TOMZN DTS238-2L3W WIFI Three Circuit Single Phase Energy Meter User Manual

Model: DTS238-2L3W

1. Introduction

The DTS238-2L3W is a WIFI type static three-circuit single-phase energy meter designed for measuring AC active energy and various electrical parameters. It incorporates advanced large-scale integrated circuit IC and SMT manufacturing technology, offering features such as bidirectional energy measurement, wide voltage range, anti-tamper capabilities, high accuracy, and reliability. This meter is suitable for both single-phase and three-phase power systems, providing comprehensive monitoring and control through its WIFI and RS485 communication interfaces.

The meter is manufactured in compliance with international standards IEC 62052-11 (Electricity metering equipment - General requirements, tests and test conditions) and IEC 62053-21 (Static meters for active energy, classes 1 and 2).

2. Safety Information

  • Installation and maintenance should only be performed by qualified personnel.
  • Ensure the meter is installed in a suitable environment with an ambient temperature range between -25°C to +55°C.
  • The relative humidity should be less than 75%.
  • Avoid installing the meter in areas with corrosive gases.
  • The meter box should be fixed on a strong and flame-resistant wall.
  • All screws must be tightened securely during installation.
  • Do not install or use the meter if it is damaged or if the seals are broken.

3. Product Overview

The DTS238-2L3W energy meter provides a clear display and intuitive indicators for its operational status.

TOMZN DTS238-2L3W Energy Meter with mobile app interface
Figure 3.1: DTS238-2L3W Energy Meter and associated mobile application interface.

3.1. Indicators and Buttons

Diagram of the energy meter showing labels for WIFI, Impulse, L1, L2, L3, and Button
Figure 3.2: Front panel indicators and button.
  • WIFI LED: Flashes when waiting for WIFI distribution network; solid light indicates successful WIFI connection.
  • Impulse LED: Flashes at a speed proportional to the current load of the meter.
  • L1, L2, L3 LEDs: Indicate the status of each phase.
  • Button: Used for display navigation, setting values, and entering WIFI distribution mode (long press for 5 seconds).

3.2. Terminal Layout

Side view of the energy meter showing numbered terminals 1 through 8
Figure 3.3: Side view showing terminal connections.

4. Key Features

Image highlighting features like current, voltage, reactive power, active power, power factor, and frequency measurement
Figure 4.1: Powerful and versatile measurement capabilities.
  • Versatile Measurement: Functions as a three-circuit single-phase or three-phase AC energy meter.
  • Remote Reset: Active energy can be reset to zero via WIFI or RS485.
  • Multi-parameter Measurement: Measures Current, Voltage, Reactive power, Active power, Power Factor, and Frequency.
  • Bidirectional Display: Independently displays positive (import) and reverse (export) active energy for each phase.
  • Protection Alarms: Features overvoltage, undervoltage, and overcurrent alarms for each phase (alarms only, no circuit cut-off).
  • Configurable RS485: Supports modification of Modbus ID and baud rate via RS485.
  • Data Export: History energy consumption data (hour/day/month/year) can be tracked via the APP and exported in Excel format via email.
  • DIN Rail Installation: Standard 35mm DIN rail installation for easy integration into distribution boxes.
  • Independent Metering: Can independently measure the circuits of three rooms or be used in three-circuit single-phase or three-phase power systems in factories. Note: DTS238-2L3W only shows individual energy consumption per circuit, not total energy consumption.
Image showing bidirectional active energy display on the mobile app
Figure 4.2: Bidirectional active energy display.

