PowMr POW-SunSmart 12KL3

Contents

PowMr POW-SunSmart 12KL3 Three-Phase Solar Hybrid Inverter

Model: POW-SunSmart 12KL3

User Manual

1. Introduction

The PowMr POW-SunSmart L3 series, including the 12KL3 model, is an advanced solar energy storage inverter designed for integrating solar power, utility charging, and energy storage with AC sine wave output. Utilizing DSP control, it offers high response speed, reliability, and industrial-standard performance through sophisticated control algorithms.

PowMr Hybrid Solar Inverter front view
Figure 1.1: PowMr POW-SunSmart 12KL3 Hybrid Solar Inverter

2. Safety Instructions

This chapter contains important safety instructions. Read and keep this manual for future reference. Always comply with local requirements and regulations during installation and operation.

2.1 Symbols Used in This Manual

  • DANGER: Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
  • WARNING: Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
  • CAUTION: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
  • NOTICE: Provides tips on product operation.

2.2 General Safety Precautions

  • DANGER: High Voltage. Turn off the switch of all power sources before and during installation to avoid electric shock.
  • For optimal operation, select appropriate cable sizes and necessary protective devices as specified.
  • Do not connect or disconnect any connections while the inverter is operating.
  • Do not open the terminal cover while the inverter is operating.
  • Ensure the inverter is properly grounded.
  • Be careful not to cause short-circuiting of the AC output and DC input.
  • Do not disassemble this unit. All repairs and maintenance must be performed by a professional service center.
  • Never charge a frozen battery.

3. Package Contents

Upon unpacking, verify that all items are present and undamaged. The package typically includes:

  • PowMr POW-SunSmart 12KL3 Hybrid Solar Inverter Unit
  • User Manual (PDF version available online)
  • Mounting hardware (screws, expansion bolts)
  • Parallel communication cable (for parallel models)
  • Cable lugs and ferrules (may vary)
  • Warranty Card and Inspection Report
Package contents including inverter, manual, and accessories
Figure 3.1: Typical Package Contents

4. Setup and Installation

4.1 Selecting the Mount Location

The POW-SunSmart L3 series can be used outdoors (protection degree IP20). Consider the following:

  • Choose a solid wall for installation.
  • Mount the inverter at eye level.
  • Ensure adequate cooling space around the inverter.
  • Ambient temperature should be between -10°C to 55°C (14°F to 131°F) for optimal operation.

DANGER: Do not install near flammable materials, in explosive areas, or in confined spaces with lead-acid batteries.

CAUTION: Avoid direct sunlight and humid environments.

4.2 Mounting the Inverter

Drill 4 mounting holes in the wall according to the specified dimensions. Insert 2 expansion screws above and 2 M5 screws below to secure the inverter.

4.3 Removing Terminal Protection Cover and Dust Screen

Use a screwdriver to remove the terminal protection cover and dust screen. Periodically clean the dust screen, especially in areas with poor air quality, to prevent overheating faults.

4.4 System Connection Overview

A complete system consists of PV modules, a utility grid or generator, a battery bank, home loads, and the inverter. The actual cabling depends on your specific application scenario.

Comprehensive System Connection Diagram
Figure 4.1: System Connection Diagram (Generator, Main Power, Solar Panels, AC Output, Battery, PV Input, AC Input)

4.5 Cable and Circuit Breaker Requirements

Ensure all cables are properly sized and circuit breakers meet the specifications below. Use a stripper to remove 6-8mm of insulation and fix ferrules or cable lugs as appropriate.

PV Input

ModelCable DiameterMax. PV Input CurrentCircuit Breaker Spec
12KW Model5mm² / 10 AWG22A2P-25A

AC Input

ModelOutput ModeMax. CurrentCable DiameterCircuit Breaker Spec
12KW ModelThree-phase35A9mm² / 6 AWG (L1/L2/L3/N)4P-40A

Battery

ModelCable DiameterMax. PV Input CurrentCircuit Breaker Spec
12KW Model50mm² / 1 AWG260A2P-300A

AC Output

ModelOutput ModeMax. CurrentCable DiameterCircuit Breaker Spec
12KW ModelThree-phase17.4A5mm² / 10 AWG (L1/L2/L3/N)4P-32A

DANGER: Before connecting AC Input/Output, Battery, or PV, ensure the circuit breaker is disconnected. Verify cable size is sufficient to prevent hazards.

