models Recommended PV wiring diameter Maximum PV input current Recommended circuit breaker type
POW-SunSmart SP5.2K 6mm²/10AWG 22A 2P-25A

Note: The voltage in series shall not exceed the maximum PV input open circuit voltage.

AC Input Wiring

Models Recommended AC input wiring diameter Maximum bypass input current Recommended circuit breaker type
POW-SunSmart SP5.2K 10mm²/7AWG 63A 2P-63A

Note: An appropriate circuit breaker is already present at the Mains input wiring terminal; no additional one is needed.

Battery Input Wiring

Models Recommended battery wiring diameter Rated battery discharge Maximum charge current Recommended circuit breaker type
POW-SunSmart SP5.2K 30mm²/2AWG 125A 100A 2P-200A

AC Output Wiring

Models Recommended AC output wiring Rated inverter AC output current Maximum bypass output current Recommended circuit breaker type
POW-SunSmart SP5.2K 10mm²/7AWG 42A 63A 2P-63A

Note: Wiring diameter is for reference only. Use thicker wires for longer distances to reduce voltage drop. Always select appropriate wiring and circuit breakers based on actual situations.

3.4 Connection Procedures

Before proceeding, ensure the external circuit breaker is open and wires are of sufficient thickness.

AC Input/Output Wiring

  1. Connect the ground wire first, then the live wire (L), and finally the neutral wire (N) according to the terminal positions. The ground wire should be as thick as possible (≥4mm²) and connected to the grounding screw hole on the cabinet via an O-type terminal.
  2. Repeat the process for AC output wiring.
AC Input and Output Wiring Diagram
Figure 3: Detailed view of AC input and output wiring terminals. Ensure correct polarity and secure connections.

PV Input Wiring

  1. Disconnect the external circuit breaker before wiring.
  2. Connect the PV input wires (PV+ and PV-) according to the terminal positions. For parallel connections, each inverter requires a dedicated PV array or source.
PV Input Wiring Diagram
Figure 4: PV input wiring terminals. Connect PV+ to positive and PV- to negative.

Battery Wiring

  1. Disconnect the external circuit breaker before wiring.
  2. Connect the battery wires (BAT+ and BAT-) using O-type terminals (6mm inner diameter recommended) to ensure firm contact and prevent overheating.
Battery Wiring Diagram
Figure 5: Battery wiring terminals. Connect BAT+ to positive and BAT- to negative.

WARNING: Mains input, AC output, and PV array generate high voltage. Be extremely careful during wiring. Do not close circuit breakers or fuses until all connections are secure and correct. Install an external lightning arrester at the PV input terminal in areas with frequent lightning.

3.5 Final Assembly and Start-Up

  1. Verify all wiring is correct and firm, especially battery and PV input polarities, and AC input connection. Install the terminal cover.
  2. Close the circuit breaker at the battery terminal.
  3. Turn the rocker switch on the left side of the machine to the "ON" state. The "AC/INV" indicator will flash, indicating normal inverter operation.
  4. Close the circuit breakers of the PV array and the Mains.
  5. Turn on AC loads one by one. Start with loads having large surge currents, then smaller ones, to avoid protection actions from simultaneous high load. The inverter will now operate according to its set mode.

NOTICE: If the inverter does not work properly or the LCD/indicator is abnormal, refer to the Troubleshooting section.

4. Operating Instructions

4.1 Operating Modes

Charging Modes

  • Solar First: Prioritizes PV charging. Mains charging only starts if PV fails. Ideal for maximizing solar energy use and in regions with high feed-in tariffs.
  • Mains First: Prioritizes Mains Power charging. PV charging only starts if Mains fails.
  • Hybrid Charging: Combines PV MPPT charging with Mains Power. Mains supplements if PV energy is insufficient, and stops when PV is sufficient. Suitable for unstable grids, providing backup power.
  • Only Solar: Exclusively PV charging, no mains charging. Battery power comes solely from solar energy. Most energy-efficient mode for good daylighting conditions.
Charging Modes Diagram
Figure 6: Visual representation of the four charging modes: Solar First, Mains First, Hybrid Charge, and Only Solar.

Output Modes

  • Solar First: PV and battery power the load. Switches to Mains Power if PV fails. Maximizes solar energy use while maintaining battery power, suitable for stable grids.
  • Mains First: Inverter power supply only when Mains Power fails (backup UPS). Used in regions with unstable power grids.
  • Inverter First: Inverter supplies power from the battery until it reaches under-voltage, then switches to Mains Power. Maximizes DC energy use.
  • Hybrid Output and Grid Connection: In utility bypass state, if no battery is connected or battery is full, load power is supplied by PV and utility. Surplus PV energy can be fed back to the grid if enabled.
Output Modes Diagram and Peak-Valley Tariff
Figure 7: Visual representation of the four output modes and a graph illustrating Peak-Valley Electricity Tariff management for sectional charging and discharging functions.