5. Specifications

Detailed technical parameters of the DTS238-2L3W energy meter are provided below:

Table of meter specifications including type, frequency, current, voltage, accuracy, WIFI, and RS485
Figure 5.1: Meter Specifications.
Table 5.1: General Specifications
Parameter Value
Meter TypeWIFI type three circuit single phase
Rate Frequency50 or 60 Hz
Rated Current10(100)A or 200A clamper CT (special order)
Rated Voltage85-300V (each phase L-N)
Normal Voltage Range80%Un ~ 110%Un
Limits Voltage Range70%Un ~ 120%Un
Accuracy ClassClass 1
WIFI802.11b/g/n, only support 2.4GHz network (not 5GHz)
RS485 PortMODBUS-RTU protocol, 1200~9600bps, None parity, default 9600bps
Dimensions125*65*97MM (approx. 4.92*2.56*3.82 inches)
Max Operating Current80A - 99A
Operating TemperatureNormal
Power SupplyAC
Display TypeDigital Only
CertificationCE

5.2. Product Dimensions

Diagram showing the dimensions of the DTS238-2L3W energy meter
Figure 5.2: Product dimensions (in mm and inches).

6. Installation

6.1. Rail Installation

The meter is designed for standard 35mm DIN rail installation. It can be combined with a circuit breaker and installed in a distribution box.

Image showing the energy meter mounted on a DIN rail
Figure 6.1: Rail installation example.

6.2. Wiring Diagram

Proper wiring is crucial for accurate measurement and safe operation. The equipment is powered by L3, and L3 must be connected.

Wiring diagram for normal type clamper CT connection for three-phase ABC line
Figure 6.2: Normal type clamper CT connection (measures primary circuit data). L1, L2, L3 lines can input from three-phase ABC line for each phase measurement.
Wiring diagram for special order XXXX/5A CT connection for secondary circuit data
Figure 6.3: Special order XXXX/5A CT connection (measures secondary circuit data). L1, L2, L3 lines can input from the same single-phase line for single-phase measurement when your circuit is from the same phase L3 original MCB.
Detailed wiring diagram showing RS485 and CT connections to the meter terminals
Figure 6.4: Wiring diagram for RS485 and CT connections.

Important Notes for CT Connection:

  • For CT input type connection, the power consumed data in the register is not the actual power consumed. The actual power equals the power data in the meter's register multiplied by the CT rate. For example, if the power data in the register is 0.5 kWh and the CT is 800/5A, the actual power consumed is 0.5 kWh X 160 = 80 kWh.
  • Ensure that the three CT wire connections through the side are all the same. Do not have 1 or 2 CT reverse wire connections.

7. Operation

7.1. Mobile Application (APP) Setup and Functions

The DTS238-2L3W can be controlled and monitored via a mobile application. Follow these steps to set up and use the APP:

  1. Download APP: Download the "SMART LIFE" application from Google Play Store or Apple App Store.
  2. Meter Power On: Power on the meter.
  3. Enter WIFI Distribution Mode: Push and hold the setting button on the meter for 5 seconds. The WIFI LED will flash, indicating the meter is in WIFI distribution network waiting status.
  4. Add Device: Ensure your phone is connected to an available 2.4GHz WIFI network (5GHz networks are not supported). Open the SMART LIFE APP. The app may automatically discover the meter if Bluetooth is enabled, or you can click the "Add Device" button and select the meter manually.

7.1.1. APP Interface Overview

Mobile app interface showing L1 Positive active energy data
Figure 7.1: APP display for L1 Positive active energy.
Mobile app interface showing L1 Details with various parameters like CO2 emissions, frequency, temperature, voltage, and current
Figure 7.2: APP display for L1 Details.

7.1.2. Key APP Functions

  • Energy Tracking: View hour/day/month/year history of positive and negative active energy consumption. Export 28-31 days of daily kWh records via email.
  • Parameter Display: Displays real voltage, current, active power, reactive power, power factor, and frequency for each of the three circuits.
  • Customization: Change circuit names within the APP.
  • Alarm Management: View alarm logs for overvoltage, undervoltage, and overcurrent protection. Each protection function can be enabled/disabled and values set via the APP.
  • Operation Records: Access records of relay on/off operations for each circuit.
  • Remote Control: On/off control for the three circuits separately.
  • Timing Control: Set different times for on/off control (note: meter does not have a countdown control function).
  • Data Export: Export energy history to email (only for day kWh or month Wh).
  • Device Settings: Modify device name, share device access, and view device ID information.
  • Real-time Power Curve: View 15-minute interval active power records for the current day.
  • Prepayment Function: If enabled, the meter will automatically cut off power when the balance energy is used up. This function can be enabled/disabled via APP for each circuit.
  • Energy Reset: Active energy can be reset to zero from the APP for each circuit. Note: If you reset energy, you should delete the device from the APP and reconnect WIFI again for history records to display correctly.
  • Solar Power Generation Support: Suitable for solar power generation systems, displaying import and export energy separately. RMS active power will show positive and negative symbols.
Mobile app interface showing protection settings for overvoltage, undervoltage, and overcurrent
Figure 7.3: APP protection settings interface.

