Aninerel Hybrid Solar Inverter

Contents

Aninerel Hybrid Solar Inverter User Manual

Models: 2KW, 4.2KW, 6.2KW, 11KW

1. Introduction

This manual provides essential information for the assembly, installation, operation, and troubleshooting of your Aninerel Hybrid Solar Inverter. Please read it carefully before installation and operation, and keep it for future reference. This inverter is designed for both on-grid and off-grid needs, featuring a built-in MPPT controller for efficient solar energy harvesting and pure sine wave output for sensitive appliances.

Aninerel Hybrid Solar Inverter with LCD display and MPPT label
Aninerel Hybrid Solar Inverter, available in various power ratings.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  • To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  • To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • Only qualified personnel can install this device with a battery.
  • NEVER charge a frozen battery.
  • For optimum operation, please follow the required specifications to select appropriate cable sizes.
  • Be very cautious when working with metal tools on or around batteries. A potential risk exists for a tool to spark or short-circuit batteries or other electrical parts, which could cause an explosion.
  • Please strictly follow the installation procedure when disconnecting AC or DC terminals.
  • A fuse is provided as over-current protection for the battery supply.
  • GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations.
  • NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  • Only qualified service persons are able to service this device. If errors persist after troubleshooting, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Product Overview

The Aninerel Hybrid Solar Inverter is an all-in-one unit designed for comprehensive power management. It features a user-friendly interface and robust connectivity options.

Product Overview showing LCD display, function buttons, RGB indicator, power on/off switch, RS485, RS232, grounding, AC input, main out, second out, battery input, PV input.
Detailed view of the inverter's front panel and rear connections.

3.1. Components

  1. LCD display
  2. Function buttons (ESC, UP, DOWN, ENTER)
  3. RGB indicator
  4. Grounding terminal
  5. RS232 communication port
  6. RS485 communication port
  7. AC input terminals
  8. Main out terminals
  9. Second out terminals (available on 4.2KW, 6.2KW, 11KW models)
  10. Battery input terminals
  11. PV input terminals
  12. Power on/off switch

4. Setup and Installation

4.1. Unpacking and Inspection

Before installation, inspect the unit for any damage. Ensure the package contains:

  • The inverter unit x 1
  • User manual x 1 (PDF version available here)

4.2. Preparation

Before connecting any wirings, remove the bottom cover by unscrewing the two retaining screws.

Inverter with bottom cover removed, showing internal components and connection points.
Inverter with bottom cover removed for wiring access.

4.3. Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface (concrete or other non-combustible surface only).
  • Install at eye level for easy LCD display reading.
  • Ambient temperature should be between 0°C and 55°C for optimal operation.
  • Recommended installation position is vertically on a wall.
  • Ensure sufficient clearance around the unit for heat dissipation and wiring access.
Mounting dimensions for the inverter, showing 200mm clearance at top, 20cm on sides, and 50cm at bottom.
Recommended mounting clearances for proper ventilation.

4.4. Battery Connection

WARNING: All wiring must be performed by qualified personnel.

Install a separate DC over-current protector or disconnect device between the battery and inverter. Ensure correct polarity. Use appropriate cable sizes as per the table below:

ModelMaximum AmperageBattery CapacityWire SizeCable mm²Terminal Size (L x W x D)Torque Value
4.2KVA175A200AH1AWG5037 x 15.3 x 6.4 mm4~6 Nm
6.2KVA130A200AH2AWG3537 x 15.3 x 6.4 mm4~6 Nm

Steps:

  1. Make positive and negative cables based on recommended terminal size.
  2. Connect all battery packs as units require.
  3. Insert battery cable flatly into the battery connector of the inverter and ensure bolts are tightened with a torque of 4~6Nm. Verify correct polarity.

4.5. AC Input/Output Connection

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

Install a separate AC breaker between the inverter and the AC input power source. The recommended AC breaker spec is 50A. Do not mis-connect input and output connectors.

ModelGaugeTorque Value
4.2KVA10AWG1.4~1.6Nm
6.2KVA10AWG1.4~1.6Nm

Steps:

  1. Before making AC input/output connection, open the DC protector or disconnector.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities (Ground (yellow-green), L-LINE (brown or black), N-Neutral (blue)) and tighten terminal screws. Connect PE protective conductor first.
  4. Insert AC output wires according to polarities and tighten terminal screws. Connect PE protective conductor first.

4.6. PV Connection

WARNING: All wiring must be performed by qualified personnel.

Before connecting to PV modules, install a DC circuit breaker between the inverter and PV modules. Use appropriate cable sizes.

ModelTypical AmperageCable SizeTorque
4.2KVA27A10 AWG1.4~1.6 Nm
6.2KVA27A10 AWG1.4~1.6 Nm

When selecting PV modules, consider the following:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
PV Connection Diagram showing solar panels connected to the inverter, which is connected to the utility grid and a battery, supplying power to household appliances.
Typical PV connection diagram for a home solar system.