4.6 Wiring Connections

  • AC Input & Output: Connect live, neutral, and ground cables as shown in the diagram (refer to Figure 4.1).
  • Battery Connection: Connect positive and negative battery cables. Ensure correct polarity.
  • PV Connection: Connect positive and negative wires from PV strings. Ensure PV open-circuit voltage does not exceed 800V.
  • Dry Contact Connection: Insert communication cable into the dry junction port (0.2-1.5mm² cross-section).
  • Grounding Connection: Securely connect the earth terminal to the grounding busbar. Grounding wire should be at least 4mm².

4.7 Final Assembly and Start-up

  1. After verifying all wiring is correct and secure, restore the terminal protection cover.
  2. Close the circuit breaker of the battery.
  3. Press the ON/OFF switch on the bottom of the inverter. The screen and indicator lights will illuminate, indicating activation.
  4. Sequentially close the circuit breakers for PV, AC input, and AC output.
  5. Start the loads one by one, from smallest to largest power consumption.

5. Operation

5.1 Display Panel and Controls

The inverter features an LCD screen, three LED indicators, and four touchable keys for operation and monitoring.

LCD HD Display Screen with control buttons and status indicators
Figure 5.1: LCD HD Display Screen and Controls

Touchable Keys

  • Menu/Enter: To enter/exit the setting menu.
  • Up/Increase: To navigate to the next selection or increase a value.
  • Down/Decrease: To navigate to the last selection or decrease a value.
  • OK/Confirm: To confirm/enter the selection in the setting menu.

LED Indicators

  • AC/INV (Green): Solid for utility bypass output, flashing for inverter output.
  • CHARGE (Yellow): Solid for charging complete, flashing for charging in progress.
  • FAULT (Red): Flashing indicates a fault has occurred.

5.2 Operating Modes

The inverter supports various operating modes for AC output and battery charging.

AC Output Modes

  • Utility Priority (UTI): Inverter switches to battery/PV only when utility is outaged.
  • Solar and Utility Hybrid (MIX LOD): Solar and utility supply power to the load simultaneously (when battery is full or not connected).
  • Solar Priority (SOL): PV powers load first, then charges battery. Battery supplements if PV is insufficient. Switches to mains if PV is ineffective or battery is low.
  • Inverter Priority (SBU): PV powers load first. Battery supplements if PV is insufficient. Switches to utility if battery is low.

Battery Charging Modes

4 Charging Modes diagram
Figure 5.2: Available Charging Modes
  • Solar First: Priority given to charging by PV. Mains charging starts only if PV fails.
  • Mains First: Priority given to charging by Mains Power. PV charging starts only if mains fails.
  • Hybrid Charging: PV and Mains Power charge simultaneously. PV MPPT charging is prioritized, with Mains Power supplementing if PV energy is insufficient.
  • Only Solar: Only PV charging is initiated; no mains charging.

5.3 Time-Slot Charging/Discharging Function

This function allows users to set different charging/discharging time slots based on local peak and valley electricity prices. This optimizes the use of utility power and PV energy, reducing electricity costs.

5.4 Settings

The inverter offers extensive settings configurable via the display panel. Key settings include AC output source priority, AC output frequency, battery voltage points for switching, battery charging mode, battery type, charging currents, various battery protection thresholds, power saving mode, alarm settings, and communication parameters. Refer to the detailed tables in the full PDF manual for all parameter IDs and descriptions.

6. Maintenance

To ensure optimum long-lasting performance, it is recommended to perform the following checks twice a year:

  • Ensure airflow around the inverter is not blocked and remove any dirt or debris from the radiator.
  • Check all exposed conductors for damage (sunlight, friction, dry rot, insects, rodents). Repair or replace as necessary.
  • Verify that indications and displays are consistent with equipment operation. Address any faults or incorrect displays.
  • Check all terminals for corrosion, insulation damage, high temperatures, or discoloration. Tighten terminal screws.
  • Clean for dirt, nesting insects, and corrosion. Clean insect screens regularly.
  • If the lightning arrester has failed, replace it promptly to prevent damage.

