1. Introduction
The TOMZN TOVPD1-60-VA is an intelligent dual-display voltage and current protector designed for DIN rail mounting. This device automatically monitors the voltage and current in your circuit and will cut off the power supply instantaneously if it detects over-voltage, under-voltage, or over-current faults. This protects connected electrical equipment from potential damage. It features adjustable protection values and automatic recovery.

Figure 1: Front view of the TOMZN TOVPD1-60-VA device.
2. Safety Information
WARNING: To avoid danger of suffocation, keep any plastic packaging away from babies and children. Do not use this bag in cribs, beds, carriages, or playpens. This bag is not a toy.
- Always have a qualified electrical professional perform the installation and operation of this device.
- Do not place the device near flammable materials.
- Ensure adequate ventilation during operation to prevent overheating.
- Disconnect the device from power before performing any maintenance or adjustments.
- Store the device properly when not in use for extended periods.
3. Product Overview and Features
The TOVPD1-60-VA offers comprehensive protection and monitoring capabilities:
- Over-voltage Protection (OV): Automatically disconnects power if voltage exceeds set limit.
- Under-voltage Protection (UV): Automatically disconnects power if voltage drops below set limit.
- Over-current Protection (OCP): Automatically disconnects power if current exceeds set limit.
- Automatic Recovery: Device automatically restores power once conditions return to normal after a set delay.
- Voltage Display: Real-time display of current voltage (voltage measurement).
- Current Display: Real-time display of current draw (current measurement).
- Adjustable Parameters: All protection thresholds and delay times are user-adjustable.
- Voltage Calibration (A13): Allows for fine-tuning of voltage readings.

Figure 2: Key functions of the device including voltage display, over-voltage, under-voltage, current display, active time adjustable, and automatic recovery.
4. Setup
4.1. Unpacking
Carefully remove the device from its packaging. Inspect for any visible damage. If any damage is found, do not proceed with installation and contact your supplier.
4.2. Mounting
The TOVPD1-60-VA is designed for 35mm DIN rail installation.
- Locate a suitable position on your electrical panel's DIN rail.
- Align the device with the DIN rail and press firmly until it clicks into place.
- Ensure the device is securely mounted and does not wobble.

Figure 3: The device is designed for simple and convenient 35mm standard DIN rail installation and disassembly.
4.3. Wiring
IMPORTANT: All wiring must be performed by a qualified electrical professional. Ensure the main power supply is OFF before starting any wiring work.
- Identify the 'IN' (Input) terminals (N and L) and 'OUT' (Output) terminals on the device.
- Connect the incoming neutral (N) and live (L) power lines to the 'IN' terminals. When power is input through L and N, screw down to penetrate the insulating layer of the power lines.
- Connect the outgoing neutral (N) and live (L) lines to your load (e.g., circuit breaker, appliances) from the 'OUT' terminals.
- Ensure all connections are tight and secure to prevent loose contacts and potential hazards.

Figure 4: Easy wiring diagram showing connection between a power switch, the voltage protector, and an air circuit breaker.
5. Operating Instructions
5.1. Display Elements and Buttons

Figure 5: Front panel showing Volt Display, Current Display, Set button, Adjustment keys, Over Voltage indicator, Under Voltage indicator, Over Current indicator, and Power indicator.
- Volt Display: Shows the real-time voltage.
- Current Display: Shows the real-time current.
- >V (Red LED): Illuminates when an over-voltage condition is detected.
- <V (Red LED): Illuminates when an under-voltage condition is detected.
- >A (Red LED): Illuminates when an over-current condition is detected.
- POWER (Green LED): Illuminates when the device is powered on and operating normally.
- SET Button: Used to enter the parameter setting mode.
- Up/Down Adjustment Keys (Green Triangles): Used to navigate through settings and adjust values.
5.2. Setting Parameters
The device allows you to adjust various protection values and delay times. The operation of button setting is simple.
- Enter Setting Mode: Press and hold the SET button for a few seconds until the display starts flashing, indicating you are in setting mode.
- Navigate Settings: Use the Up and Down adjustment keys to cycle through the parameters (A1 to A13, and OFF).
- Adjust Values: When the desired parameter is displayed, press the SET button briefly to select it. Then use the Up and Down keys to change its value.
- Confirm Value: Press the SET button again to confirm the new value and move to the next parameter, or wait a few seconds for the device to automatically save and exit.
- Exit Setting Mode: To exit settings, either cycle through all parameters until 'End setting' is displayed and press SET, or wait for the device to time out and automatically exit.