Steps for PV Module Wire Connection:

  1. Remove 6mm of insulation sleeve for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
  3. Ensure the wires are securely connected.

4.7. Final Assembly

After connecting all wirings, replace the bottom cover by screwing in the two screws.

5. Operation

5.1. Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the side of the case) to turn on the unit.

5.2. Operation and Display Panel

The front panel features an LCD display, three indicators, and four function keys to monitor operating status and input/output power information.

RGB IndicatorColorStateMessages
Inverter modeGreenSolid OnOutput is powered by battery or PV; battery is fully charged or not charged.
FlashingBattery is charging with 2s-on and 1s-off.
AC modeBlueSolid OnOutput is powered by AC or PV in AC mode; battery is fully charged or not charged.
FlashingBattery is charging with 2s-on and 1s-off.
Standby modeCyanSolid OnBattery is fully charged or not charged.
FlashingBattery is charging with 2s-on and 1s-off.
Fault modeRedSolid OnFault occurs in the inverter.
Bypass modePurpleSolid OnWorking in AC mode without charging.
Charging modeYellowSolid OnBattery is fully charged, when switch is off.
FlashingBattery is charging, when switch is off.
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3. LCD Display Description

The LCD display shows various information across five areas. Information can be switched by pressing the UP/DOWN keys.

  1. Area 1: PV data (voltage, current, power)
  2. Area 2: Battery data (voltage, current, power, SOC)
  3. Area 3: AC output data (voltage, current, power, percentage, frequency)
  4. Area 4: AC input data (voltage, current, power, percentage, frequency)
  5. Area 5: Setting program code, Eco mode, buzzer status, error, warning

LCD Data Polling Display Mode:

  • Simultaneously polling data: Press "UP" or "DOWN" to show all data from area 1-4 simultaneously. Press ESC to return to initial data.
  • Independent polling data: Press "ENTER" to make a circle icon flash, then use "UP" or "DOWN" to display data for that specific area. Repeat for other areas.

5.4. LCD Settings

To enter setting mode, press and hold the "ENTER" key for 3 seconds. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit. Key settings include:

  • Program 01: Output source priority (Utility first, Solar first, SBU priority, SUB priority, SUF priority)
  • Program 02: Maximum charging current (60A default)
  • Program 03: AC input voltage range (Appliances, UPS, Generator)
  • Program 05: Battery type (AGM, Flooded, User-Defined, LI2, LI4, LIB)
  • Program 06: Auto restart when overload occurs (Restart disable/enable)
  • Program 07: Auto restart when over temperature occurs (Restart disable/enable)
  • Program 08: Output voltage (220V, 230V, 240V)
  • Program 09: Output frequency (50Hz, 60Hz)
  • Program 10: Auto bypass (Manual/Auto)
  • Program 11: Maximum utility charging current (30A default)
  • Program 12: Setting voltage point back to utility source
  • Program 13: Setting voltage point back to battery mode
  • Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar)
  • Program 18: Buzzer mode (Mode1-4)
  • Program 19: Auto return to default display screen (Return to default/Stay at latest)
  • Program 20: Backlight control (Backlight on/off)
  • Program 23: Overload bypass (Bypass disable/enable)
  • Program 25: Modbus ID Setting (001-247)
  • Program 26: Bulk charging voltage (C.V voltage)
  • Program 27: Floating charging voltage
  • Program 29: Setting cut off voltage point or SOC percentage on the second output (OP2)
  • Program 31: Setting cut off voltage point or SOC percentage on the Main output (OP1)
  • Program 32: Bulk charging time (C.V stage)
  • Program 33: Battery equalization (Enable/Disable)
  • Program 34: Battery equalization voltage
  • Program 35: Battery equalized time
  • Program 36: Battery equalized timeout
  • Program 37: Equalization interval
  • Program 39: Equalization activated immediately (Enable/Disable)
  • Program 41: Automatic activation for lithium battery (Disable/Auto)
  • Program 42: Manual activation for lithium battery (Activation/Disable)
  • Program 43: OP2 Output Enable (Enable/Disable)
  • Program 46: Maximum discharge current protection
  • Program 47: Setting the OP2 overload warning point
  • Program 49: RGB mode - Checking RGB Indicator table (Mode 1-5)
  • Program 50: Lithium battery activation time

6. Maintenance

6.1. Battery Equalization

The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, extending battery life. It is recommended to equalize the battery periodically.

To apply equalization:

  1. Enable battery equalization in LCD setting program 33.
  2. Set the equalization interval in program 37, or activate immediately in program 39.

