DAXTROMN EGH-4.2KW

Contents

DAXTROMN 4.2KW 24V Hybrid Solar Inverter User Manual

Model: EGH-4.2KW

Brand: DAXTROMN

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the DAXTROMN 4.2KW 24V Hybrid Solar Inverter. Please read this manual thoroughly before proceeding with installation and operation. Keep this manual for future reference.

The inverter is designed to manage photovoltaic power, offering both on-grid and off-grid capabilities with an integrated MPPT 120A solar charge controller. It supports various battery types, including lithium batteries, and can operate without a battery.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • Before using the unit, read all instructions and cautionary markings on the unit, batteries, and all appropriate sections of this manual.
  • CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  • To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • CAUTION: Only qualified personnel can install this device with a battery.
  • NEVER charge a frozen battery.
  • For optimum operation, follow required specifications for appropriate cable sizes.
  • Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
  • Strictly follow the installation procedure when disconnecting AC or DC terminals.
  • A fuse is provided for over-current protection for the battery supply.
  • GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  • NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  • Warning!! Only qualified service persons are able to service this device. If errors persist after troubleshooting, send the inverter/charger back to a local dealer or service center for maintenance.

3. Product Overview

The DAXTROMN 4.2KW Hybrid Solar Inverter is designed for efficient power conversion and management in solar energy systems. It features a robust design with clear indicators and communication ports for comprehensive system monitoring and control.

Product Overview Diagram showing inverter components
Figure 3.1: Product Overview with labeled components.

Key components and indicators:

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons (ESC, UP, DOWN, ENTER)
  6. Grounding
  7. RS232 communication port
  8. RS485 communication port
  9. AC input
  10. Main out
  11. Second out
  12. Battery input
  13. PV input
  14. Power on/off switch
DAXTROMN 4.2KW 24V Hybrid Solar Inverter front view
Figure 3.2: Front view of the DAXTROMN 4.2KW Hybrid Solar Inverter.

4. Setup (Installation)

4.1 Unpacking and Inspection

Before installation, inspect the unit for any damage. The package should contain:

  • The inverter unit x 1
  • User manual x 1
  • AC terminals (red x 3 / black x 3)
  • PV terminals (red x 1 / black x 1)
  • Ground terminal (red x 1)

4.2 Preparation

Before connecting any wirings, remove the bottom cover by unscrewing the two screws.

4.3 Mounting the Unit

Consider the following when selecting an installation location:

  • Do not mount the inverter on flammable materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Ambient temperature should be between 0°C and 55°C for optimal operation.
  • Adhere to vertical wall mounting.
  • Ensure sufficient space (as shown in diagrams) for heat dissipation and wiring.

WARNING: Suitable for mounting on concrete or other non-combustible surfaces only.

Diagram showing inverter mounting dimensions and clearances
Figure 4.1: Recommended mounting clearances for heat dissipation.

4.4 Battery Connection

CAUTION: Install a separate DC over-current protector or disconnect device between the battery and inverter. All wiring must be performed by qualified personnel. Use appropriate cable sizes to reduce risk of injury.

Recommended battery cable and terminal sizes:

Model Maximum Amperage Battery Capacity Wire Size Cable mm² Torque Value
4.2KVA 175A 200AH 1AWG 50 4~6 Nm
6.2KVA 130A 200AH 2AWG 35 4~6 Nm

Steps for battery connection:

  1. Make positive and negative cables based on recommended terminal size.
  2. Connect all battery packs as units require. It's suggested to use recommended battery capacity.
  3. Insert battery cable flatly into the battery connector of the inverter and ensure bolts are tightened with a torque of 4~6Nm. Verify correct polarity at both the battery and the inverter/charger.
Connection diagram showing solar, generator, utility, battery, and home appliance connections to the inverter
Figure 4.2: General connection diagram for the hybrid solar inverter.

4.5 AC Input/Output Connection

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION: Do not place anything between the flat part of the inverter terminal. Overheating may occur. Do not apply anti-oxidant substance on the terminals before tightening. Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and protected from overcurrent. Recommended AC breaker spec is 50A.

CAUTION: There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for AC input connection.