Figure 6: Flowchart illustrating the product setting parameters (A1-A12, OFF) and how to adjust them.
Parameter List:
| Parameter | Description | Range | Default |
|---|---|---|---|
| A1 | Power-on delay time | 1-500s | 10s |
| A2 | Over-voltage protection value | 230-300V | 270V |
| A3 | Over-voltage recovery value | 225-295V | 250V |
| A4 | Over-voltage recovery delay time | 1-500s | 30s |
| A5 | Over-voltage protection action time | 0.1-30s | 0.5s |
| A6 | Under-voltage protection value | 140-210V | 170V |
| A7 | Under-voltage recovery value | 145-215V | 190V |
| A8 | Under-voltage recovery delay time | 1-500s | 30s |
| A9 | Under-voltage protection action time | 0.1-30s | 0.5s |
| A10 | Over-current protection value | 0.5-40A / 0.5-63A | 20A / 40A |
| A11 | Over-current recovery delay time | 1-500s | 30s |
| A12 | Over-current protection action time | 0.1-30s | 0.5s |
| A13 | Voltage calibration | +/- 9.5% | 0% |
| OFF | Manual switch (turn off protection) | On/Off | On |
6. Maintenance
- Keep the device clean and free from dust. Use a dry, soft cloth for cleaning.
- Do not use abrasive cleaners or solvents.
- Ensure adequate ventilation around the device during operation.
- Regularly check wiring connections for tightness.
- If the device is not going to be used for an extended period, disconnect it from the power supply and store it in a dry, cool place.
7. Troubleshooting
- Device not powering on: Check the input power supply and wiring connections. Ensure the main circuit breaker is on.
- Protection tripping unexpectedly: Verify that the set protection values (over-voltage, under-voltage, over-current) are appropriate for your load and power supply. Check for actual voltage/current fluctuations in your circuit.
- Display not working: Ensure the device is receiving power. If power is present and the display is still off, the device may be faulty.
- Device not recovering automatically: Check the recovery delay time settings. Ensure the fault condition has cleared.
8. Specifications
| Function | Technical Parameter | Function | Technical Parameter |
|---|---|---|---|
| Input voltage | AC 140-300V | Power-on delay time | 1-500s (default 10s) |
| Over-voltage protection value | 230-300V (default 270V) | Over-voltage recovery value | 225-295V (default 250V) |
| Under-voltage protection value | 140-210V (default 170V) | Under-voltage recovery value | 145-215V (default 190V) |
| Over-current protection value | 0.5-40A (default 20A) / 0.5-63A (default 40A) | Over-current recovery value | 0-39.5A / 0-62.5A |
| Recovery delay time | 1-500s (default 30s) | Action time | 0.1-30s (default 0.5s) |
| Power consumption | ≤2W | Electrical and mechanical life | ≥100,000 cycles |
| Boundary dimension | 86×38×68mm | Wiring | Over-entering down-out |

Figure 7: Device dimensions: 85mm height, 37.5mm width (front view); 65mm depth, 45mm height from DIN rail (side view).
8.1. Applicable Regulations and Harmonized Standards
- Low Voltage Directive (LVD) 2014/35/EU
- Electromagnetic Compatibility (EMC) Directive 2014/30/EU
- Restriction of the Use of Certain Hazardous Substances (RoHS) Directive 2011/65/EU
9. User Tips
- Many users find this device easy to set up, configure, and install, making it a straightforward addition to your electrical system.
- Always double-check your wiring against the diagram before powering on to ensure correct functionality and safety.
- Take advantage of the adjustable parameters to fine-tune the protection levels to perfectly match the requirements of your specific appliances and electrical environment.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your original point of purchase or the TOMZN official support channels.
11. Disposal Information
This product contains electronic components and should not be disposed of with general household waste. Please follow local regulations for the disposal of electronic waste. Look for collection points or recycling facilities in your area.


Recycle this product and its packaging responsibly.