The controller will enter the Equalize stage when the set interval is reached or immediately activated. During this stage, the controller charges the battery until it reaches the equalization voltage, then maintains this voltage until the set equalized time is reached.

6.2. Lithium Battery Connection and Setting

If using a lithium battery, ensure it is a compatible model. Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter. This cable facilitates communication for advanced BMS control.

Setting for Lithium Battery without Communication:

If your lithium battery does not communicate via RS485, you must manually configure the inverter settings. It is recommended to set the battery type to "LIB" in program 05. Alternatively, you can manually set the following parameters based on your battery's BMS specifications:

  • Max charging voltage
  • Max charging current
  • Discharging protection voltage

Then, configure the following programs:

  • Program 05: Set battery type to "LIB".
  • Program 26: Set C.V voltage as Max charging voltage of BMS - 0.5V.
  • Program 27: Set floating charging voltage as C.V voltage.
  • Program 29: Set Low DC cut-off voltage as discharging protection voltage.
  • Program 02: Set Max charging current (must be less than the Max charging current of BMS).
  • Program 12: Set voltage point back to utility source when selecting "SBU priority". The value must be ≥ Low DC cut-off voltage + 2V.

Remark: It is best to complete these settings before turning on the inverter (only LCD display, no output). After finishing settings, restart the inverter.

7. Troubleshooting

This section provides guidance for common issues. For persistent problems, refer to the full PDF manual or contact customer support.

7.1. Fault Reference Code

Fault CodeFault Event
01Over temperature of inverter module
02Over temperature of DCDC module
03Battery voltage is too high
04Over temperature of PV module
05Output short circuited.
06Output voltage is too high.
07Overload time out
08Bus voltage is too high
09Bus soft start failed
10PV over current
11PV over voltage
12DCDC over current
13Over current or surge
14Bus voltage is too low
15Inverter failed (Self-checking)
18Op current offset is too high
19Inverter current offset is too high
20DC/DC current offset is too high
21PV current offset is too high
22Output voltage is too low
23Inverter negative power
24Op2 current offset is too high

7.2. Warning Indicator

Warning CodeWarning EventAudible Alarm
02Temperature is too HighBeep three times every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
14Fan blockedNone
15PV energy is lowBeep twice every 3 seconds
19Lithium Battery communication is failedBeep once every 0.5 second
21Lithium Battery over currentNone
22The load exceeds the set value of program 47None
E9Battery equalizationNone
b8Battery is not connectedNone

8. Specifications

The Aninerel Hybrid Solar Inverter is available in multiple power configurations. Please refer to the specific model's specifications below.

8.1. 2000W-12V-60A Model Specifications

Table of detailed specifications for the 2000W-12V-60A Aninerel Hybrid Solar Inverter, including input, output, battery, solar charger, and physical parameters.
Specifications for the 2000W-12V-60A model.

8.2. 4200W-24V-120A Model Specifications

Table of detailed specifications for the 4200W-24V-120A Aninerel Hybrid Solar Inverter, including input, output, battery, solar charger, and physical parameters.
Specifications for the 4200W-24V-120A model.

8.3. 6200W-48V-120A Model Specifications

Table of detailed specifications for the 6200W-48V-120A Aninerel Hybrid Solar Inverter, including input, output, battery, solar charger, and physical parameters.
Specifications for the 6200W-48V-120A model.

8.4. 11000W-48V-160A Model Specifications

Table of detailed specifications for the 11000W-48V-160A Aninerel Hybrid Solar Inverter, including input, output, battery, solar charger, and physical parameters.
Specifications for the 11000W-48V-160A model.

8.5. General Specifications (All Models)

Parameter4.2KVA6.2KVA
Operating Temperature Range-10°C to 55°C
Storage temperature-15°C ~ 60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm368x328x120
Net Weight, kg7.08.0

9. User Tips

  • Voltage Compatibility: This inverter is designed for 220V output. It is not suitable for 110V equipment. Please ensure your appliances match the inverter's output voltage.
  • Battery Type Selection: If using a lithium battery without RS485 communication, carefully follow the manual settings (Program 05, 26, 27, 29, 02, 12) to avoid issues. It's best to configure these settings before the inverter is fully operational.
  • Overload Protection: Pay attention to the overload warning indicators and reduce connected loads if necessary to prevent faults.

10. Warranty and Support

For detailed warranty information, please refer to the complete user manual (PDF) provided with your product. If you encounter any issues not covered in this manual or require further assistance, please contact Aninerel customer support or your local dealer.

You can view the full user manual in PDF format here.

11. Product Video

Watch this video for a visual overview of the Aninerel Hybrid Solar Inverter, including its features and a demonstration of battery connection.

Demonstration of the Aninerel Hybrid Solar Inverter's features and battery connection process.

© 2024 Aninerel. All rights reserved.