SONGGER ATDV-Y

Contents

ATDV-Y Dual Cycle Timer Relay

Instruction Manual

1. Introduction

The SONGGER ATDV-Y is a dual-cycle time delay relay designed for precise cyclic control in industrial automation systems. This device allows for alternating or repeating ON/OFF timing control with independently adjustable delay intervals. It is ideal for applications such as motor control, lighting systems, and equipment sequencing, ensuring continuous and reliable cyclic operation.

2. Specifications

ParameterValue
Product NameTime Delay Relay
ModelATDV-Y
Power SupplyAC 220V, 50/60Hz
Operation ModeCyclic Delay (Repeat ON/OFF Cycle)
Control Output5A at 250VAC (Resistive Load)
Delay Time Range3 seconds to 60 minutes (Adjustable)
Contact Configuration1 Normally Open (NO) + 1 Normally Closed (NC)
Contact LifeApprox. 1,000,000 operations
Repeat Accuracy≤1%
Mounting TypePanel-mounted / Built-in / Embedded
MaterialABS Housing with Metal Terminals
Operating Temperature-10°C to +50°C
EU LVD VoltageHigh voltage: Above 50Vac or 75Vdc
High-concerned chemicalNone
OriginMainland China

For detailed dimensions, please refer to the product diagram below:

ATDV-Y Timer Relay Dimensions

Image: ATDV-Y Timer Relay with dimensions showing 87mm (3.43in) height, 57.5mm (2.26in) width for the front panel, and 90mm (3.54in) depth for the body.

3. Package Contents

The package typically includes:

  • 1 x ATDV-Y Dual Cycle Timer Relay Unit
  • 1 x 8-pin Base Socket (if included with your purchase)

4. Safety Precautions

WARNING! Risk of Electric Shock!

  • Always ensure power is disconnected from the circuit before installation, wiring, or maintenance to prevent electric shock.
  • Installation and wiring must be performed by qualified personnel in accordance with local electrical regulations and safety standards.
  • Do not exceed the rated voltage (AC 220V) or load capacity (5A at 250VAC) to avoid damage or malfunction.
  • Avoid using the relay in environments with high humidity, excessive dust, corrosive gases, or extreme temperatures outside the specified operating range (-10°C to +50°C).
  • Do not adjust the rotary dials with excessive force, as this may cause mechanical damage.
  • This relay is not intended for use in safety-critical systems where failure could lead to injury or significant damage, unless proper redundancy and protection mechanisms are in place.
  • Keep out of reach of children.

5. Installation and Setup

5.1 Preparation

  1. Ensure the power supply available matches the relay's requirements: AC 220V, 50/60Hz.
  2. Verify that all components are present and undamaged.
  3. Familiarize yourself with the connection diagrams provided below and on the device itself.

5.2 Mounting

The ATDV-Y relay can be panel-mounted, built-in, or embedded. Secure the relay firmly into its compatible 8-pin base socket (if applicable) and then mount the base securely in your control panel or enclosure.

5.3 Wiring

Correct wiring is crucial for safe and proper operation. Refer to the connection diagrams carefully.

ATDV-Y Relay Connection Diagram on Device

Image: Close-up of the ATDV-Y relay showing the connection diagram on its side. The diagram indicates pins for AC power, DC power (not used for this model), and time delay contacts (5A 250VAC resistive load). Pins are numbered 1-8.

Normally Open Wiring Method

In this configuration, after power-on, the output is activated after the set delay time.

Normally Open Wiring Diagram

Image: Wiring diagram for Normally Open operation. A circuit breaker (DZ47-63 C32) is connected to the relay base (pins 7 and 8 for power). The relay's output (pins 6 and 5) controls a contactor (e.g., 1810). Example: If ON knob is set to 6 seconds and OFF knob to 3 seconds, after power-on, the circuit stays off for 6 seconds, then outputs for 3 seconds, repeating this cycle.