Suggested cable requirement for AC wires:

Model Gauge Torque Value
4.2KVA 10AWG 1.4~1.6 Nm
6.2KVA 10AWG 1.4~1.6 Nm

Steps for AC input/output connection:

  1. Before making AC input/output connection, open the DC protector or disconnector.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the screws. Connect the PE protective conductor (yellow-green) first.
  4. WARNING: Ensure AC power source is disconnected before hardwiring.
  5. Insert AC output wires according to polarities and tighten screws. Connect PE protective conductor first.

This inverter has dual output (main out and second out). The main output handles heavy loads (e.g., air-conditioners, heaters), while the second output handles light loads (e.g., lights, computers). The second output's cutoff point is typically lower than the main output to ensure light loads are not cut off prematurely.

CAUTION: Important. Connect AC wires with correct polarity. Reversed L and N wires can cause utility short-circuit in parallel operation.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If power fluctuates, the inverter may trigger an overload fault to protect appliances, but internal damage can still occur. Check if your appliance has a time-delay function.

4.6 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules. All wiring must be performed by qualified personnel. Use appropriate cable sizes.

Suggested cable requirement for PV wires:

Model Typical Amperage Cable Size Torque
4.2KVA 27A 10 AWG 1.4~1.6 Nm
6.2KVA 27A 10 AWG 1.4~1.6 Nm

PV Module Selection considerations:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.

Example PV module configurations (450Wp and 550Wp):

Product Data Sheet showing PV module configuration tables
Figure 4.3: Recommended PV module configurations for 4.2KVA and 6.2KVA models.

PV Module Wire Connection steps:

  1. Remove 6mm of insulation sleeve for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) and negative pole (-) to negative pole (-).
  3. Ensure wires are securely connected.

4.7 Final Assembly

After connecting all wirings, replace the bottom cover by screwing in the three screws.

5. Operation

5.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Operation and Display Panel

The front panel features an LCD display, three indicators (Status, Charging, Fault), and four function keys (ESC, UP, DOWN, ENTER) to show operating status and input/output power information.

LED Indicator Color State Message
AC/INV Green Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
CHG Green Solid On Battery is fully charged.
Flashing Battery is charging.
FAULT Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.

Function Keys:

  • ESC: To exit setting mode
  • UP: To go to previous selection
  • DOWN: To go to next selection
  • ENTER: To confirm the selection in setting mode or enter setting mode

5.3 LCD Setting

Press and hold the ENTER button for 3 seconds to enter setting mode. Use UP/DOWN to select programs and ENTER to confirm or ESC to exit.

Refer to pages 12-19 of the PDF manual for a comprehensive list of LCD setting programs and their options, including output source priority, charging current, battery type, voltage ranges, and more.

5.4 Battery Equalization

The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, extending battery life. It's recommended to equalize batteries periodically.

To apply equalization:

  1. Enable battery equalization in LCD setting program 33.
  2. Set equalization interval in program 37 or activate immediately in program 39.

The inverter will enter the Equalize stage when the set interval is reached or immediately activated. It charges the battery until the equalization voltage is met, then maintains this voltage. If the battery voltage doesn't reach the target within the equalized time, the time will be extended. If still not reached after the timeout, equalization stops, and the inverter returns to float stage.

Battery Equalization Charging Curve Diagram
Figure 5.1: Battery Equalization Charging Curve.

5.5 Setting for Lithium Battery

If using a lithium battery, ensure it is a compatible type. Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter. This communication cable transmits vital information for charging and discharging.

Lithium battery communication and settings allow for:

  • Re-configuring charging voltage, current, and discharge cut-off voltage based on lithium battery parameters.
  • Inverter to start or stop charging according to the lithium battery status.

Ensure the lithium battery RS485 port connects pin-to-pin to the inverter's RS485 port. Refer to the manual for pin assignments (PIN1: RS485-B, PIN2: RS485-A, PIN7: RS485-A, PIN8: RS485-B).

For PYLON US2000 lithium batteries, configure dip switches for baud rate and battery group address. Dip 1 "ON" for baud rate 9600. Dips 2, 3, and 4 are for battery group address on the master battery.