4.2 LCD Screen Operating Instructions

The inverter features a backlight LCD screen display and 3 LED indicators for dynamic display of system data and operating status.

Smart LCD Screen Display
Figure 8: Smart LCD Screen with labels for Solar Power, Mains Power Parameters, PV Parameters, Mains/Generator Power, Inverter Work State, Indicator Light, Load Percentage, Home Load, Battery Type, Battery Capacity, Battery Parameters, Real-time time, date, total PV power generation, total load power, Normal Work, Load Parameters.

Operation Buttons

  • Menu/Enter/Exit Settings: Access and exit the settings menu.
  • Page Number/Option Increase: Navigate through pages or increase parameter values.
  • Page Number/Option Decrease: Navigate through pages or decrease parameter values.
  • OK/Enter Options: Confirm selections within the settings menu.

Indicator Lights

Indicator Light Color Description
AC/INV Yellow Normally On: Mains Power output
Flicker: Inverter output
CHARGE Green Flicker: The battery is being charged.
Normally On: The charging is completed.
FAULT Red Normally On: Fault status

Real-time Data Viewing

On the LCD main screen, use the navigation buttons to view real-time data such as PV voltage, battery voltage, AC voltage, load voltage, currents, power, temperatures, and various status indicators.

Setup Parameters Description

The inverter allows configuration of various parameters including:

  • Supply Priority Mode (AC1ST, BT1ST, PV1ST, Mix load default)
  • Output Frequency (50.0Hz, 60.0Hz)
  • AC Input Voltage Range (UPS default, APL)
  • Battery to Mains Switch Voltage
  • Mains to Battery Switch Voltage
  • Charging Mode (Hybrid default, ONLYPV)
  • Maximum Charging Current (0-100A)
  • Battery Type (USER, SLd, FLd, GEL, LFP14/15/16, NCM13/14, No battery)
  • Boost Voltage, Float Charge Voltage, Over-discharge Voltage, Over-discharge Delay Time, Battery Under-voltage Alarm Point
  • Equalization Charge settings (ENA/DIS, Voltage, Time, Delay)
  • ECO Mode (ENA/DIS)
  • Overload Automatic Restart (ENA/DIS)
  • Auto Restart Upon Over-temperature (ENA/DIS)
  • Buzzer Alarm (ENA/DIS)
  • Mode Change Reminder (ENA/DIS)
  • Inverter Overload to Bypass (ENA/DIS)
  • Current of Charging Under Grid Electricity (0-40A)
  • RS485 Address (1-254)
  • AC Output Mode (SIG default, PAL, 2P0/2P1/2P2, 3P1/3P2/3P3)
  • BMS Communication Protocol (PAC, RDA, AOG, OLT, HWD, DAQ, WOW, SRNE, PYL, UOL, WEILAN)
  • Battery Under-Voltage Recovery Point, Max PV Charger Current, Battery Recharge Recovery Point
  • AC Output Rated Voltage (120Vac default, settable to 100/105/110/120Vac)
  • Charge Current Limiting Method (LC SET, LC BMS, LC INV)
  • Sectional Charging/Discharging Functions (start/end times for 3 sections)
  • Leakage Protection Function (ENA/DIS)
  • Stop Charging Current, Discharge Alarm SOC Setting, Cut-off Discharge SOC Settings
  • Switch to Mains SOC Settings, Switch to Inverter Output SOC Settings
  • Battery Hybrid Discharge Current

Refer to the detailed tables in the PDF manual (pages 25-40) for specific parameter ranges and default values.

5. Other Functions

5.1 Dry Contact

The dry contact can control the ON/OFF of a diesel generator to charge the battery. Normally, the NC-N point is closed and NO-N is open. When battery voltage reaches low disconnection point, the relay energizes, closing NO-N and opening NC-N. NO-N can drive resistive loads: 125VAC/1A, 230VAC/1A, 30VDC/1A.

5.2 RS485 Communication Port

The RS485 port has two functions:

  1. RS485-2: Allows direct communication with an optional host computer for monitoring and parameter setting.
  2. RS485-1/RS485-2: Connects to an optional RS485 to WiFi/GPRS communication module for monitoring via a mobile app.

RS485-1 Pinout: Pin 1 (5V power), Pin 2 (GND), Pin 7 (RS485-A1), Pin 8 (RS485-B1).

RS485-2 Pinout: Pin 1 (5V power), Pin 2 (GND), Pin 7 (RS485-A2), Pin 8 (RS485-B2).

5.3 USB Communication Port

This port is for USB communication with optional PC host software. Install the "USB to serial chip CH340T driver" on your computer to use this port.