DANGER: Before any checks or operations, ensure the inverter is disconnected from all power sources and capacitors are fully discharged to avoid electric shock.

7. Troubleshooting

This section provides solutions for common issues. For detailed fault codes and remedies, refer to the comprehensive tables in the full PDF manual.

7.1 Common Issues and Solutions

Fault CodeMeaningCausesRemedy
/No screen displayNo power input, or ON/OFF switch is off.Check battery/PV breakers, ensure ON/OFF switch is ON.
01Battery under-voltageBattery voltage below set threshold.Charge battery until voltage is above threshold.
03Battery not connectedBattery not connected or BMS in protection.Check battery connections, breaker, and BMS communication.
14Inverter over-loadInverter output exceeds capacity.Reduce load. Inverter will resume after 3 mins (5 consecutive overloads will shut down).
21Fan failureHardware detects fan failure.Power off, check for blockages, manually toggle fan.

If you encounter product faults that cannot be solved by the methods above, contact customer support. Do not disassemble the equipment yourself.

8. Specifications

Below are the key technical specifications for the PowMr POW-SunSmart 12KL3 model.

8.1 General Features

Key features summary
Figure 8.1: Key Features of PowMr POW-SunSmart 12KL3
  • Rated Output Power: 12000W
  • Max. Peak Power: 24000W
  • Rated Output Voltage: 230/400Vac (three-phase)
  • Rated Frequency: 50/60Hz
  • Output Waveform: Pure sine wave
  • Switching Time: 10ms (typical)
  • Protection: 360° protection including short circuit, over current, over voltage, under voltage, over-load, backfill, over-temperature, over charge.

8.2 Detailed Specifications

CategoryParameterValue (POW-SunSmart 12KL3)
Inverter OutputRated Output Power12000W
Max. Peak Power24000W
BatteryBattery TypesLi-ion / Lead-Acid / User Defined
Rated Battery Voltage48Vdc
Voltage Range40-60Vdc
PV InputNo. of MPPT2
Max. Input Power9000W/9000W
Max. Open-circuit Voltage800Vdc/800Vdc
Utility / Generator InputInput Voltage RangePhase voltage 170~280V, Line voltage 305~485V
Bypass Overload Current35A
EfficiencyMPPT Tracking Efficiency99.9%
Max. Battery Inverter Efficiency≥92%
CommunicationInternal InterfaceRS485 / CAN / USB / Dry contact
External Module (optional)Wi-Fi / GPRS
GeneralProtection DegreeIP20, indoor only
Ambient Temp-10~55℃, >45℃ derated
Cooling MethodFan cooling
Model Comparison Table (POW-SunSmart 8KL3 vs 12KL3)
Figure 8.2: Model Comparison Table (POW-SunSmart 8KL3 vs 12KL3)

9. User Tips

  • Ensure all wiring connections are tight and secure to prevent intermittent operation or faults.
  • Regularly monitor the LCD display for real-time data and any fault codes to ensure optimal system performance.
  • When setting up parallel systems, carefully follow the specific wiring diagrams and cautions provided in the manual to avoid damage.

10. Frequently Asked Questions (FAQ)

Q: Can this inverter run without batteries?

A: Yes, the PowMr POW-SunSmart 12KL3 supports batteryless operation, allowing it to power loads directly from the PV array or AC grid.

Q: What types of batteries are compatible?

A: The inverter is compatible with 48V Lead-Acid batteries (AGM, GEL, FLD, SLD) and Lithium-ion batteries (Li-ion, LiFePO4). It also supports user-defined battery parameters.

Q: How many units can be paralleled?

A: Up to six units of the PowMr POW-SunSmart 12KL3 can be paralleled to increase system capacity.

Max Six Solar Inverter Parallel wiring diagrams
Figure 10.1: Parallel Connection Diagrams

11. Warranty and Support

The PowMr POW-SunSmart 12KL3 typically comes with an 18-month warranty. For warranty claims, technical support, or service, please contact the seller or PowMr customer service directly. Refer to your warranty card for specific terms and conditions.

SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
Tel/Fax: +86 755-28219903