Normally Closed Wiring Method

In this configuration, after power-on, the output is activated immediately and disconnects after the set delay time.

Normally Closed Wiring Diagram

Image: Wiring diagram for Normally Closed operation. A circuit breaker (DZ47-63 C32) is connected to the relay base (pins 7 and 8 for power). The relay's output (pins 6 and 5) controls a contactor (e.g., 1810). Example: If ON knob is set to 6 seconds and OFF knob to 3 seconds, after power-on, the output stays on for 6 seconds, then off for 3 seconds, repeating this cycle.

6. Operation

The ATDV-Y features two rotary dials for independent ON and OFF time settings.

ATDV-Y Relay Front Panel Overview

Image: Front panel of the ATDV-Y relay showing two rotary dials labeled 'ON' and 'OFF', with scales from 0 to 6. Indicator lights for Power-On and Power-Off are also visible.

  1. Set ON Time: Turn the upper rotary dial (labeled 'ON') to set the desired energized duration. The scale typically ranges from 0 to 6, which corresponds to the selected time range (e.g., 0-3S, 0-60M).
  2. Set OFF Time: Turn the lower rotary dial (labeled 'OFF') to set the desired de-energized duration. The scale also ranges from 0 to 6.
  3. Apply Power: Once the desired ON and OFF times are set, apply AC 220V power to the relay. The device will automatically begin its cyclic operation according to the preset intervals.

6.1 Data Reading and Status Indication

  • Observe the indicator lights on the front panel to confirm the relay's status.
  • The relay will alternate between ON and OFF states based on the preset time intervals, with corresponding indicator lights illuminating.

7. Maintenance

  • Storage: Store the product in a dry, clean environment away from direct sunlight, moisture, and corrosive substances.
  • Cleaning: Keep the device free from dust and contaminants to ensure reliable operation. Clean the housing with a dry, soft cloth. Do not use solvents, abrasive cleaners, or liquids.
  • Inspection: Periodically check terminal connections for tightness and signs of corrosion. Ensure all wiring remains secure.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges.

8. Troubleshooting

ProblemPossible CauseSolution
Relay does not power onNo power supply; Incorrect wiring; Faulty power sourceCheck power connections and voltage; Verify wiring against diagram; Test power source
Incorrect timing or no cycleDials set incorrectly; Relay malfunction; Load issueRe-adjust ON/OFF dials; Test relay with a known good load; Consult support if malfunction persists
Output not switchingOverload; Incorrect load wiring; Damaged contactsEnsure load is within specifications; Check load wiring; Replace relay if contacts are damaged
Indicator lights not workingNo power; Internal faultCheck power supply; If power is present, relay may be faulty, consult support

9. User Tips

  • Automated Control Panels: This relay is well-suited for integration into automated control panels due to its accurate and easily adjustable timing functions.
  • Precise Adjustments: The dual rotary dials allow for quick and precise setting of ON and OFF times, making it convenient for fine-tuning your automation sequences.

10. Frequently Asked Questions (FAQ)

Q1: Can this relay control two machines alternately?
A1: Yes, it supports alternating operation between two devices as well as continuous cycling for a single device.
Q2: Is the delay time adjustable?
A2: Yes, the delay time can be adjusted from 3 seconds to 60 minutes using the rotary dials.
Q3: What is the operating voltage?
A3: It operates on AC 220V, 50/60Hz.
Q4: What type of contacts does it have?
A4: It has 1 Normally Open (NO) and 1 Normally Closed (NC) contact configuration.

11. Warranty and Support

For any technical assistance, warranty claims, or further inquiries, please contact your retailer or the manufacturer's customer support. Please have your product model number (ATDV-Y) and purchase details ready when contacting support.

A user manual in PDF format is also available for download from the product's official page or by contacting customer support.

12. Product Overview Video

Video: An overview of the SONGGER manufacturing process and various automation products, including the ATDV-Y timer relay in industrial settings.

© 2024 SONGGER. All rights reserved.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.