5.4 Parallel Communication Function (Parallel Operation Only)

This port enables communication between parallel inverter modules. Each inverter has two DB15 ports (one male, one female). Connect the male connector of one inverter to the female connector of another. Do not connect a male connector to its own female connector.

Parallel Communication Port Diagram
Figure 9: Male and Female DB15 connectors for parallel communication.

5.5 Current Sharing Detection Function (Parallel Operation Only)

This port detects current sharing among parallel modules. Each inverter has two current sharing detection ports. Either port can be used for connection; no specific wiring order is mandatory. Ensure red and black current sharing lines are not manually exchanged and connections are tightened to prevent abnormal operation.

Current Sharing Detection Port Diagram
Figure 10: Current sharing detection ports.

5.6 Parallel Installation Guide

The inverter supports parallel connection of up to six units. When using parallel operation, ensure the DB15 parallel communication line and current sharing detection line are firmly and reliably connected and locked with screws.

Parallel Connection Precautions

  • Battery Wiring: For single or split phase, ensure all inverters are connected to the same battery with correct polarity (BAT+ to BAT+, BAT- to BAT-), using the same wiring length and diameter.
  • AC OUT Wiring: For single phase, ensure L-to-L, N-to-N, and PE-to-PE connections for all inverters, with same wiring length and diameter. For split phase, ensure N-to-N and PE-to-PE. L lines of inverters connected to the same phase must be connected together, but L lines of different phases cannot be joined.
  • AC IN Wiring: For single phase, ensure L-to-L, N-to-N, and PE-to-PE connections. Ensure a single, consistent AC source input. For split phase, ensure N-to-N and PE-to-PE. L lines of inverters connected to the same phase must be connected together, but L lines of different phases cannot be joined.
  • Parallel Communication Line: Use a shielded DB15 cable. Follow a "one-in-one-out" rule (male connector of one to female of another). Tighten screws to prevent loose connections.
  • Current Sharing Detection Line: Use a twisted connection line. Follow a "one-in-one-out" rule. Do not manually exchange red and black lines. Tighten screws.
  • Always refer to the wiring diagrams for specific configurations (Single Phase, Two Phase, Three Phase).
  • If adding a new inverter to an existing parallel system, disconnect battery input, PV input, AC input, and AC output, and power off all inverters before reconnecting.
Parallel Connection Diagrams
Figure 11: Examples of parallel connection for 2, 3, and 6 inverters in single, three, and split-phase configurations.

Detailed schematic diagrams for parallel connection in single, two, and three phases are provided in the full PDF manual (pages 55-67).

6. Maintenance

To ensure optimal long-term performance, perform the following checks twice a year:

  • Ensure airflow around the unit is not blocked. Clean any dirt or debris from the heat sink.
  • Inspect all exposed wires for damage (sunlight, friction, pests, dryness). Repair or replace damaged wires.
  • Verify consistency between indications and display with device operation. Address any displayed faults or errors.
  • Check all wiring terminals for corrosion, insulation damage, signs of high temperature or discoloration. Tighten screws as needed.
  • Check for dirt, nesting insects, and corrosion. Clean as required.
  • If the arrester has failed, replace it promptly to prevent lightning damage.

WARNING: Danger of electric shock! Disconnect all power supplies and ensure all capacitors are discharged before performing any maintenance.

The manufacturer is not liable for damages caused by improper use, exceeding voltage ratings, operating outside temperature limits, unauthorized disassembly/repair, or force majeure.

7. Troubleshooting

7.1 Protections Provided

The inverter is equipped with various protections to ensure safe and stable operation:

  • PV current/power limiting protection
  • PV night reverse-current protection
  • Mains input over/under voltage protection
  • Battery over voltage protection
  • Battery low voltage protection
  • Load output short circuit protection
  • Heat sink over temperature protection
  • Overload protection
  • PV reverse polarity protection
  • AC reverse protection (off-grid mode)
  • Bypass over current (built-in AC input overcurrent protection circuit breaker)
  • Battery input over current protection
  • Battery input protection (internal fuse)
  • Charge short protection
  • CAN communication loss protection (parallel operation)
  • Parallel connection error protection
  • Parallel battery voltage difference protection
  • Parallel AC voltage difference protection
  • Parallel current sharing fault protection
  • Synchronization signal fault protection

7.2 Fault Codes and Handling Measures

The LCD screen will display fault codes if an issue occurs. Refer to the table below for common fault codes and their remedies.