After connecting, select program 05 as lithium battery type and confirm programs 12/13/29/31/41/42 settings. If communication is successful, the battery icon "Li" on the LCD will light up, and specific lithium battery information will be displayed.

For lithium batteries without communication, set battery type to "LIB" in program 05. Then, configure C.V voltage (program 26), floating charging voltage (program 27), low DC cut-off voltage (program 29), and max charging current (program 02) based on the battery's BMS specifications. The setting value for the voltage point back to utility source (program 12) must be ≥ Low DC cut-off voltage + 2V to avoid low battery warnings.

6. Maintenance

Regular maintenance ensures the longevity and optimal performance of your DAXTROMN Hybrid Solar Inverter.

  • Cleaning: Before any cleaning or maintenance, always disconnect all wirings to prevent electric shock. The unit features a detachable dust cover for easier cleaning in harsh environments. Regularly clean the inverter's exterior and ventilation openings to ensure proper airflow and heat dissipation.
  • Battery Inspection: Periodically check battery connections for tightness and corrosion. Ensure battery polarity is correct. Monitor battery voltage and performance, especially if using lead-acid batteries, and perform equalization as recommended.
  • Wiring Checks: Periodically inspect all AC, DC, and PV wiring for any signs of wear, damage, or loose connections. Ensure all terminals are securely tightened to the specified torque values.
  • Environmental Conditions: Ensure the inverter is operating within the recommended ambient temperature range (0°C to 55°C) and humidity levels (5% to 95% non-condensing).

7. Troubleshooting

This section provides guidance on common issues, fault codes, and warning indicators. If problems persist after following these steps, contact qualified service personnel.

7.1 Fault Reference Codes

Fault Code Fault Event
01Over temperature of inverter module
02Over temperature of DCDC module
03Battery voltage is too high
04Over temperature of PV module
05Output short circuited.
06Output voltage is too high.
07Overload time out
08Bus voltage is too high
09Bus soft start failed
10PV over current
11PV over voltage
12DCDC over current
13Over current or surge
14Bus voltage is too low
15Inverter failed (Self-checking)
18Op current offset is too high
19Inverter current offset is too high
20DC/DC current offset is too high
21PV current offset is too high
22Output voltage is too low
23Inverter negative power
24Op2 current offset is too high

7.2 Warning Indicators

Warning Code Warning Event Audible Alarm
02Temperature is too HighBeep three times every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
14Fan blockedNone
15PV energy is lowBeep twice every 3 seconds
19Lithium Battery communication is failedBeep once every 0.5 second
21Lithium Battery over currentNone
22The load exceeds the set value of program 47None
49Battery equalizationNone
50Battery is not connectedNone

7.3 Common Problems and Solutions

Problem Explanation / Possible Cause What to do
Unit shuts Down automatically during startup process. The battery voltage is too low 1. Re-charge battery. 2. Replace battery.
No response after power on. 1. The battery voltage is far too low. 2. Battery polarity is connected reversed. 1. Check if batteries and wiring are connected well. 2. Re-charge battery. 3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing. Input protector is tripped Check if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode. Insufficient quality of AC power. (Shore or Generator) Check if AC wires are too thin and/or too long. Check if generator (if applied) is working well or if input voltage range setting is correct.
Green LED is flashing (Mains exist but unit works in battery mode). Set "Solar First" as the priority of output source. Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly. Battery is disconnected. Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on. (Fault code 07) Overload error. The inverter is overload 110% and time is up. Reduce the connected load by switching off some equipment.
Buzzer beeps continuously and red LED is on. (Fault code 05) Output short circuited. Check if wiring is connected well and remove abnormal load.
Buzzer beeps continuously and red LED is on. (Fault code 02) Internal temperature of inverter component is over 100°C. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Buzzer beeps continuously and red LED is on. (Fault code 03) Battery is over-charged. The battery voltage is too high. Return to repair center. Check if spec and quantity of batteries meet requirements.
Buzzer beeps continuously and red LED is on. (Fault code 06/22) Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) 1. Reduce the connected load. 2. Return to repair center.
Buzzer beeps continuously and red LED is on. (Fault code 08/09/15) Internal components failed. Return to repair center.
Buzzer beeps continuously and red LED is on. (Fault code 13) Over current or surge. Restart the unit, if the error happens again, please return to repair center.
Buzzer beeps continuously and red LED is on. (Fault code 14) Bus voltage is too low. If the wires are connected well, please return to repair center.
Another fault code (Refer to Fault Reference Codes) Consult the full user manual or contact support.