7.2. Meter Display Items

The LCD on the meter displays various parameters. Use the Up/Down buttons to navigate through the display items.

Table showing LCD display items and their corresponding values for L1, L2, L3 phases
Figure 7.4: LCD Display Items.

8. RS485 Communication

The DTS238-2L3W supports MODBUS-RTU protocol for RS485 communication, allowing for remote reading and control. The equipment supports modifying the Modbus ID via RS485.

Image showing the meter with text 'Free to modify the baud rate and Modbus ID'
Figure 8.1: Modbus ID and Baud Rate Configuration.

8.1. Modbus Register Addresses

The following tables detail the Modbus register addresses for various parameters:

Table of Modbus register addresses for L1 phase parameters
Figure 8.2: L1 Phase Modbus Register Addresses.
Table of Modbus register addresses for L3 phase parameters and communication baud rate settings
Figure 8.3: L3 Phase Modbus Register Addresses and Communication Baud Rate Settings.

Notes for RS485 Communication:

  • One register address stores 2 bytes of data. Therefore, the data length read should be 4 bytes when the data number is 2.
  • You can use ID 0 (broadcast) to obtain data if the meter ID is unknown. This method is primarily for 1-phase meter connection on RS485.
  • When decoding data, refer to the signed/unsigned format for active and reactive power.

9. Maintenance

9.1. Storage Conditions

  • The product should be stored in its original packaging.
  • Maintain a storage temperature between -40°C to +70°C.
  • The relative humidity should be less than 75%.
  • Ensure there are no corrosive gases in the storage environment.

9.2. Cleaning

Keep the meter clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.

10. Troubleshooting

  • Meter Not Working: If the meter is not working, check the L1 phase voltage. The meter's internal work voltage is derived from the L1 phase; if L1 loses phase, the other two phases will also not work.
  • WIFI Connection Issues: Ensure you are connected to a 2.4GHz WIFI network, as 5GHz networks are not supported. If the WIFI LED is flashing, long-press the setting button for 5 seconds to re-enter WIFI distribution mode.
  • Meter Cut-off: If the meter cuts off unexpectedly, verify your protection mode settings and phase sequence. If unsure, try disabling the reverse phase sequence protection.
  • Energy Reset and History: If you reset the active energy to zero, you must delete the device from the APP and reconnect it for the history records to display correctly.
  • Protection Alarms: The overvoltage, undervoltage, and overcurrent protection functions are designed to trigger alarms only and cannot cut off the circuit.
  • Leakage Current/Temperature Protection: This meter does not support leakage current or temperature protection functions.

11. User Tips

  • Leverage the APP: Fully utilize the "SMART LIFE" app for remote monitoring, historical data tracking, and convenient configuration of protection settings.
  • Monitor Alarms: Regularly check the alarm logs in the APP to stay informed about any overvoltage, undervoltage, or overcurrent events.
  • Verify CT Connections: Always ensure that the Current Transformer (CT) connections are correct and consistent (e.g., all wires passing through the same side) to guarantee accurate energy readings.
  • Data Export: Use the email export feature for historical energy data to analyze consumption patterns over time.

12. Warranty and Support

12.1. Warranty Period

The product comes with a 12-month warranty from the date of sale. This warranty is valid provided that the user operates the meter correctly according to the instructions in this manual. If the meter fails to meet its technical specifications under normal operating conditions, it will be repaired or replaced free of charge by the manufacturer.

12.2. Additional Resources

For further item guides and documents, please refer to the official PDF manual available at: User Manual (PDF)