Fault Code Fault Name Remedy
Display Off No display on the screen Check if battery PV air switch is closed, if switch is ON, press any button to exit sleep mode.
【01】 Battery undervoltage protection Charge battery until it returns to low voltage disconnection recovery voltage.
【06】 Battery overvoltage protection Measure battery voltage, turn off PV array and Mains AC switches.
【09】 PV overvoltage Use multimeter to check if PV input voltage exceeds maximum allowable rated voltage.
【13】 Bypass overload protection Reduce power equipment usage. Restart unit.
【14】 Inverter overload protection Reduce power equipment usage. Restart unit.
【17】 Inverter short circuit protection Check load connection, clear short-circuit points. Re-power to resume output.
【19】 Heat sink over temperature protection When device cools to recovery temperature, normal charge/discharge resumes.
【21】 Fan failure Check if fan is turning or blocked by foreign object.
【35】 Parallel ID setting error Check if parallel ID number setting is repeated.
【37】 Parallel current sharing fault Check if parallel current sharing line is connected well (loose/wrong connection).
【39】 Inconsistent AC input source in parallel mode Check if parallel AC inputs are from the same input interface.
【40】 Parallel connection fault Check if parallel line is connected well (loose/wrong connection).
【42】 Inconsistent system firmware version in parallel mode Check if software version of each inverter is consistent.
【58】 BMS communication error Check communication line and BMS setting.

8. Technical Specifications

Models POW-SunSmart SP5.2K
Parallel Mode
Permitted parallel number 1~6
AC Mode
Rated input voltage 110/120Vac
Input voltage range (90Vac~140Vac) ± 2%
Frequency 50Hz/60Hz (Auto detection)
Frequency Range 47±0.3Hz~55±0.3Hz (50Hz); 57±0.3Hz~65±0.3Hz (60Hz)
Overload/short circuit protection Circuit breaker
Efficiency >95%
Conversion time (bypass and inverter) 10ms (typical)
AC reverse protection Available
Maximum bypass overload current 63A
Inverter Mode
Output voltage waveform Pure sine wave
Rated output power 5200VA/5200W
Power factor 1
Rated output voltage 120Vac (100/105/110Vac Settable)
Output voltage error ± 5%
Output frequency range 50Hz±0.3Hz; 60Hz±0.3Hz
Maximum Efficiency >92%
Overload protection (102% < load < 110%) ±10%: report error and turn off output after 5 minutes; (110% < load < 125%) ±10%: report error and turn off output after 10 seconds; (Load > 125% ±10%): report error and turn off output after 5 seconds.
Peak power 10400VA
Loaded motor capability 4HP
Rated battery input voltage 48V (Minimum starting voltage 44V)
Battery voltage range Undervoltage alarm/shutdown voltage/overvoltage alarm/overvoltage recovery... settable on LCD screen
Power saving mode self-consumption Load ≤ 50W
AC Output (Grid)
Rated Output Power 5200W
Max. apparent power 5200VA
Max. output current 41.7A
Rated voltage 120Vac
Frequency 50Hz/60Hz
AC Charging
Battery type Lead acid or lithium battery
Maximum charge current (can be set) 0-40A
Charge current error ± 3Adc
Charge voltage range 40-58Vdc
Short circuit protection Circuit breaker and blown fuse
Circuit breaker specifications 63A
Overcharge protection Alarm and turn off charging after 1 minute
PV Charging
Maximum PV open circuit voltage 500Vdc
PV operating voltage range 120-500Vdc
MPPT voltage range 120-450Vdc
Battery voltage range 40-60Vdc
Maximum PV input power 6000W
Maximum PV input current 22A
PV charging current range (can be set) 100A
Charging short circuit protection Blown fuse
Wiring protection Reverse polarity protection
Hybrid charging Max charger current specifications (AC charger + PV charger)
Max charger current (can be set) 100A
Certified specifications
Certification CE(IEC62109-1)
EMC certification level EN61000
Operating temperature range -10°C ~ 55°C
Storage temperature range -25°C ~ 60°C
Humidity range 5% to 95% (Conformal coating protection)
Noise ≤60dB
Heat dissipation Forced air cooling, variable speed of fan
Communication interface USB/RS485(WiFi/GPRS)/Dry contact control
Dimension (L*W*D) 446.9mm*350mm*133mm
Weight 14kg

9. User Tips

  • Always ensure proper ventilation around the inverter to prevent overheating, especially when running at high loads or in parallel configurations.
  • Regularly check all wiring connections for tightness and signs of wear or corrosion to maintain optimal performance and safety.
  • Familiarize yourself with the LCD display and indicator lights to quickly identify the system's status and any potential issues.
  • When configuring battery types, ensure the settings match your specific battery chemistry (e.g., LiFePO4, Lead-Acid) to prevent damage and optimize charging.
  • For parallel systems, double-check all communication and current sharing lines to ensure stable and balanced operation.

10. Warranty and Support

For technical support, warranty claims, or any inquiries regarding your POW-SunSmart SP5.2K Hybrid Solar Inverter, please contact the manufacturer directly.

SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD

  • Tel/Fax: +86 755-28219903
  • Email: support@powmr.com
  • Website: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

Please have your product model and serial number ready when contacting support.