8. Specifications

Detailed technical specifications for the DAXTROMN 4.2KW Hybrid Solar Inverter.

8.1 General Specifications

Attribute Value (4.2KVA Model) Value (6.2KVA Model)
Model NumberEGH-4.2KWEGH-6.2KW
Output Current120A120A
Size (D*W*H)368*328*120 mm438*328*120 mm
Weight6.9 kgs8.05 kgs
Output TypeSINGLESINGLE
Output Frequency50/60 Hz50/60 Hz
Is Smart DeviceYes (with optional WiFi module)Yes (with optional WiFi module)
OriginMainland ChinaMainland China
CertificationCECE
Operating Temperature Range-10°C to 55°C-10°C to 55°C
Storage Temperature-15°C to 60°C-15°C to 60°C
Humidity5% to 95% Relative Humidity (Non-condensing)5% to 95% Relative Humidity (Non-condensing)

8.2 Line Mode Specifications (Table 1)

Parameter 4.2KVA 6.2KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage (UPS)170Vac±7V
Low Loss Voltage (Appliances)90Vac±7V
Low Loss Return Voltage (UPS)180Vac±7V
Low Loss Return Voltage (Appliances)100Vac±7V
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionBattery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time (UPS)10ms typical
Transfer Time (Appliances)20ms typical

8.3 Inverter Mode Specifications (Table 2)

Parameter 4.2KVA 6.2KVA
Rated Output Power4.2KVA / 4.2KW6.2KVA / 6.2KW
Dual output functionYesYes
Max. main output power4.2KVA6.2KVA
Max. second output power4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz or 60Hz
Peak Efficiency94%
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage (AGM/Flooded, load < 20%)22.0Vdc44.0Vdc
Low DC Warning Voltage (AGM/Flooded, 20% ≤ load < 50%)21.4Vdc42.8Vdc
Low DC Warning Voltage (AGM/Flooded, load ≥ 50%)20.2Vdc40.4Vdc
Low DC Cut-off Voltage (AGM/Flooded, load < 20%)21.0Vdc42.0Vdc
Low DC Cut-off Voltage (AGM/Flooded, 20% ≤ load < 50%)20.4Vdc40.8Vdc
Low DC Cut-off Voltage (AGM/Flooded, load ≥ 50%)19.2Vdc38.4Vdc

8.4 Charge Mode Specifications (Table 3)

Parameter 4.2KVA 6.2KVA
Max Charging Current (PV+AC)120Amp120Amp
Max Charging Current (AC)120Amp120Amp
Bulk Charging Voltage (Flooded Battery)29.2Vdc58.4Vdc
Bulk Charging Voltage (AGM / Gel Battery)28.2Vdc56.4Vdc
Floating Charging Voltage27Vdc54Vdc
Overcharge Protection32Vdc63Vdc
Battery reverse connection protectionNoNo
Charging Algorithm3-Step

8.5 Solar Input Specifications

Parameter 4.2KVA 6.2KVA
Rated Power6200W9000W
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. Input Current27A
Max. Charging Current (PV)120A

9. User Tips

  • The inverter has been successfully tested with 280A battery packs, indicating good compatibility with higher capacity batteries.
  • Ensure all connections are secure and polarity is correct, especially for battery and AC inputs, to prevent issues during startup and operation.
  • If you encounter any issues or have questions, the seller is generally communicative and responsive.
  • Consider purchasing the optional Wi-Fi module for remote monitoring capabilities, which can enhance system management.

10. Warranty and Support

For detailed warranty information and technical support, please refer to the complete user manual PDF or contact the seller directly. The seller's store name is Daxtromn Power Global Store.

A comprehensive user manual in PDF format is available for download. This document contains additional detailed diagrams, LCD setting explanations, and in-depth troubleshooting guides.

You can access the full user manual (PDF) for more detailed information.

Documents and downloads

Ask a question about this manual